15. Fault finding
For fault finding, first observe the status and alarm indications.
Warning
Only trained personnel are allowed to open the
cabinet door.
Warning
Service work must be carried out by authorised
personnel.
Before servicing, make sure that the pump set
cannot be accidentally started.
Note
See also the installation and operating
instructions for the pump and the motor.
Fault
Possible cause
Remedy
1. No power supply to
controller.
a) Main switch in position "O".
No indicator lights on.
Switch on the controller by means of the main
switch.
b) No mains voltage.
No indicator lights on.
Check the cable and mains connection.
Re-establish the power supply. See section
c) Main fuse F1 has tripped.
Cut in fuse F1.
d) Other fuses have tripped.
Cut in the corresponding fuse.
e) Phase failure. "Power supply" indicator light not
on.
Connect the power supply correctly. See section
2. Pump does not start in
automatic mode despite
power supply.
a) Selector switch not in position "Auto".
Turn the selector switch to position "Auto".
b) Pressure switches or cable to pressure switches
defective. Pressure switches incorrectly
connected.
Test the pressure switches and replace, if
necessary. Check the pressure switch
connection according to section
.
c) Defective controller.
No indicator lights on.
Replace the controller.
d) Motor defective.
"Failure to start" indicator light on.
Check and replace the motor, if necessary.
e) Fault in power supply to motor.
"Power failure" indicator light on
Check the motor cable for damages. Check if
the motor cable is connected correctly.
3. Pump does not start in
manual mode despite
power supply.
a) Selector switch not in position "Test".
Turn the selector switch to position "Test".
b) Defective controller.
No indicator lights on.
Replace the controller.
4. Motor continues running
although [Stop] has been
pressed.
a) Selector switch has not been turned to position
"Test" before pressing [Stop] (applies only to
automatic operation).
Turn the selector switch to position "Test" before
pressing [Stop].
Содержание EPC 300
Страница 1: ...GRUNDFOS INSTRUCTIONS Fire Control EN electric 55 kW Installation and operating instructions...
Страница 2: ...2...
Страница 23: ...BG 23 8 4 8 1 TM05 0744 1511 Test Test 1 2...
Страница 24: ...BG 24 8 2 Status 8 3 Alarms AR1 AR2 AR3 1 2 P1 P1 AR1 AR4 DI4 AR5...
Страница 26: ...BG 26 11 10 1 I 2 Test 3 4 Start 8 3 15 5 6 25 Nm 1 2 30 Nm 3 8 7 Stop 8 Auto 9...
Страница 27: ...BG 27 12 8 2 15 12 1 Auto I Auto Test Stop O I 1 2...
Страница 28: ...BG 28 12 2 1 I 2 Test 3 4 Start 15 1 Stop 2 Auto 3...
Страница 29: ...BG 29 12 3 1 Test 2 3 P1 4 Stop 5 P2 6 12 2...
Страница 30: ...BG 30 13 14 5 Grundfos 5 12 2 1 2 3 4 EN TM05 4262 2112...
Страница 32: ...BG 32 16 Grundfos Grundfos 17 18 1 2 Grundfos Grundfos Grundfos...