Pos. Description
1
Start level
Recommended start levels in relation to the inlet
height and pipe configuration
7.1.1 Setting the start levels with a controller
LC 220
Select a start level, either "LOW" or "HIGH", via the
DIP switches. The stop and alarm levels are set
automatically according to the selected start level.
LOW
HIGH
Start level
[mm]
180
500
Stop level
[mm]
100
100
Alarm level
[mm]
350
600
See the installation and operating instructions of the
controller for more information about the DIP
switches.
You can change the values corresponding to "LOW"
and "HIGH" via PC Tool, which is available as an
accessory. Product number: 96705378.
LC 221
Go go [Setup], [L_01] and select one of the following
start levels. The stop and alarm levels are set
automatically according to the selected start level.
1
2
3
4
5
Start level
[mm]
180
250
350
450
500
Stop level
[mm]
100
100
100
100
100
Alarm level
[mm]
350
400
550
600
600
7.1.2 Setting the start levels with float switches
Set the start and stop levels by adjusting the free
cable length (L).
29
English (GB)
Содержание UNOLIFT
Страница 1: ...UNOLIFT DUOLIFT Installation and operating instructions GRUNDFOS INSTRUCTIONS ...
Страница 2: ......
Страница 18: ...TM059633 UNILIFT AP35B AP50B TM059630 UNILIFT CC KP 18 English GB ...
Страница 19: ...x4 TM082793 UNILIFT APG x4 TM059632 SEG 19 English GB ...
Страница 20: ...x4 TM078303 DUOLIFT SEG 20 English GB ...
Страница 21: ...x4 TM082794 DUOLIFT UNILIFT APG 21 English GB ...
Страница 36: ...Appendix A A 1 Appendix TM061067 Unolift 270 Duolift 270 678 Appendix A ...
Страница 37: ...TM061066 Duolift 540 679 Appendix A ...