7-5 IM ( Switch input management )
Press the " SETUP Button " once, LCD will show :
1:AD 2:IO 3: TEL
SETUP SCREEN
4:RP 5:IM 6:SAVE
* key in " 5 ", LCD will show
Alarm : Close ( Pulse )
IM SETTING SCREEN
( 0): P ,(1): C
@ IM function is to set the two kind switch alarm
type : Close alarm or Pulse alarm
@ 0 = Pulse alarm, 1 = Close alarm
@ Close alarm type : Input switch is normal open,
if the switch is closed, send the SMS alarm
message out. if the switch is opened again, the
alarm SMS message will stop.
@ Pulse alarm type : Input switch is normal open, if
the switch is closed, send the SMS alarm message
out. if the switch is opened again, the alarm SMS
message will still send continuously no matter the
switch open again.
Under the " Pulse alarm " type, if intend to stop
the alarm SMS, it should do as :
1. From the system " IO " setting function to let
the switch input alarm disable.
2. From mobile to send the SMS command :
( SET-DIP-ALARM 00000000 ) , refer Chapter 8
page 24.