English (GB)
18
7. Systems with 2 electrodes
Description (see also page
):
The pump is controlled by the liquid level in the borehole.
• The electrode, pos. 1, is the reference electrode.
• When the electrode, pos. 2, registers liquid, the "waiting time"
is initiated (can be set). After expiration of the waiting time, the
pump is started.
• The pump is stopped when the electrode, pos. 2, does
not
register any liquid.
• The pressure switch, pos. 3, stops the pump if the discharge
pressure exceeds the stop pressure of the pressure switch.
Restarting at the starting pressure of the pressure switch is
only effected if the electrode, pos. 2, registers liquid.
7.1 Electrical connection
2 electrodes, pages
and
.
Fig.
on page
.
The figures show all electrical connections required to connect
the LC 108 for
direct-on-line starting, 2 electrodes
.
Fig.
on page
.
The figure shows all electrical connections required to connect
the LC 108 for
star-delta starting, 2 electrodes
.
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the
electricity supply on which it will be used.
All cables/wires must be fitted through the Pg cable entries and
gaskets (IP65).
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, an external mains
switch must be installed.
Single-phase motors must be connected to an external operating
capacitor and in certain cases also to a starting capacitor.
Further details can be found in the installation and operating
instructions for the pump in question.
The pressure switch, pos. 3, must be connected as an NC
contact.
Key to the symbols in fig.
on page
on page
:
7.2 Setting
2 electrodes, pages
The CU 211 module has a 10-pole DIP switch in the bottom right
corner, see fig.
.
The DIP switch setting offers the following possibilities:
• selection of starting delay and automatic test run (switch 4),
• setting of waiting time (switches 5, 6, 7 and 8),
• selection of automatic alarm resetting (switch 9),
• selection of automatic restarting (switch 10).
Fig. 14
Set the DIP switch as shown in fig.
.
Each individual switch (1 to 10) of the DIP switch can be set to
position OFF or ON.
Warning
Before starting any work on pumps used to pump
liquids which could be constituted as being
hazardous to health, thorough cleaning/venting of
pumps, pits, etc. must be carried out according to
local regulations.
Before making any connections in the LC 108 or
work on pumps, pits, etc., it must be ensured that the
electricity supply has been switched off and that it
cannot be accidentally switched on.
Warning
Before starting work on the system, switch off the
supply voltage and lock the mains switch in position
0.
Any external voltage connected to the system must
be switched off before work is started.
Warning
The LC 108 must be connected in accordance with
the rules and standards in force for the application in
question.
Caution
If the PTC resistance/thermal switch of the motor is
connected, the factory-fitted short-circuit jumper
must be removed (terminals T11-T21).
Warning
Float switches or electrodes placed in an explosion
hazard area must be connected via an EEx barrier,
e.g. Grundfos number 96440300. The EEx barrier
must not be installed in the explosion hazard area.
Equipment used in explosion hazard areas must in
each individual case have been approved for this
particular application. Furthermore, the cables into
the explosion hazard area must be laid in
accordance with local regulations.
Note
The motor/pump housing must not be used as
reference electrode.
Pos. Description
Terminal
number
1
Reference electrode.
11
2
Electrode for start/stop of pump.
12
3
Pressure switch.
41-42
Caution
The controller must be off circuit to ensure the
correct configuration during start-up after change of
the DIP switch setting.
TM
04 234
2 230
8
Note
The DIP switch must not be set to other switch
combinations than those described in this section.