English (GB)
8. Start the main pump
manually by pressing
the [Start] button. Keep
the button pressed until
the pump starts.
10. Stop the main pump
manually by pressing
the [Stop] button.
11. Close the ball valve for testing the pressure switches for the
main pump and the jockey pump.
12. Turn the selector switch
for the main pump to “AUTO”
position by means of the key.
13. Turn the selector
switch for the jockey
pump to “AUTO”
position.
14. Open the isolating valve on the discharge manifold.
Step
Illustration
5. Turn the selector
switch for the jockey
pump to “MAN”
position. The jockey
pump will start.
Note:
If the jockey pump does not start, see section
8.3 Fault
indications
and
15. Fault finding
.
6. As soon as the jockey pump starts, check the direction of
rotation. The correct direction of rotation is indicated by ar-
rows on the fan cover of the motor.
7. Turn the selector
switch for the main
pump to “TEST” posi-
tion by means of the
key.
Note:
If the main pump does not start, see section
8.3 Fault
indications
and
15. Fault finding
.
9. As soon as the main pump starts, check the direction of
rotation. The correct direction of rotation is indicated by
arrows on the fan cover of the motor.
Step
Illustration
15
English
(GB)
15
5. Turn the selector
switch for the jockey
pump to "MAN"
position. The jockey
pump will start.
Note: If the jockey pump does not start, see section
8.3 Fault
indications
and
15. Fault finding
.
6. As soon as the jockey pump starts, check the direction of
rotation. The correct direction of rotation is indicated by
arrows on the fan cover of the motor.
7. Turn the selector
switch for the main
pump to "TEST"
position by means of
the key.
8. Start the main pump
manually by pressing
the [Start] button. Keep
the button pressed
until the pump starts.
Note: If the main pump does not start, see section
8.3 Fault
indications
and
15. Fault finding
.
9. As soon as the main pump starts, check the direction of
rotation. The correct direction of rotation is indicated by
arrows on the fan cover of the motor.
Step
Illustration
10. Stop the main pump
manually by pressing
the [Stop] button.
11. Close the ball valve for testing the pressure switches for the
main pump and the jockey pump.
12. Turn the selector
switch for the main
pump to "AUTO"
position by means of
the key.
13. Turn the selector
switch for the jockey
pump to "AUTO"
position.
14. Open the isolating valve on the discharge manifold.
Step
Illustration