English (GB)

4

1. Symbols used in this document

Safety instructions placed directly on the fire pump set:

2. Applications

The Grundfos Fire HSEF and DNF pump sets are designed for 
fire systems for supplying water to hose reels, fire hydrants and 
sprinkler systems.

The Grundfos Fire HSEF and DNF pump sets with electric motor 
must not be used for ordinary pumping of liquids or common 
pressure boosting in daily work. They should only be used for 
firefighting.
The pump controller must not be used as a junction box for 
supplying other equipment.

3. Delivery, transport, storage

3.1 Delivery

The fire pump set is delivered from factory in an open wooden 
box or wooden/cardboard box which is specifically designed for 
transport by fork-lift truck or similar device.

3.2 Transport

For lifting the entire fire pump set, use the lifting holes of the base 
frame. When lifting, the lifting point should always be above the 
centre of gravity of the fire pump set. See fig. 1.

Fig. 1

Correct lifting of fire pump set

Warning

If these safety instructions are not observed, 
it may result in personal injury.

Caution

If these safety instructions are not observed, 
it may result in malfunction or damage to the 
equipment.

Note

Notes or instructions that make the job easier 
and ensure safe operation.

Warning

Hazardous voltages are present in this 
enclosure. Improper use or failure to 
take precautions can cause serious 
injury, electric shock and/or damage 
to the equipment.

Disconnect all supply sources 
(including any foreign circuits) before 
working on controller, motor or pump.

Only qualified personnel should work 
on or around this equipment.

Warning

The mains terminals are still live when 
the main switch is in position "OFF".

Warning

Phase-sensitive equipment.

Connect in ABC order.

Warning

The enclosure and withstand rating 
are applicable only if all door locks are 
in closed position.

The ambient temperature must be 5 to 
50 °C.

Warning

If an overload or a fault current 
interruption occurs, circuits must be 
checked to determine the cause of the 
interruption. If a fault condition exists, 
the current-carrying components 
should be examined and replaced if 
damaged, and the integral current 
sensors must be replaced to reduce 
the risk of fire or electric shock.

To maintain overcurrent, short-circuit 
and earth-fault protection and to 
reduce the risk of fire or electric 
shock, the manufacturer’s 
instructions for selection of overload 
and short-circuit protection must be 
followed.

Lifting points for the entire fire pump set.

Hazadous voltages are present
inside this enclosure. Serious
injury, electrocution and/or
equipment damage will result of
improper application or if
precaution is not used.

Disconnect all supply sources
(including any foreign circuits)
before working om controller,
motor(s) or pump(s).

Only qualified personnel should
work on or around this
equipment.

LINE TERMINALS ALIVE
WHEN MAIN SWITCH
IS IN “OFF” POSITION

DANGER

PHASE SENSITIVE EQUIPMENT

CONNECT IN ABC ORDER

WARNING

ENCLOSURE AND WITH STAND RATING
APPLICABLE ONLY IF ALL DOORLOCKS

ARE IN A CLOSED POSITION.

CONTROLLER MUST BE INSTALLED IN

AN ENVIROMENT WHERE AMBIENT

TEMPERAURE IS BETWEEN 41°F(5° V) 

AND 122°F (50°C)

WARNING

WARNING

IF AN OVERLOAD OR A FAULT CURRENT

INTERRUPTION OCCURS, CIRCUITS MUST BE

CHECKED TO DETERMINE THE CAUSE OF THE

INTERRUPTION. IF A FAULT CONDITION EXISTS,

THE CURREN-CARRYING COMPONENTS

SHOULD BE EXAMINED AND REPLACED IF

DAMAGED, AND THE INTEFRAL CURRENT

SENSORS MUST BE REPLACED TO REDUCE

THE RISK OF FIRE OR ELECTRICAL SHOCK.

TO MAINTAIN OVERCURRENT, SHORT-CIRCUIT,

AND GROUND-FAULT PROTECTION, THE

MANUFACTURER’S INSTRUCTIONS FOR THE

SELECTION OF OVERLOAD AND SHORT-

CIRCUIT PROTECTION MUST BE FOLLOWED TO

REDUCE THE RISK OF FIRE OR

ELECTRIC SHOCK.

CB FXD63A250 / CFD63A250

SPECIFICALLY SET FOR THIS INSTALLATION

L=1100
5=1900

2=1300
6=2100

3=1500
7=2300

4=1700
h=2500

Warning

The fire pump set must only be used for the 
applications mentioned. Any other use is 
considered improper use. Grundfos cannot be 
held responsible for damage caused by improper 
use. The liability rests solely with the operator.

Note

Check the fire pump set carefully on delivery 
against the papers and inspect for damage 
incurred during transport. Immediately notify the 
carrier of any damage or shortage found. 
Transport and store it correctly before 
installation.

Warning

Lifting the fire pump set should only be done by 
qualified personnel.

When lifting the entire fire pump set, never use 
the lifting eyes of the individual components.

Use only suitable lifting equipment in proper 
condition. See also weight specifications in 
section 7. Technical data
.

During transport of the fire pump set, the cabinet 
door must be closed and locked.

Do not stand or place hands under a component 
in such a way that the component would fall on 
the hands if dropped.

TM

03

 29

33

 49

05

Содержание Fire DNF

Страница 1: ...Fire DNF Fire HSEF electric Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...EC Member States Machinery Directive 2006 42 EC Standards used EN 12100 1 2003 EN 12100 2 2003 EN 809 1998 Low Voltage Directive 2006 95 EC Standards used EN 60204 1 2006 EN 60439 1 1999 EMC Directiv...

Страница 3: ...4 Levelling 17 9 5 Pipework 18 9 6 Bypass 18 9 7 Connection to the pressure sensor 18 9 8 Priming tank and test pipe 18 9 9 Alignment 19 9 10 Separate control cabinet 20 10 Electrical connection 21 1...

Страница 4: ...o reduce the risk of fire or electric shock the manufacturer s instructions for selection of overload and short circuit protection must be followed Lifting points for the entire fire pump set Hazadous...

Страница 5: ...impeller diameter may therefore deviate from the standard diameters stated in catalogues data sheets etc The actual impeller diameter is stated on the pump nameplate 4 2 1 Split case pump The Grundfo...

Страница 6: ...and allows for setting of pressure values See section 5 2 Settings via display Fig 4 Control panel She controller has two DIP switches for settings See section 5 1 Settings via DIP switches The intern...

Страница 7: ...ia display Cut in B3 fig 4 This button is used to set the pressure limit for starting the pump It is enabled with a DIP switch See section 5 1 Settings via DIP switches It is also used when setting th...

Страница 8: ...an be displayed in PSI P or bar B The display also gives access to the setting menus of the controller See section 5 2 Settings via display 4 4 6 Indicator lights on control panel Four indicator light...

Страница 9: ...Pressing these buttons simulates a pressure drop in the system Start delay In systems with several pumps it may be necessary to set a start delay to prevent all motors from starting at the same time...

Страница 10: ...scribed below Setting of upper DIP switch Phase reversal reference switch No 6 If indicator light Phase Reversal is on change the DIP switch setting ABC CBA to another setting using a pencil Setting o...

Страница 11: ...the previous log To exit the menu do not press any button for more than 30 seconds or press Cut in button B3 for more than 10 seconds Menu 12 event log In this menu the user can view the event log The...

Страница 12: ...er placed on the common base frame Example DNF Fire DN F 80 25 260 E A X A A B B Example HSEF Fire HSE F 8 15 323 E B X D A B C Fire Fire system Pump type DN End suction pump HSE Horizontal split case...

Страница 13: ...60 60 Hz Example S N E A S Packing type stuffing box N Uncooled stuffing box E With internal barrier fluid F With external barrier fluid A PTFE impregnated fibre packing rings and EPDM O ring in pump...

Страница 14: ...AGES MAXIMUM BRAKE HORSEPOWER REQUIRED AT RATED SPEED AT ANY CAPACITY CONDITION 1 3 5 7 9 11 4 6 8 10 12 13 2 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2...

Страница 15: ...eplate for the fire pump set See fig 11 8 7 Maximum operating pressure 10 16 or 25 bar The maximum operating pressure is stated on the pump nameplate 8 8 Ambient temperature Minimum ambient temperatur...

Страница 16: ...d are one part cement to three parts sand and four parts medium aggregate The concrete foundation must have an absolutely level and even surface Provide the foundation with anchor bolts to fasten to f...

Страница 17: ...e borne noise in the pipework only rubber bellows expansion joints Fit the expansion joints both on the suction and the discharge sides The distance from the pump should be at least 1 to 1 1 2 x DN di...

Страница 18: ...ssure sensor 1 4 NPTF is on the right side of the controller fig 3 pos 6 Run a hose from the discharge pipe to the pressure sensor Water pipes must be flushed clean before connecting the pressure sens...

Страница 19: ...long coupling life This is particularly important with increased motor speed Follow the installation instructions of the coupling manufacturer TM03 2999 5005 Outside diameter of coupling mm Clearance...

Страница 20: ...recommended to avoid water accumulation at the controller s feet 7 TM01 8886 0800 Place the foil where needed 8 TM01 8887 0800 Retighten the screws 9 TM01 8888 0800 Check the alignment carefully once...

Страница 21: ...erminal 104 106 must be used when connecting a remote control voltage from the other equipment Make sure that the control voltage from other equipment and that from control relay CR10 are compatible F...

Страница 22: ...uttons START and STOP 10 Simulate a power failure by turning the circuit breaker to OFF and check if the circuit connected to terminals PowAv is reacting properly 11 Simulate phase reversal by pressin...

Страница 23: ...ndle back to OFF and press STOP button A3 fig 3 pos 3 12 3 Test run To start a test run open the isolating valve to the test pipe and press buttons Cut in B3 and Cut out B2 fig 4 The pump runs for ten...

Страница 24: ...hermal paper and be correctly oriented The following operations must be followed to replace the paper 1 Unscrew the axle and remove the empty roll 2 On the printer open the top cover to get access to...

Страница 25: ...e desired results To set the leakage rate of the stuffing box remove the protecting guards of the shaft on both sides This gives access to the setting screw See service instructions Bearing lubricatio...

Страница 26: ...pipe has been installed according to section 9 5 Pipework c Impeller out of balance Clean the impeller d Inner pump parts worn Replace defective parts e Pump stressed by the pipework Install the pump...

Страница 27: ...ce technician can prepare and provide the appropriate spare parts Please obtain the technical data for the system from the nameplate 17 Warranty The warranty is governed by the framework of our genera...

Страница 28: ...75 2220 x 701 x 1320 1050 525 MMG 280M E 90 2271 x 701 x 1320 1096 590 HSEF 5 8 MMG 200LA E 30 2010 x 701 x 1320 669 6 5 283 283 143 248 MMG 200LB E 37 2010 x 701 x 1320 692 270 HSEF 5 11 MMG 225M E 4...

Страница 29: ...5 525 MMG 280M E 90 1728 x 701 x 842 891 590 HSEF 5 12 MMG 280M E 90 1733 x 701 x 891 999 6 5 302 390 257 590 MMG 315S E 110 1943 x 853 x 976 1479 1050 MMG 315M E 132 2023 x 853 x 976 1591 1150 HSEF 6...

Страница 30: ...0M E 55 2280 x 701 x 1320 1195 447 MMG 280S E 75 2355 x 701 x 1472 1344 554 HSEF 8 17 MMG 280S E 75 2399 x 701 x 1472 1400 10 8 353 302 458 554 MMG 280M E 90 2449 x 701 x 1472 1447 600 MMG 315S E 110...

Страница 31: ...E 55 1775 x 701 x 915 1037 447 MMG 280S E 75 1805 x 701 x 942 1138 554 HSEF 8 17 MMG 280S E 75 1844 x 701 x 994 1194 10 8 353 302 458 554 MMG 280M E 90 1894 x 701 x 994 1241 600 MMG 315S E 110 2028 x...

Страница 32: ...80M E 90 2980 154 89 7 2 HSEF 5 12 MMG 280M E 90 3 x 380 415 660 690 Y 2980 154 89 7 2 MMG 315S E 110 2980 188 108 7 2 MMG 315M E 132 2980 222 128 7 5 HSEF 6 10 MMG 280S E 75 3 x 380 415 660 690 Y 297...

Страница 33: ...74 7 4 HSEF 8 15 MMG 225M E 45 3 x 380 415 660 690 Y 1480 78 45 7 5 MMG 250M E 55 1480 95 55 7 5 MMG 280S E 75 1480 128 74 7 4 HSEF 8 17 MMG 280S E 75 3 x 380 415 660 690 Y 1480 128 74 7 4 MMG 280M E...

Страница 34: ...34...

Страница 35: ...22 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 L...

Страница 36: ...1739 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: