Temperature influence is suitable in:
•
systems with variable flows (e.g. two-pipe heating
systems), in which the activation of the
temperature influence function will ensure a
further reduction of the pump performance in
periods with small heating demands and
consequently a reduced flow-pipe temperature.
•
systems with almost constant flows (e.g. one-pipe
heating systems and underfloor heating systems),
in which variable heating demands cannot be
registered as changes in the head as is the case
with two-pipe heating systems. In such systems,
the pump performance can only be adjusted by
activating the temperature influence function.
Selection of T
max.
In systems with a dimensioned flow-pipe
temperature of:
•
up to and including 55 °C, select T
max.
= 50 °C,
•
above 55 °C, select T
max.
= 80 °C.
7.7 External start/stop
The pump can be started or stopped via an external
potential-free contact or a relay connected to
terminals 7 and 8, see section
Functional diagram: Start/stop input
7.8 Signal relay
The pump incorporates a signal relay, terminals
1, 2 and 3, for a potential-free fault and operating
signal. The function of the signal relay, fault signal
(factory setting), ready signal or operating signal, is
set with the R100.
The output, terminals 1, 2 and 3, is electrically
separated from the rest of the controller.
The signal relay is activated as follows:
•
Fault signal
The signal relay is activated together with the red
indicator light on the pump, see section
.
•
Ready signal
The signal relay is active when the pump is
running or has been set to stop, but is ready to
run, see section
•
Operating signal
The signal relay is activated together with the
green indicator light on the pump, see section
.
Functions of signal relay
Resetting of fault indications
A fault indication can be reset in one of the following
ways:
•
Briefly press
,
or
on the pump. This will
not influence the pump performance set.
•
Briefly switch off the electricity supply to the
pump.
•
With the R100, see section
Before the pump can revert to normal duty, the fault
cause must be eliminated.
If the fault disappears by itself, the fault indication
will automatically be reset.
The fault cause will be stored in the pump alarm log.
The latest five faults can be called up with the R100.
Note
The temperature influence function
cannot be used in air-conditioning
systems.
Start/stop input
Normal duty
Stop
Q
H
Q
H
Signal relay Fault signal
Not activated:
• The electricity supply has been
switched off.
• The pump has not registered
a fault.
Activated:
• The pump has registered a fault.
Signal relay
Ready signal
Not activated:
• The pump has registered a fault
and is unable to run.
Activated:
• The pump has been set to stop,
but is ready to run.
• The pump is running.
Signal relay Operating signal
Not activated:
• The pump has been set to stop.
• The pump has registered a fault
and is unable to run.
Activated:
• The pump is running.
• The pump has registered a fault,
but is able to run.
1
3
2
NC NO C
1 2
3
NC NO C
1
3
2
NC NO C
1 2
3
NC NO C
1
3
2
NC NO C
1 2
3
NC NO C
Содержание MAGNA 2000 Series
Страница 4: ...4...
Страница 160: ...160 2 4 3 GENI 7 12 1 3 4 4 4 4 4 5 TM02 5507 3402 1 2 3 4 5 6 Rp 3 TM03 8831 2607 5 4 6 TM02 0640 0301...
Страница 163: ...163 6 11 8 8 TM02 5508 3402...
Страница 164: ...164 7 R100 19 172 AUTOADAPT R100 GENI 0 10 V bus GENIbus O Control MPC Series 2000 Grundfos 7 12 1 LON bus LON LonWorks...
Страница 166: ...166 7 2 7 2 1 AUTOADAPT Grundfos AUTOADAPT AUTOADAPT 1 4 2 3 fan coils 1 2 2 3 4...
Страница 169: ...169 R100 8 4 R100 R100 7 9 19 8 2 2 9 7 10 GENI LON 14 14 14 R100 5 1 TM02 0241 0904 2 TM02 0242 0904 3 TM02 0805 0904...
Страница 174: ...174 8 2 4 7 5 MIN 24 24 8 2 5 STOP 8 2 6 0 255 sec 8 3 R100 R100 Grundfos R100 R100 R100 R100 TM02 0247 2507 R100 H MIN...
Страница 176: ...176 8 5 R100 R100 8 5 1 8 8 AUTOADAPT R100 AUTOADAPT Stop Q H 8 5 2 Stop AUTOADAPT 8 5 3 8 5 4 R100...
Страница 177: ...177 8 6 8 6 1 0 10 V 8 6 2 Stop R100 BUS 8 6 3 8 6 4 8 6 5 8 6 6 8 6 7...
Страница 178: ...178 8 7 8 7 1 7 1 7 4 AUTOADAPT 8 5 1 AUTOADAPT 8 7 2 8 7 3 7 6 8 7 1 50 C 80 C 8 5 1 8 7 4 R100 8 7 5 AUTOADAPT R100...
Страница 180: ...180 9 5 1 2 R100 3 on off off 4 bus 1 2 R100 3 on off 4 bus R100 8 5 3...
Страница 181: ...181 R100 8 5 3 Grundfos AUTOADAPT AUTOADAPT R100...
Страница 182: ...182 10 GRUNDFOS MAGNA 1 2 L N 3 L B 4 A 5 L C 1000 VAC 1500 VDC L N 35 mA 6 A 7 L B 8 L 9 TM02 0238 0904 A B C...
Страница 310: ...310 1 1 1 1 2 1 3 1 4 1 5 1 6 DIN 4844 W00...
Страница 311: ...311 1 7 1 8 1 9 3 2 15150 3 GRUNDFOS MAGNA 2000 4 GRUNDFOS MAGNA 4 1 o VDI 2035 GRUNDFOS MAGNA 14...
Страница 313: ...313 5 4 4 4 5 5 0 C TM02 0640 0301...
Страница 314: ...314 6 5 5 6 6 6 1 1 x 230 240 10 6 50 60 5 3 11 1 TM02 0456 3503 2 TM02 0457 3503 1 TM02 7441 3503 2 TM02 7442 3503...
Страница 316: ...316 7 12 8 8 TM02 5508 3402...
Страница 317: ...317 8 R100 19 327 ADAPT R100 GENI 0 10 GENIbus Grundfos Control MPC 2000 8 12 1 LON LON LonWorks...
Страница 319: ...319 8 2 Grundfos ADAPT ADAPT 1 HN 4 1 2 3 1 HN 2 1 2 3 4...
Страница 322: ...322 8 8 1 2 3 R100 1 2 3 9 2 9 2 9 2 1 3 2 NC NO C 1 2 3 NC NO C 1 3 2 NC NO C 1 2 3 NC NO C 1 3 2 NC NO C 1 2 3 NC NO C...
Страница 323: ...323 R100 9 4 R100 R100 8 9 19 9 2 2 10 8 10 GENI LON 14 14 14 R100 5 1 TM02 0241 0904 2 TM02 0242 0904 3 TM02 0805 0904...
Страница 327: ...327 9 1 ADAPT 9 2 19 10 19 9 2 1 8 1 3 20 4 19 1 2 3 4 5 TM03 8798 2507 TM03 1288 1505 ADAPT ADAPT ADAPT ADAPT...
Страница 329: ...329 9 2 5 STOP 9 2 6 0 255 9 3 R100 Grundfos R100 R100 R100 R100...
Страница 331: ...331 9 5 R100 R100 9 5 1 9 8 ADAPT R100 ADAPT Q H 9 5 2 ADAPT 9 5 3 9 5 4 A R100...
Страница 332: ...332 9 6 9 6 1 0 10 9 6 2 R100 9 6 3 9 6 4 9 6 5 9 6 6 0 9 6 7 0...
Страница 333: ...333 9 7 9 7 1 8 1 8 4 ADAPT 9 5 1 ADAPT 9 7 2 9 7 3 8 6 9 7 1 50 80 9 5 1 9 7 4 R100 9 7 5 P ADAPT R100...
Страница 334: ...334 9 7 6 1 64 R100 Grundfos Control MPC 2000 9 8 R100 R100 R100 Grundfos R100 1 2 3 4 5 R100 1 2 3 4 5 6...
Страница 335: ...335 10 5 GRUNDFOS 1 2 R100 3 4 1 2 R100 3 4 R100 9 5 3 GRUNDFOS...
Страница 336: ...336 R100 9 5 3 Grundfos e ADAPT ADAPT R100...
Страница 339: ...339 13 1 2 Grundfos 14 24 Grundfos...
Страница 342: ...342 MAGNA 32 120 40 120 50 120 65 120 50 60 65 60 TM02 0477 1004 C NO NC N L O P T S 7 8 3 2 1...
Страница 347: ...347 Positioning TM04 3266 4108...
Страница 348: ...348...
Страница 349: ...349...
Страница 350: ...350...