Intelligent Graphic Repeater Panel

  

                                            

 

                

Installation and Operation Manual

 

  

                                                  

      

 

 

The Intelligent Solution

 

 

 

Page 5 

 Shut down power supply and take off the two jumpers on Pin X1. Plug P-9910B to 

the socket XS1.Write-in the indicator number and code. Re-plug the two jumpers to 
Pin X1. Switch on the power supply, the repeater panel will start self- test. The first 
is the sound test and all indictors will be lit. After the self-test, only the “Work” 
indicator will be lit in the normal situation. If all indicators twinkle every two seconds 
and the speaker gives a trouble signal, it means the EEROM data is wrong. 

4. Operation 

4.1 Under the monitoring state, only the “Work” indicator is lit, it has polling function 

(When the host control panel is polling the repeater panel, the indicator will 
twinkle once). Pressing self-test key, the repeater panel will inspect the display 
components and the sound. 

4.2 In case of fire alarm, the indicator corresponding with the detector code will be 

lit. If it is the latest alarm, the indicator will twinkle (every 0.5 second) and give 
an alarm sound at the same time. Pressing the “Mute” key, it could mute the 
alarm sound. If there is fire alarm again, the mute state will be called off, and the 
repeater panel gives an alarm over again. 

4.3 In the EEROM trouble state, all the indicators will twinkle (in 2-second period). 

The speaker will give a trouble sound at the same time. You need to reprogram 
the EEROM, write-in the indicator number and code again. 

5. Programming 

 

5.1 Programming is done by P-9910B Hand Held Programmer. 
5.2 Method for entering and exiting programming to the repeater panel:  

Connect the programmer with the repeater panel, then input 2, 5, 8 and press 
the “Function” key to start programming to the repeater panel. After the above 
operation, input 2, 5, 8 again and press the “Function” key to exit programming. 

5.3 Reading out and writing in the address code:  

5.3.1  Enter repeater panel programming mode, “0” is displayed on the 

screen. 

5.3.2  Press the “Down” key, it displays the current address code. 
5.3.3  To change the coded point, you can directly input the required code 

(1-64) and press the “Program” key. If the

 

coding is successful, then it 

will display “P” on the screen. 

5.3.4 Press 

Clear

 key, then other operations could be continued. 

5.4 Programming of the LED number and its corresponding user code. 

5.4.1  Enter into the repeater panel programming mode, “0” is on the screen. 
5.4.2  Input the required LED number, press the 

Function

 key, L and LED 

number (1-256) is on the screen. 

5.4.3  There will be two cases: 

a) Not to change the LED number: Press “Function” key, “0” is shown on 

the screen, then input the required user code.

 

(6 digits in total, you can 

input the figure of 0-9 to each digit. Pressing “Down”, “-” will be shown 
which means the user code could represent any figures. For GST200  
panel, the first digit represents the network number of the device, the 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Содержание 8903

Страница 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 2: ...eration 4 VII Troubleshooting 7 VIII Cautions 7 Appendix 1 Installation of the Mainboard 8 Appendix 2 Installation of the LED Board 9 Appendix 3 Installation of the Membrane 10 Appendix 4 Installation of the Buzzer 11 Appendix 5 Installation of the LED 12 Appendix 6 Configuration of the Whole 13 Appendix 7 Connection of Repeater Panel 14 Appendix 8 Membrane of Repeater Panel and Corresponding LED ...

Страница 3: ... information can be displayed by each mainboard 3 Wiring Connected with fire alarm control panel with two polarized wires connected with power supply with two 24VDC power lines non polarized 4 Operating Current Monitoring Current 25mA Alarming Current 100mA 5 Operating Environment Environment Temperature 0 40 Relative Humidity 95 non condensing 6 Power Centralized power supply by 18VDC 28VDC quies...

Страница 4: ...LED Board Installation method is shown in Fig 2 See Appendix 2 and 6 for more information 115 0 2 40 0 2 255 0 2 5 5 265 LED Board Fig 2 LED board 3 Mounting of the Membrane Installation method is shown in Fig 3 See Appendix 3 and 6 for more information 4 R2 0 7 0 2 7 2 0 0 15 Fig 3 Membrane Door 114 15 7 5 Through hole Membrane pasted with in the frame Through hole HTTP GSTRU RU E MAIL hombi homb...

Страница 5: ...alarm sound Press this key again or fire alarm recurs the repeater panel will sound again Fig 4 4 Mounting of the Buzzer Installation method is shown in Fig 5 See Appendix 4 and 6 for more information Fig 5 Buzzer 5 Mounting of the LED Installation method is shown in Fig 6 See Appendix 5 and 6 for more information Fig 6 the LED 6 Mounting of the Repeater Panel The repeater panel is wall mounted Dr...

Страница 6: ...uld be shielded 1 0mm2 cable and the shield cover should be connected with GNDG on the main board 24VDC power cable should be 4 0mm2 cable 8 Wiring Connection of boards is shown in Fig 7 9 Commission Program the device number and user code before power up The repeater panel should work normally VI Operation Set up the system according to the project requirement 1 The repeater panel is defaulted as...

Страница 7: ...speaker will give a trouble sound at the same time You need to reprogram the EEROM write in the indicator number and code again 5 Programming 5 1 Programming is done by P 9910B Hand Held Programmer 5 2 Method for entering and exiting programming to the repeater panel Connect the programmer with the repeater panel then input 2 5 8 and press the Function key to start programming to the repeater pane...

Страница 8: ...in the new LED number and user code so that this operation can be used to modify an incorrect LED number and user code At most 100 LED numbers can be written in the screen will show PPPP when all numbers have been finished 2 Every fire alarm signal can only light one LED of GST8903 even if all LED are defined the same It cannot be defined to display by device and by zone at the same time 5 4 4 Aft...

Страница 9: ...tion cable is not well connected b The power supply is not well connected c The transformer secondary coil is not well soldered d 75176 optocoupler and other nearby components are damaged a Connect it in a right way b Connect it in a right way c Solder again d Replace the damaged parts 5 No sound a Triode VT2 and its peripheral components are damaged b Buzzer is damaged a Replace the damaged compo...

Страница 10: ...ent Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 8 Appendix 1 Installation of the Mainboard 97 0 2 106 0 2 214 0 2 116 5 5 Mainboard Box body Weld Nut 6 M3 8 HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 11: ...nt Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 9 Appendix 2 Installation of the LED Board 115 0 2 40 0 2 255 0 2 LED Board Box Body 6 M3 40 5 5 265 Ⅰ Weld nut HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 12: ...d Operation Manual The Intelligent Solution Page 10 Appendix 3 Installation of the Membrane 114 Through hole 4 R2 15 0 7 0 2 0 7 0 2 15 7 5 106 0 2 10 20 136 15 18 18 32 18 3 2 M3 9 5 0 0 1 2 1 Ⅰ M 6 1 Weld nut Ⅰ Remove keyboard Switch Panel HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 13: ...igent Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 11 Appendix 4 Installation of the Buzzer 45 0 2 Through hole 2 M3 2 6 14 Ⅰ Ⅰ 2 1 buzzer Box Body Weld nut HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 14: ... RU GST8903 Intelligent Graphic Repeater Panel Installation and Operation Manual The Intelligent Solution Page 12 Appendix 5 Installation of the LED 1 2 3 4 A B 6 5 Through hole B HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 15: ...he Whole 上 上 下 下 雨棚 下 A A A A A A Second Floor 室 UP Repeater Panel 1 2 3 4 5 6 5 5 7 8 5 9 10 11 I I remove box body 12 Notes Make memebrane according to plan of the floor Make enclosure according to membrane and fix light emitting diode at corresponding positions with plastic sleeve and nylon sleeve Enlarge A Direction A HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 16: ...0 HL31HL32 HL93HL94 HL95 HL96 HL64 HL61HL62 HL63 HL99HL100 HL32 XS2 Buzzer Buzzer XS1 HL2 HL56 HL55 HL34 HL33 HL97 HL2 HL3 HL4 Mould Zone Discharge Zone A V6 TCC Process Zone F CPerformance Test and Packing Zone die casting zone A HL1 HL5 HL1 N Scaleboard N Mainboard1 LED Board1 HL98 Strategic Area Switchboard Name Cable No Model and Size Length Remarks Buzzer Cable X01 After Mainboard soldered Ri...

Страница 17: ...d Operation Manual The Intelligent Solution Page 15 Appendix 8 Membrane of Repeater Panel and Corresponding LED Number Membrane of Repeater Panel and The Corresponding LED Number Stick the relevant drawing according to the project requirement HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 18: ...T UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst uk com GST Dubai Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email info gst uk com www gst uk com HTTP GSTRU RU E MAIL ho...

Отзывы: