GST852RPX LCD Repeater Panel
Installation and Operation Manual
The Intelligent Solution
Page 1
I General
GST852RPX LCD Repeater Panel (the repeater panel) is designed with a
microprocessor to display the user code and description of the alarming detector
(detectors) and generate audible and visual signals simultaneously.
II Features
Through communication loops, GST852RPX LCD repeater panel can connected with
GST200, GST500 and GST5000 fire alarm control panels, processing and displaying
the data transmitted from the control panels. Command of
Silence
and
Reset
can be
sent to the control panel, and the
Silence
command can stop the output of sounder.
When one fire alarm control panel monitors several floors or several zones, a repeater
panel can be installed on each floor or in each zone instead of zonal control panel.
III Technical Specifications
1.
Display Range: Each screen displays no more than 1 piece of fire information. The
following can be displayed in turn.
2.
Display Capacity: Not more than 126 pieces of fire information can be displayed by
the repeater panel.
3.
Wiring: Connected with fire alarm control panel through polarity sensitive two wires;
connected with power supply through two 24VDC power lines, polarity insensitive.
4. Operating
environment:
Temperature: 0
℃~
+40
℃
Relative Humidity:
≤
95%, non condensing
5. Power supply: centralized electrification by 24VDC power supply.
6. Quiescent power consumption
≤
2W; Maximum power consumption
≤
5W
IV Structure and Operation Principle
1. GST852RPX LCD repeater panel is wall-mounted. Fig.1 shows its appearance.
E-MAIL: [email protected]