background image

English (GB)

7

4.3 How to set the correct pressure

The pump can be set to provide a water pressure between 1.5 to 
5.5 bar (22 to 80 psi) at intervals of 0.5 bar (7 psi).
The factory setting is 3 bar (44 psi). See sectio

3.2 System 

sizing

.

4.3.1 Boosting from a well or a tank

If you are boosting from a well or a tank, make sure not to set the 
pressure setpoint too high. The difference between the inlet 
pressure and outlet pressure must not exceed 3.5 bar (51 psi).

Fig. 10

Boosting from a well or a tank

4.3.2 Boosting from the mains

The pressure settings 4.5, 5.0 and 5.5 bar (65, 73 and 80 psi) 
require a positive inlet pressure and these settings must only be 
used when boosting from the water mains.

Fig. 11

Boosting from the mains

4.3.3 Self-learning setpoint

If the pump cannot reach the user-defined pressure setpoint, the 
self-learning function will automatically lower the setpoint. See 
section 

8.3.2 Self-learning function

.

4.4 Shaft seal run-in

The shaft seal faces are lubricated by the pumped liquid. A slight 
leakage from the shaft seal of up to 10 ml per day or 8 to 10 drops 
per hour may occur.
When the pump is started up for the first time, or when the shaft 
seal has been replaced, a certain run-in period is required before 
the leakage is reduced to an acceptable level. The time required 
for this depends on the operating conditions, that is, every time 
the operating conditions change, a new run-in period will be 
started.
Under normal conditions, the leaking liquid will evaporate. As a 
result, no leakage will be detected.
The leakage is visible where the screws are mounted on the base 
plate. If the unlikely event of an internal leakage occurs, the liquid 
will be drained through the bottom of the pump. Install the pump 
in such a way that no undesirable collateral damage can arise.

5. Handling and storing the product

5.1 Handling the product

5.2 Storing the product

If the pump is to be stored for a period of time, for example during 
the winter, drain it and store it indoors in a dry location. See 
section 

10. Starting up the product after standstill

.

Temperature range during storing must be -40 to 70 °C (-40 to 
158 °F).

6. Product introduction

6.1 Product description

Fig. 12

Grundfos SCALA2 pump

The inlet and outlet openings include flexible connections of ± 5 °.

We recommend to use the default pressure of 3.0 bar 
(44 psi) which will suit most applications.

The difference between the inlet pressure and outlet 
pressure must not exceed 3.5 bar (51 psi).
Example: If the inlet pressure is 0.5 bar (7 psi), the 
maximum outlet pressure is 4 bar (58 psi).

If you set the pressure too high, this might cause the 
pump to operate for up to three minutes after the tap 
is turned off.

Maximum setpoint

[bar (psi)]

Well application

3.0 (44)

Tank below ground level

3.5 (51)

Tank above ground level

4.0 (58)

TM

07 00

75 41

17

TM

07 00

76 41

17

TM

07

 00

74 

41

17

Take care not to drop the pump as it may break.

Maximum relative humidity during storing: 95 % RH.

T

M

06

 38

18

 10

15

Pos. Description

1

Air valve for built-in pressure tank

2

Operating panel. See section 

7. Control functions

.

3

Nameplate. See section 

6.4.1 Nameplate

.

4

Plug for access to pump shaft. See section 

10.1 Deblocking the pump

.

5

Priming plug. See section 

4.1 Priming the pump

.

6

Outlet opening. See section 

3.3.3 Connecting the piping 

system

.

7

Inlet opening. See section 

3.3.3 Connecting the piping 

system

.

8

Drain plug. See sectio

6.4 Identification

.

9

Ventilation holes. They must not be flooded.

1

5

6

7

8

2

3

4

9

Содержание SCALA Series

Страница 1: ...SCALA Installation and operating instructions GRUNDFOS INSTRUCTIONS http waterheatertimer org Water heater recirculation system html...

Страница 2: ...9 8 Setting the product 10 8 1 Setting the outlet pressure 10 8 2 Locking and unlocking the operating panel 10 8 3 Expert settings SCALA2 10 8 4 Resetting to factory settings 11 9 Servicing the produ...

Страница 3: ...1 25 bar 18 psi In case of suction lift of more than six metres the pipe resistance on the outlet side must be at least two metres water column or 3 psi at any given flow in order to obtain optimum op...

Страница 4: ...f the flexible hose Fig 4 How to reduce noise in the installation 3 3 5 Installation examples Fittings hoses and valves are not supplied with the pump We recommend to follow the installation examples...

Страница 5: ...ction lift is 8 m 26 ft H2 Inlet pipe must be submersed at least 0 5 m 1 64 ft TM06 4348 4117 Pos Description 1 Highest tapping point 2 Pipe hangers 3 Isolating valve 4 Flexible hoses 5 Drain to sewer...

Страница 6: ...ertain that the pump is connected only to a properly grounded grounding type receptacle protective earthing If national legislation requires a Residual Current Device RCD a Ground Fault Circuit Interr...

Страница 7: ...ent of an internal leakage occurs the liquid will be drained through the bottom of the pump Install the pump in such a way that no undesirable collateral damage can arise 5 Handling and storing the pr...

Страница 8: ...temperature 13 Minimum and maximum rated power 14 Model 15 Voltage and frequency 16 Approvals 17 Minimum and maximum rated current DK 8850 Bjerringbro Denmark SCALA2 3 45 AKCHDE Model A 200 240V 50 60...

Страница 9: ...e cause has disappeared or been remedied See section 8 3 3 Auto reset For further information about system status see section 12 Fault finding the product TM06 3301 5114 SCALA2 Function On off Increas...

Страница 10: ...tpoint The pump will lower the setpoint to either 4 5 3 5 or 2 5 bar 65 51 or 36 psi The self learned setpoint is indicated on the operating panel by one flashing green light After every 24 hours the...

Страница 11: ...bottom and can easily be removed and cleaned with a stiff brush See fig 19 Clean the insect filter once a year or as needed Fig 19 Insect filter 9 1 2 Inlet and outlet valves The pump is maintenance f...

Страница 12: ...uct 4 The pump will remember the controller settings even if it is turned off 10 1 Deblocking the pump The end cover incorporates a plug which can be removed by means of a suitable tool This makes it...

Страница 13: ...reset function in the service menu Grundfos Eye Indication Description No lights are on The power is off The pump is not running Two opposite green indicator lights running in the direction of rotatio...

Страница 14: ...completely or partly open position Clean repair or replace the non return valve See section 9 Servicing the product 2 The pump is running a Leakage from the pipe system or the non return valve is not...

Страница 15: ...ump but it runs only for a few seconds Yes a Dry running or water shortage Check the water source and prime the pump Yes b The inlet pipe is blocked by impurities Clean the inlet pipe Yes c The foot o...

Страница 16: ...ontact the nearest Grundfos company or service workshop See also end of life information on www grundfos com product recycling Temperature C F Maximum ambient temperature 1 x 208 230 V 60 Hz 45 113 1...

Страница 17: ...8 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznes...

Страница 18: ...8564 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: