background image

English (GB)

22

10.4 Connection to optional control relays

If more detailed information about operating and alarm conditions 
is required, conductors can be connected to the optional control 
relays for transferring operating and alarm messages to for 
instance a building management system. The alarm relays have 
one NO and one NC contact. The signal can be transferred to 
maximum two external controllers. If the NO contact is to be 
used, connect the signal cable to terminal 14 (24); if the NC 
contact is to be used, connect the signal cable to terminal 12 (22). 
The common conductor must be connected to terminal 11 (21). 
The position of the optional alarm relays (pos. 1) is shown in fig. 5 
and 6.
The table below gives an overview of relays.

11. Start-up

11.1 Check before start-up

1. Check coupling alignment. See section 

9.9 Alignment

.

2. Check that all bolts are properly tightened.
3. Check that pipework has been installed correctly.
4. Check that all electric connections in and outside the control 

cabinet.

5. Check that there is enough water in the reservoir.

11.2 Start-up

1. Close the isolating valve on the discharge side of the pump. 

Open the isolating valve on the suction side of the pump. 
Open the isolating valve to the test pipe.

2. Turn circuit breaker A1 (fig. 3, pos. 1) to "ON". If the system 

pressure is lower than the cut-in pressure, the pump will start 
automatically.

3. Set the cut-in and cut-out pressures. See section 

11.3 Setting 

of cut-in and cut-out pressures

.

4. If the system pressure is higher than the cut-in pressure, the 

pump will not start. It must started manually. See section 

12.2.1 Manual operation with buttons [START] and [STOP]

.

5. Slowly open the isolating valve on the discharge side and to 

the test pipe.

6. When the pump reaches the operating pressure, open the 

isolating valve sufficiently to reach the duty point.

7. Check the direction of rotation. See section 

11.4 Checking the 

direction of rotation

.

8. Adjust the stuffing box, if necessary. See section 15.3 Pump.
9. Stop the pump manually. See section 

12.2.1 Manual operation 

with buttons [START] and [STOP]

.

10. Simulate a power failure by turning the circuit breaker to 

"OFF", and check if the circuit connected to terminals 
"PowAv" is reacting properly.

11. Simulate phase reversal by pressing the [Alarm Reset] button 

for more than 10 seconds, and check that the circuit 
connected to terminals "Ph. Rev." is reacting properly.

The fire pump set is now operational and in automatic mode.

11.3 Setting of cut-in and cut-out pressures

To enable setting, DIP switch "Lock-Unlock" must be set to "ON". 
See section 

5.1 Settings via DIP switches

.

It is important to set the cut-out pressure first. It must be lower 
than the maximum pressure of the pump; otherwise the pump will 
never stop. The cut-in pressure must be set according to the 
system pressure.
A quick push on buttons [Cut-in] B3 and [Cut-out] B2 (fig. 4) 
increases the value by one unit. A long push increases the value 
by ten units. The value only increases from minimum to 
maximum. When the maximum value is reached, the value 
returns to the minimum value.

11.4 Checking the direction of rotation

1. Turn circuit breaker A1 to "ON". If the pump does not start, 

press [START] button A2 (fig. 3, pos. 2).

2. Observe the direction of rotation.
3. If the direction of rotation is not correct, switch off the power 

supply, and interchange two phases in the terminal box or in 
the controller.

Option

Relay

Function

C1

-

Extra motor run alarm relay
NO: Terminals 93-94
NC: Terminals 95-96

C4

Weekly t.

Weekly test signal

C5

CR18

Alarm, low inlet pressure

C6

CR19

Alarm, low discharge pressure

C7

CR20

Alarm, low ambient temperature

C10

CR21

Alarm, low level in water reservoir

C11

CR22

Alarm, high motor temperature

C12

CR23

Alarm, high vibration

C13

CR24

Alarm, earth fault

C14

CR25

Signal, pump-on-demand

C15

CR26

Alarm, fail to start

C16

CR27

Signal, control voltage okay

C17

CR39

Signal, flowmeter open

C18

CR40

Alarm, high level in water reservoir

Warning

Start-up may only be carried out by authorised 
personnel.

The control cabinet must remain closed during 
start-up. Danger of electric shock!

Note

If the pump does not start, check the error 
messages and instruction in the display. Other 
causes, see section 15. Fault finding.

Note

It is important to set DIP switch "Lock-Unlock" 
back to "OFF" to prevent unauthorised changes.

Содержание Fire DNF

Страница 1: ...Fire DNF Fire HSEF electric Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...EC Member States Machinery Directive 2006 42 EC Standards used EN 12100 1 2003 EN 12100 2 2003 EN 809 1998 Low Voltage Directive 2006 95 EC Standards used EN 60204 1 2006 EN 60439 1 1999 EMC Directiv...

Страница 3: ...4 Levelling 17 9 5 Pipework 18 9 6 Bypass 18 9 7 Connection to the pressure sensor 18 9 8 Priming tank and test pipe 18 9 9 Alignment 19 9 10 Separate control cabinet 20 10 Electrical connection 21 1...

Страница 4: ...o reduce the risk of fire or electric shock the manufacturer s instructions for selection of overload and short circuit protection must be followed Lifting points for the entire fire pump set Hazadous...

Страница 5: ...impeller diameter may therefore deviate from the standard diameters stated in catalogues data sheets etc The actual impeller diameter is stated on the pump nameplate 4 2 1 Split case pump The Grundfo...

Страница 6: ...and allows for setting of pressure values See section 5 2 Settings via display Fig 4 Control panel She controller has two DIP switches for settings See section 5 1 Settings via DIP switches The intern...

Страница 7: ...ia display Cut in B3 fig 4 This button is used to set the pressure limit for starting the pump It is enabled with a DIP switch See section 5 1 Settings via DIP switches It is also used when setting th...

Страница 8: ...an be displayed in PSI P or bar B The display also gives access to the setting menus of the controller See section 5 2 Settings via display 4 4 6 Indicator lights on control panel Four indicator light...

Страница 9: ...Pressing these buttons simulates a pressure drop in the system Start delay In systems with several pumps it may be necessary to set a start delay to prevent all motors from starting at the same time...

Страница 10: ...scribed below Setting of upper DIP switch Phase reversal reference switch No 6 If indicator light Phase Reversal is on change the DIP switch setting ABC CBA to another setting using a pencil Setting o...

Страница 11: ...the previous log To exit the menu do not press any button for more than 30 seconds or press Cut in button B3 for more than 10 seconds Menu 12 event log In this menu the user can view the event log The...

Страница 12: ...er placed on the common base frame Example DNF Fire DN F 80 25 260 E A X A A B B Example HSEF Fire HSE F 8 15 323 E B X D A B C Fire Fire system Pump type DN End suction pump HSE Horizontal split case...

Страница 13: ...60 60 Hz Example S N E A S Packing type stuffing box N Uncooled stuffing box E With internal barrier fluid F With external barrier fluid A PTFE impregnated fibre packing rings and EPDM O ring in pump...

Страница 14: ...AGES MAXIMUM BRAKE HORSEPOWER REQUIRED AT RATED SPEED AT ANY CAPACITY CONDITION 1 3 5 7 9 11 4 6 8 10 12 13 2 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2...

Страница 15: ...eplate for the fire pump set See fig 11 8 7 Maximum operating pressure 10 16 or 25 bar The maximum operating pressure is stated on the pump nameplate 8 8 Ambient temperature Minimum ambient temperatur...

Страница 16: ...d are one part cement to three parts sand and four parts medium aggregate The concrete foundation must have an absolutely level and even surface Provide the foundation with anchor bolts to fasten to f...

Страница 17: ...e borne noise in the pipework only rubber bellows expansion joints Fit the expansion joints both on the suction and the discharge sides The distance from the pump should be at least 1 to 1 1 2 x DN di...

Страница 18: ...ssure sensor 1 4 NPTF is on the right side of the controller fig 3 pos 6 Run a hose from the discharge pipe to the pressure sensor Water pipes must be flushed clean before connecting the pressure sens...

Страница 19: ...long coupling life This is particularly important with increased motor speed Follow the installation instructions of the coupling manufacturer TM03 2999 5005 Outside diameter of coupling mm Clearance...

Страница 20: ...recommended to avoid water accumulation at the controller s feet 7 TM01 8886 0800 Place the foil where needed 8 TM01 8887 0800 Retighten the screws 9 TM01 8888 0800 Check the alignment carefully once...

Страница 21: ...erminal 104 106 must be used when connecting a remote control voltage from the other equipment Make sure that the control voltage from other equipment and that from control relay CR10 are compatible F...

Страница 22: ...uttons START and STOP 10 Simulate a power failure by turning the circuit breaker to OFF and check if the circuit connected to terminals PowAv is reacting properly 11 Simulate phase reversal by pressin...

Страница 23: ...ndle back to OFF and press STOP button A3 fig 3 pos 3 12 3 Test run To start a test run open the isolating valve to the test pipe and press buttons Cut in B3 and Cut out B2 fig 4 The pump runs for ten...

Страница 24: ...hermal paper and be correctly oriented The following operations must be followed to replace the paper 1 Unscrew the axle and remove the empty roll 2 On the printer open the top cover to get access to...

Страница 25: ...e desired results To set the leakage rate of the stuffing box remove the protecting guards of the shaft on both sides This gives access to the setting screw See service instructions Bearing lubricatio...

Страница 26: ...pipe has been installed according to section 9 5 Pipework c Impeller out of balance Clean the impeller d Inner pump parts worn Replace defective parts e Pump stressed by the pipework Install the pump...

Страница 27: ...ce technician can prepare and provide the appropriate spare parts Please obtain the technical data for the system from the nameplate 17 Warranty The warranty is governed by the framework of our genera...

Страница 28: ...75 2220 x 701 x 1320 1050 525 MMG 280M E 90 2271 x 701 x 1320 1096 590 HSEF 5 8 MMG 200LA E 30 2010 x 701 x 1320 669 6 5 283 283 143 248 MMG 200LB E 37 2010 x 701 x 1320 692 270 HSEF 5 11 MMG 225M E 4...

Страница 29: ...5 525 MMG 280M E 90 1728 x 701 x 842 891 590 HSEF 5 12 MMG 280M E 90 1733 x 701 x 891 999 6 5 302 390 257 590 MMG 315S E 110 1943 x 853 x 976 1479 1050 MMG 315M E 132 2023 x 853 x 976 1591 1150 HSEF 6...

Страница 30: ...0M E 55 2280 x 701 x 1320 1195 447 MMG 280S E 75 2355 x 701 x 1472 1344 554 HSEF 8 17 MMG 280S E 75 2399 x 701 x 1472 1400 10 8 353 302 458 554 MMG 280M E 90 2449 x 701 x 1472 1447 600 MMG 315S E 110...

Страница 31: ...E 55 1775 x 701 x 915 1037 447 MMG 280S E 75 1805 x 701 x 942 1138 554 HSEF 8 17 MMG 280S E 75 1844 x 701 x 994 1194 10 8 353 302 458 554 MMG 280M E 90 1894 x 701 x 994 1241 600 MMG 315S E 110 2028 x...

Страница 32: ...80M E 90 2980 154 89 7 2 HSEF 5 12 MMG 280M E 90 3 x 380 415 660 690 Y 2980 154 89 7 2 MMG 315S E 110 2980 188 108 7 2 MMG 315M E 132 2980 222 128 7 5 HSEF 6 10 MMG 280S E 75 3 x 380 415 660 690 Y 297...

Страница 33: ...74 7 4 HSEF 8 15 MMG 225M E 45 3 x 380 415 660 690 Y 1480 78 45 7 5 MMG 250M E 55 1480 95 55 7 5 MMG 280S E 75 1480 128 74 7 4 HSEF 8 17 MMG 280S E 75 3 x 380 415 660 690 Y 1480 128 74 7 4 MMG 280M E...

Страница 34: ...34...

Страница 35: ...22 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 L...

Страница 36: ...1739 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: