GST 852RPX Скачать руководство пользователя страница 3

HTTP://WWW.HOMBI.RU

 

GST852RPX LCD Repeater Panel                                                               
Installation and Operation Manual

 

  

                                                  

      

 

 

The Intelligent Solution

 

 

Page 1  

I General 

GST852RPX LCD Repeater Panel (the repeater panel) is designed with a 

microprocessor to display the user code and description of the alarming detector 

(detectors) and generate audible and visual signals simultaneously.  

II Features 

Through communication loops, GST852RPX LCD repeater panel can connected with 

GST200, GST500 and GST5000 fire alarm control panels, processing and displaying 

the data transmitted from the control panels. Command of 

Silence

 

and 

Reset

 can be 

sent to the control panel, and the 

Silence

 command can stop the output of sounder. 

When one fire alarm control panel monitors several floors or several zones, a repeater 

panel can be installed on each floor or in each zone instead of zonal control panel. 

III Technical Specifications

 

1. 

Display Range: Each screen displays no more than 1 piece of fire information. The 

following can be displayed in turn.  

2. 

Display Capacity: Not more than 126 pieces of fire information can be displayed by 

the repeater panel. 

3. 

Wiring: Connected with fire alarm control panel through polarity sensitive two wires; 

connected with power supply through two 24VDC power lines, polarity insensitive.  

4. Operating 

environment: 

       Temperature: 0

℃~

+40

 

       Relative Humidity: 

95%, non condensing 

5.  Power supply: centralized electrification by 24VDC power supply. 

6.  Quiescent power consumption 

2W; Maximum power consumption 

5W 

IV  Structure and Operation Principle

 

1.  GST852RPX LCD repeater panel is wall-mounted. Fig.1 shows its appearance.

 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Содержание 852RPX

Страница 1: ...HTTP WWW HOMBI RU HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 2: ...Installation and Operation Manual The Intelligent Solution CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 1 V Operation 3 VI Troubleshooting 4 VII Cautions 4 HTTP GSTRU RU E MAIL hombi hombi ru ...

Страница 3: ...monitors several floors or several zones a repeater panel can be installed on each floor or in each zone instead of zonal control panel III Technical Specifications 1 Display Range Each screen displays no more than 1 piece of fire information The following can be displayed in turn 2 Display Capacity Not more than 126 pieces of fire information can be displayed by the repeater panel 3 Wiring Connec...

Страница 4: ...ys 1 Silence Key In monitoring state the repeater panel enters in power save mode and it will exit the current state when this key is pressed again In alarm state pressing Silence key and inputting password can stop the sound of the repeater panel Then send the command of silence to the control panel Press it again the repeater panel will cancel the silence command and transmit the command to the ...

Страница 5: ...djusting LCD definition If the LCD display isn t clear you can adjust the LCD ADJ adjusting resistor to make the LCD display clearly 3 System setting In monitor state the repeater panel enters system setting screen with pressed and 6 digit password 666666 is super password input 1 Password modification Selecting number 1 the screen of password modification appears then input a new password twice I...

Страница 6: ...versed 2 The wires are threaded in the same tube with strong current circuit 1 Change the polarization of communication two wire 2 Separate the two wire cables from strong current circuit The LED of repeater panel flashes regularly when it is normal VII Cautions 1 This panel is precise electronic product and must be maintained by trained personnel 2 This product must be in the charge of trained pe...

Страница 7: ...mail sales gst com cn www gst com cn GST UK Global System Technology PLC Enterprise Glade Bath Lane Moira South Derbyshire England DE12 6BD Tel 44 0 1283 225 478 Fax 44 0 1283 220 690 Regional Office PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email tech support gst uk com www gst uk com HTTP GSTRU RU E MAIL hombi hombi ru ...

Отзывы: