Grundfos PHP A-4 Скачать руководство пользователя страница 1

PHP A-4, 6, 8 & 9  

Supplement to Instruction manual  

PHP A-1 4.0 & 5.6 

UK version, original instructions

Содержание PHP A-4

Страница 1: ...PHP A 4 6 8 9 Supplement to Instruction manual PHP A 1 4 0 5 6 UK version original instructions...

Страница 2: ...due to model and configuration of the delivered PHP device INFORMATION This document refers to PHP series devices with software version V1 22 Design and operation can vary slightly due to the existing...

Страница 3: ...perature monitoring of the media streaming into the vessel Prepared connection point for mounting a makeup module for a per litre accurate measuring Combinable with an option for water softening for s...

Страница 4: ...position where no external pressure can occur External pressures could affect the trouble free operation of the pressure maintenance device 2 2 Degassing module PHP EMAE 1 makeup module PHP EMCF 1 V M...

Страница 5: ...1 V sensor T2 1 Makeup water 4 Discharge hopper for vessel safety valve 5 Suction pipe from expansion vessel 6 Overflow pipe from expansion vessel 7 Gas side vessel connection DN20 8 Expansion pipe fr...

Страница 6: ...nd main vessel additional vessels expansion modules makeup module EMCF 1 V sensor T2 1 Makeup water 4 Discharge hopper for vessel safety valve 5 Suction pipe from expansion vessel 6 Overflow pipe from...

Страница 7: ...vessel additional vessels expansion modules makeup module EMCF 1 V water treatment sensor T2 cooling vessel EV 1 Makeup water 4 Discharge hopper for vessel safety valve 5 Suction pipe from expansion...

Страница 8: ...4 Wiring diagrams PHP A 4 6 8 9 Instruction Manual Wiring diagrams 08 4 1...

Страница 9: ...PHP A 4 6 8 9 Instruction Manual Wiring diagrams 09...

Страница 10: ...PHP A 4 6 8 9 Instruction Manual Wiring diagrams 10...

Страница 11: ...nal 24378 Date Date Replaced by 11 Revision 10 17 16 Appr Replacement of 18 19 13 6 14 07 05 2019 12 Name 15 PHP Control Panel Ferryboat Lane Castletown Sunderland Tyne and Wear SR5 3JL DRAWING No She...

Страница 12: ...P1 B5 Temperature sensor T1 sending element type KTY10 6 or compatible B6 Temperature sensor T2 sending element type KTY10 6 or compatible B7 Lower vessel pressure transmitter PL2u OPTION B8 Upper ves...

Страница 13: ...expansion pipe NOTE Steps 1 3 must be completed on site in preparation for the commissioning Figure 3 determination of the upper and lower working pressure 10m wc meter water column 1 bar NOTE Commis...

Страница 14: ...overflow pipe see figure 5 detail B until a continuous water jet leaks from the ventilation valve detail A at the pressure maintenance pump To ensure a complete ventilation of the pump start and stop...

Страница 15: ...e acknowledgement only if module is installed not available default setting is available analog signalling only if module is installed not available default setting is available temperature sensor T2...

Страница 16: ...subsequently the working pressure must be set anew Select settings pressure maintenance working pressure The display shows the current settings complies with the last set working pressure e g default...

Страница 17: ...e output degassing valve output on Wait until the motor valve opened completely ca 35 sec the scale resp the red axis at the electric actuator must not rotate anymore Open the ball valve at the intake...

Страница 18: ...for future service 2 Connect the BSP Male OVERFLOW connection to drain 3 Allow the BREAK TANK to fill from the mains water connection and set the BALL FLOAT such that the BREAK TANK water level stops...

Страница 19: ...6 0 10 4 6 0 10 4 2 4 6 2 2 4 6 2 2 4 6 2 2 4 6 2 2 4 6 6 6 0 10 1 2 4 6 6 6 0 10 1 2 4 6 6 2 4 6 6 8 0 16 0 8 0 16 0 2 4 6 6 6 0 11 0 2 4 6 6 6 0 11 0 bar 10 16 25 16 C 70 V Hz voltage max electrica...

Страница 20: ...8 560 878 1370 914 939 406 202 217 R 6 4 R 6 4 Rp 6 4 MCM D6 964 1064 1035 1137 188 560 794 1370 914 939 406 204 219 R 6 4 R 6 4 Rp 6 4 MCM D8 1142 1242 1098 1200 216 560 803 1368 1466 1491 594 325 34...

Страница 21: ...1 99478310 Spare PHP Analogue Board Board expansion module analogue signalling 90624 99478311 Spare PHP Binary board Board expansion module binary signalling 90625 99478312 Spare PHP Level Transmitter...

Страница 22: ...e NOTE To ensure a correct function of the pressure maintenance unit you have to consider the following instructions for the connection between PHP and expansion vessels up to 500M 800M and above 1 2...

Страница 23: ...PHP A 4 6 8 9 Instruction Manual Appendix 23 Suction pipe overflow pipe...

Страница 24: ...PHP A 4 6 8 9 Instruction Manual EC declaration of Conformity 24 9 EC declaration of Conformity...

Страница 25: ...GRUNDFOS PUMPS LTD Grovebury Road Leighton Buzzard Bedfordshire LU7 4TL T 01525 850 000 E grundfos uk sales grundfos com Article number 61 739_00 08 2019 Grundfos I O Manual PHP A 4 6 8 9...