Settings tank level
In this menu, the settings of the degassing and storage tank can
be viewed and changed.
Fig. 52
Settings tank level
To change a value, touch the respective field and enter the new
value via the numeric keyboard. See section
To save the settings, push [
].
To reset the values to factory settings, push [
].
To revert to the previous menu, push [
].
For details on general menu symbols see section
.
8.5.17
Overview fans
This menu gives an overview of the degassing fans of the
degassing and storage tank. The display below is shown in
systems with two degassing fans. For systems with one fan, the
options for the second fan are not displayed.
Fig. 53
Overview fans
Changes done in this menu are taken over by the system
immediately.
If a fan is currently in use and the user sets the value "
blocked
"
for it, the system changes over to the standby fan. If no standby
fan is present, an error message is shown and the system stops.
To revert to the previous menu, push [
].
For details on general menu symbols see section
For details on component colours see section
.
Menu action
Required user level
Access menu
2
Parametrising staff
Change settings
2
Parametrising staff
Reset to factory settings
3
Commissioning staff
ID
00
41
Display text
Description
Process
Parameters for the electrolysis process.
•
Start
When this NaClO level is reached in the
tank, the system switches to operating state
"Production" and starts to fill the tank.
•
Stop
When this NaClO level is reached in the
tank, the system switches to operating state
"Standby" and stops filling the tank.
Enable dosing /
transfer
Parameters for dosing or transfer pumps
installed downstream the degassing and
storage tank.
•
Dosing
"
Start
": When this NaClO level is reached in
the tank, the system enables dosing.
•
Transfer
"
Start
": When this NaClO level is reached in
the tank, the system enables transfer.
•
Stop
When this NaClO level is reached in the
tank, the system disables dosing and
transfer.
Exhaust air
Parameters for the exhaust air flow
generated by the degassing fan. The values
are monitored with exhaust air flow sensor
(4.13). See section
.
•
min.
Minimum value
•
max.
Maximum value
t
Time delay before an alarm is triggered
after a value range was undercut or
exceeded. Time delay in seconds.
Menu action
Required user level
Access menu
No login required
Change settings
1
Users
ID
0
0
5
1
Display text /
symbol
Description
Exhaust air flow sensor. Next to the symbol
the name (see PID) and the measured value
are displayed. Below the measured value the
minimum and maximum values are displayed.
To change those values see section
Operation
The value "
enabled
" means, that the fan is
enabled for operation. The value "
blocked
"
means, that the fan is not enabled for
operation (e.g. for maintenance).
To toggle between these values, push the
respective symbol [
]. A yellow symbol
represents the value "
blocked
".
Operating
hours counter
Operating hours of each fan.