English (GB)
15
5.1.2 Servomotor with analogue control (optional), connected, for example, to a Conex
®
DIS-2Q (microprocessor-based controller)
• Connect the terminals to the corresponding terminals on the external controller as shown in the connection diagram.
Fig. 19
Terminal connection diagram for Conex
®
DIS-2Q on a servomotor with integrated electronics
1. Unscrew the hood screws and remove the hood.
2. Establish the electrical connections in accordance with the
circuit diagram; see fig.
– Connect terminals 51 and 52 and, if required, terminals 54
and 55, in accordance with the circuit diagram.
– Connect terminals 56 and 57 in accordance with
requirements; voltage 125 V max.
– Use separate, shielded lines with a minimum cross-section
of 0.5 mm
2
and a maximum length of 1000 m for low
voltages (setpoint/actual value signal lines).
– The screen must be connected on one side to the housing
earth (earth terminal).
• Close the hood again and tighten the hood screws.
Servomotor - with reversing potentiometer (optional)
Fig. 20
Terminal connection diagram for servomotor with
reversing potentiometer
TM
04 09
52 400
9
15 16 17 18 19 20 21 22 23
24
25
26
L1
N
P E
1
2
3
4
5
6
7
8
9 10 11 12 13 14
4(0) - 20 mA
max. 125 V
56 57
55
54
52
51
+
+
L
N
P E
Item
Description
L
Phase
Mains voltage input
N
Neutral
PE (earth)
51
Signal input (-)
52
Signal input (+)
54
Signal output (-)
55
Signal output (+)
56
Collective error message
57
Note
See Section
for warnings and notes relating to
electrical connection!
Warning
The internal wiring of the drive must never be
modified.
TM
04 09
53 400
9
Item
Description
1 N
Neutral
2
Phase
Mains voltage input
(for direction "open/max.")
3
Phase
Mains voltage input
(for direction "close/min.")
4
Mains voltage output
(position "final position max.")
5
Mains voltage output
(position "final position min.")
PE (earth)
18
Start
19
Slider
20
End
N
open
min.
PE
max.
close
N
2
3
4
5
18 19 20
< 50 V
start
slider
end
< 50 V
1
SL (max.) SR (min.)
Motor control
feedback potentiometer
Limit switches