System configuration
In this menu, the submenus for the configuration of the system
can be opened.
Fig. 65
System configuration
To revert to the previous menu, push [
].
For details on general menu symbols see section
.
8.5.30
Configuration of system capacity
In this menu, the system capacity and the brine dosing station
can be configured.
Fig. 66
Configuration of system capacity
To change a value, push the respective square. Active values are
highlighted in green.
To save the settings, push [
].
To revert to the previous menu, push [
].
For details on general menu symbols see section
Menu action
Required user level
Access menu
2
Parametrising staff
Reset configuration to factory
settings
3
Commissioning staff
ID 01
1
0
Display text
Description
See
section
System
capacity / brine
pumps
Push the symbol next to this text to
open menu "
Configuration of system
capacity
".
Tank volume /
fans
Push the symbol next to this text to
open menu "
Configuration of tank
volume
".
Interface
Push the symbol next to this text to
open menu "
Configuration of
interface
".
Factory
settings
Push the symbol next to this text to
reset all settings to factory default.
Alarm delays
Push the symbol next to this text to
open menu "
Settings alarm delays
".
Delay-/flushing
times
Push the symbol next to this text to
open menu "
Settings delay-/flushing
times
".
Operating
hours counters
plant
Push the symbol next to this text to
open menu "
Settings Operating
hours Counter plant
".
Operating
hours counters
lines
Push the symbol next to this text to
open menu "
Settings Operating
hours Counter lines
".
Menu action
Required user level
Access menu
4
Administrators
Change settings
4
Administrators
ID 0
11
1
The value "
System capacity
" must comply with the
actual capacity level of the Selcoperm electrolyser.
The standard setpoints of the system are based on
this value.
Setting a wrong value may result in damage to the
equipment.
Display text
Description
System
capacity
This setting must comply with the actual
capacity level of the Selcoperm electrolyser. A
system restart is required if this parameter was
changed.
No. of brine
pumps
Number of brine pumps within the brine dosing
station.
Automatic
changeover at
If two brine pumps are used, the cause for a
changeover from the duty pump to the standby
pump and vice versa can be defined here.
•
Start & fault
The system changes over every time
production is started and after a fault.
•
Fault
The system changes over after a fault.
•
never
The system does not change over
automatically.