English (GB)

19

19. Digital input

Hydro Multi-E has a digital input for external faults. The input has 
been factory-set to external fault and will be active in closed 
condition.

Functional diagram: input for digital function

If the digital input is active for more than 10

 

seconds (s), Hydro 

Multi-E will stop because of an external fault.
The digital input is used for the dry-running protection.

20. Data communication

It is possible to connect the system to an external network. The 
connection can be made via a GENIbus-based network or a 
network based on another fieldbus protocol.
The system can communicate via CIM modules. This enables the 
system to communicate with different types of network solutions.
A CIM module is an add-on communication interface module. The 
CIM module enables data transmission between the pump and an 
external system, for example a BMS or SCADA system.
For further information on CIM modules, see www.grundfos.com 
(Grundfos Product Center) or contact Grundfos.

21. Insulation resistance

22. Maintenance

22.1 Pumps

Pump bearings and shaft seals are maintenance-free.
If CRE or CRIE pumps are to be drained for a long period of 
inactivity, remove one of the coupling guards to inject a few drops 
of silicone oil on the shaft between the pump head and the 
coupling. This will prevent the shaft seal faces from sticking.

22.2 Motors

Keep motor cooling fins and fan blades clean to ensure sufficient 
cooling of the motor and electronics.

22.3 Breaker cabinet

The breaker cabinet is maintenance-free. Keep it clean and dry.

23. Shutdown

Shut down the system with the main switch in the breaker 
cabinet.

To shut down a pump, switch off the circuit breaker of the pump.

23.1 Frost protection

If pumps are not used during periods of frost, they must be 
drained to avoid damage.
Drain the pump by loosening the vent screw in the pump head 
and removing the drain plug from the base.
Do not tighten the vent screw or refit the drain plug until the 
system is to be used again.

23.2 Service kits

See Grundfos Product Center for service manuals.

Digital function 

(terminals 1 and 9)

Normal duty

External fault 

Q

H

Q

H

10 s

Do not measure the insulation resistance of motor 
windings or an installation incorporating motors with 
integrated frequency converters using high-voltage 
megging equipment, as this may damage the built-in 
electronics. 

DANGER
Electric shock

Death or serious personal injury
- Switch off the power supply and wait at least five 

minutes before you start any work on the product. 
Make sure that the power supply cannot be 
accidentally switched on.

DANGER
Electric shock

Death or serious personal injury
- Do not touch the conductors in front of the main 

switch as they are still energised.

Содержание Hydro Multi-E

Страница 1: ...Hydro Multi E Installation and operating instructions GRUNDFOS INSTRUCTIONS ...

Страница 2: ...w for Grundfos GO Remote 13 13 Multi master function 14 13 1 Systems with one outlet pressure sensor 14 13 2 Systems with two or more outlet pressure sensors 14 14 Protective functions 14 14 1 Dry running protection 14 15 Bus signal 16 16 Priority of settings 16 17 Grundfos Eye 17 18 Signal relays 18 19 Digital input 19 20 Data communication 19 21 Insulation resistance 19 22 Maintenance 19 22 1 Pu...

Страница 3: ...onstant pressure redundant sensor stop at low flow cascade control of pumps automatic alternation pipe filling limit exceeded function two digital inputs two digital outputs two analog inputs optional bus communication via Grundfos CIM modules 4 3 Hydro Multi E Fig 1 Hydro Multi E components The breaker cabinet incorporates a main switch and circuit breakers 5 Identification 5 1 Nameplate Fig 2 Hy...

Страница 4: ...ndard valves B Stainless steel manifold base frame and valves C Galvanised steel manifold base frame and standard valves CME A pumps only G Galvanised steel manifold base frame and standard valves P Stainless steel manifold galvanised steel base frame and standard valves Drinking water approvals A ACS approved components B Belgaqua approved components D DVGW approved components K KIWA approved com...

Страница 5: ...rating conditions that is every time the operating conditions change a new run in period will be started Under normal conditions the leaking liquid evaporates As a result a leakage will not be detected 7 6 Minimum inlet pressure Fig 4 Parameters for the calculation of minimum inlet pressure The minimum inlet pressure H in metres head required to avoid cavitation in the pumps can be calculated as f...

Страница 6: ...of flow of water through the pump The pipes connected to the booster system must be of adequate size Fit expansion joints in the inlet and outlet pipes to avoid resonance See fig 5 Connect the pipes to the manifolds of the booster system The manifold comes with a screw cap fitted to one end If this end is to be used remove the screw cap apply sealing compound to the other end of the manifold and f...

Страница 7: ...o external motor protection The motor incorporates thermal protection against slow overloading and blocking 8 4 Mains supply Check that the supply voltage and frequency correspond to the values stated on the nameplate The wires in the breaker cabinet must be as short as possible Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in ...

Страница 8: ...tors must be connected to a power supply with a quality corresponding to IEC 60146 1 1 class C to ensure correct motor operation at phase unbalance This also ensures long life of the components 9 Startup 9 1 Hydro Multi E in system with positive inlet pressure When you have carried out the mechanical and electrical installation described in section 8 Installation proceed as follows 1 Check that Hy...

Страница 9: ...system 6 Open all pump inlet valves 7 Close all pump outlet valves and prime all pumps and the inlet pipe Fig 10 Position of vent screw and filling screw 8 Switch on the power supply with the main switch 9 Start pump 1 by pressing the start stop button on the pump control panel 10 Vent pump 1 by means of the vent screw 11 Slowly open the outlet valve approximately 50 12 Repeat steps 9 and 11 for t...

Страница 10: ...r settings with Grundfos GO Remote See section 12 Grundfos GO Remote 11 User interfaces Settings can be made by means of the following user interfaces Standard control panel See section 11 1 Standard control panel Grundfos GO Remote See section 12 Grundfos GO Remote If the power supply is switched off the settings will be stored 11 1 Standard control panel Fig 13 Standard control panel TM02 4328 0...

Страница 11: ...he pump performance will lie between the maximum and minimum curve of the pump See fig 15 Fig 15 Pump in constant curve control mode Setting to maximum curve Press continuously to change over to the maximum curve of the pump top light field flashes When the top light field is on press for 3 seconds until the light field starts flashing To change back press continuously until the desired setpoint i...

Страница 12: ...ccess to status overviews technical product information and actual operating parameters Grundfos GO Remote offers three different mobile interfaces MI See fig 18 Fig 18 Grundfos GO Remote communicating with the pump via radio or infrared light 12 1 Communication When Grundfos GO Remote communicates with the pump the indicator light in the middle of Grundfos Eye will flash green See section 17 Grun...

Страница 13: ...ing function Buttons on product LiqTec Stop function Controller Operating range Ramps Pump number Radio communication Analog input 1 Analog input 2 Digital input 1 Digital input 2 Signal relay 1 Signal relay 2 Limit 1 exceeded Limit 2 exceeded Standstill heating Motor bearing monitoring Service Date and time Store settings Recall settings Undo Pump name Unit configuration Alarms and warnings Assis...

Страница 14: ...l the pumps with an outlet pressure sensor If an additional sensor is used for example for the limit exceeded function or setpoint influence this sensor must also be connected to all pumps with an outlet pressure sensor Alternatively an additional sensor per pump with an outlet pressure sensor can be installed 14 1 Dry running protection Types of dry running protection a pressure switch which is f...

Страница 15: ...NC Normally closed contact Signal relay 1 LIVE or SELV C1 Common NO Normally open contact NC Normally closed contact Signal relay 2 SELV only C2 Common NO Normally open contact 18 GND Ground 11 DI4 OC2 Digital input output configurable Open collector Maximum 24 V resistive or inductive 19 Pt100 1000 Pt100 1000 sensor input 2 17 Pt100 1000 Pt100 1000 sensor input 1 12 AO Analog output 0 20 mA 4 20 ...

Страница 16: ...e If two or more functions are enabled at the same time the system will operate according to the function with the highest priority Example If via the digital input the system has been set to maximum speed the pump control panel or Grundfos GO Remote can only set the system to Manual or Stop The priority of the settings appears from the table below If the bus communication is interrupted the syste...

Страница 17: ... has stopped The green indicator light in the middle flashes quickly four times Remote control with Grundfos GO Remote via radio The motor is trying to communicate with Grundfos GO Remote The motor is highlighted in the Grundfos GO Remote display to inform the user of the location of the motor The green indicator light in the middle flashes continuously When you have selected the motor in the Grun...

Страница 18: ...he pump is running Yellow rotating Normal Min or Max Warning but the pump is running in Manual mode Yellow rotating Manual Warning but the pump was stopped via Stop command Yellow steady Stop Alarm but the pump is running Red rotating Normal Min or Max Alarm but the pump is running in Manual mode Red rotating Manual Pump stopped due to an alarm Red flashing Stop NC NO C NC NO C NC NO C NC NO C NC ...

Страница 19: ... the pump head and the coupling This will prevent the shaft seal faces from sticking 22 2 Motors Keep motor cooling fins and fan blades clean to ensure sufficient cooling of the motor and electronics 22 3 Breaker cabinet The breaker cabinet is maintenance free Keep it clean and dry 23 Shutdown Shut down the system with the main switch in the breaker cabinet To shut down a pump switch off the circu...

Страница 20: ...eplace the terminal box of pump 1 Contact Grundfos 4 Unstable water delivery from Hydro Multi E applies only to very low consumption a The inlet pressure is too low Check the inlet pipe and possible inlet strainer b The inlet pipe or pumps are partly blocked by impurities Clean the inlet pipe or pumps c The pumps suck air Check the inlet pipe for leakages d The outlet pressure sensor is defective ...

Страница 21: ...w logic level Vi less than 1 5 VDC Certain high logic level Vi greater than 3 0 VDC Hysteresis No Screened cable 0 5 1 5 mm2 28 16 AWG Maximum cable length 500 m Open collector digital outputs OC Current sinking capability 75 mADC no current sourcing Load types Resistive and or inductive Low state output voltage at 75 mADC Max 1 2 VDC Low state output voltage at 10 mADC Max 0 6 VDC Overcurrent pro...

Страница 22: ...over contacts Minimum contact load when in use 5 VDC 10 mA Screened cable 0 5 2 5 mm2 28 12 AWG Maximum cable length 500 m Bus input Grundfos GENIbus protocol RS 485 Screened 3 core cable 0 5 1 5 mm2 28 16 AWG Maximum cable length 500 m 28 Other technical data EMC electromagnetic compatibility According to EN 61000 6 2 2005 and 61000 6 3 2007 Residential areas unlimited distribution corresponding ...

Страница 23: ...kPa 60 Hz 50 Hz CR 10 CRI 10 CRN 10 CR I E 10 0 0 0 8 1 6 2 4 3 2 4 0 4 8 Q m h 0 1 2 3 4 5 H m 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 Q l s 0 10 20 30 40 50 p kPa 60 Hz 50 Hz CR 3 CRI 3 CRN 3 CR I E 3 0 2 4 6 8 10 12 14 16 18 20 22 24 Q m h 0 1 2 3 4 5 H m 0 1 2 3 4 5 6 7 Q l s 0 16 32 48 p kPa 60 Hz 50 Hz CR 15 CRI 15 CRN 15 CR I E 15 0 1 2 3 4 5 6 7 8 9 10 Q m h 0 1 2 3 4 5 6 H m 0 0 0 4 0 8 1 2 1 6 2...

Страница 24: ...5 0 2 4 6 8 10 12 14 16 Q m h 0 2 4 6 8 10 12 14 H m 0 1 2 3 4 Q l s 0 20 40 60 80 100 120 p kPa 50 Hz 60 Hz CME A I 10 0 2 4 6 8 10 12 14 16 18 20 22 24 Q m h 0 2 4 6 8 10 12 H m 0 1 2 3 4 5 6 7 Q l s 0 20 40 60 80 100 120 p kPa 50 Hz 60 Hz CME A I 15 20 15 12 10 8 0 6 0 5 0 4 0 3 0 2 0 1 0 0 8 0 6 0 4 0 3 0 2 0 1 1 5 120 110 90 100 80 70 60 50 40 30 20 10 0 Hv m tm C 150 130 140 25 35 45 40 30 ...

Страница 25: ...o Multi E uz kuru attiecas šis paziņojums atbilst šādām Padomes direktīvām par tuvināšanos EK dalībvalstu likumdošanas normām LT EB atitikties deklaracija Mes Grundfos su visa atsakomybe pareiškiame kad gaminys Hydro Multi E kuriam skirta ši deklaracija atitinka šias Tarybos Direktyvas dėl Europos Ekonominės Bendrijos šalių narių įstatymų suderinimo HU EK megfelelőségi nyilatkozat Mi a Grundfos eg...

Страница 26: ...n EC No 640 2009 Standards used EN 60034 2 1 2007 Water pumps Commission Regulation No 547 2012 Applies only to water pumps marked with the minimum efficiency index MEI See pump nameplate This EC declaration of conformity is only valid when published as part of the Grundfos installation and operating instructions publication number 98491894 0517 Bjerringbro 7th April 2017 Svend Aage Kaae Technical...

Страница 27: ...10 2011 О безопасности машин и оборудования ТР ТС 020 2011 Электромагнитная совместимость технических средств KAZ Hydro Multi E Пайдалану бойынша нұсқаулық Атаулы өнімге арналған пайдалану бойынша нұсқаулық құрамалы болып келеді және келесі бөлімдерден тұрады 1 бөлім атаулы Пайдалану бойынша нұсқаулық 2 бөлім Грундфос компаниясының сайтында орналасқан электронды бөлім Төлқұжат Құрастыру жəне пайда...

Страница 28: ... Жабдуу жана машиналардын коопсуздугу жөнүндө ТР ТБ 020 2011 Техникалык каражаттардын электрмагниттик шайкештиги ARM Hydro Multi E Շահագործման ձեռնարկ Տվյալ սարքավորման շահագործման ձեռնարկը բաղկացած է մի քանի մասերից Մաս 1 սույն Շահագործման ձեռնարկ Մաս 2 էլեկտրոնային մաս այն է Անձնագիր Մոնտաժման և շահագործման ձեռնարկ տեղադրված Գրունդֆոս Անցեք փաստաթղթի վերջում նշված հղումով Մաս 3 տեղեկություն արտա...

Страница 29: ...Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd...

Страница 30: ...73360 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S www grundfos com ...

Отзывы: