CONTENTS

Page

1.

Symbols used in this document

2

2.

General

2

3.

Technical data

2

4.

Connecting the DDI to the PROFIBUS-DP V0

2

4.1

PROFIBUS-DP V0

2

4.2

Device master data file (GSD)

2

5.

Electrical connections

2

5.1

PROFIBUS cabling and start-up, possible faults

2

5.2

Connection to the DDI pump

3

5.3

Accessories: connector for PROFIBUS-DP

3

5.4

Installation diagram with terminal resistor

3

6.

Operating the pump using PROFIBUS-DP

4

6.1

Activating the PROFIBUS

4

6.2

Communication between the PROFIBUS master and 
the pump

5

6.3

Data protocol

5

6.4

Data transmission (programming examples)

8

7.

Disposal

8

1. Symbols used in this document

2. General

These installation and operating instructions contain all the 
information required for connecting a DDI dosing pump with 
PROFIBUS option to the PROFIBUS-DP V0 as a slave.
If you require further information or if any problems arise, which 
are not described in detail in this manual, please contact the 
nearest Grundfos Alldos company.

3. Technical data

PROFIBUS

PROFIBUS-DP V0.

Auto-detect baud rate

The following baud rates are recognised automatically:
12 Mbps, 6 Mbps, 3 Mbps, 1.5 Mbps, 500 kbps, 187 kbps, 
93.75 kbps, 45.45 kbps, 19.2 kbps, 9.6 kbps.

Maximum permissible baud rate (transmission speed)

1.5 Mbps.

Bus connection

Via Y-M12 connector.

Identification of DDI pumps with PROFIBUS-DP option

The following is indicated on the DDI pump nameplate:

Enclosure class

IP 65.

4. Connecting the DDI to the PROFIBUS-DP V0

4.1 PROFIBUS-DP V0

DP (Decentralised Peripherals) is the communication protocol for 
fast data transfer at field level. Using this protocol, the bus master 
(e.g. SPS) communicates with decentralised field devices/bus 
slaves (e.g. dosing pumps, analysis devices) via a fast serial port.
The communication functions are determined by the DP-V0 
performance level. DP V0 stands for simple, fast, cyclic and 
deterministic exchange of process data between the bus master 
and the assigned slave devices.

4.2 Device master data file (GSD)

The DDI pump with PROFIBUS-DP option is integrated into the 
PROFIBUS-DP V0 network using the device master data file 
(GSD), which must be integrated into the engineering system of 
the PROFIBUS network. This file contains the properties of the 
device, specifications on its communication capabilities and 
additional information such as diagnosis values.
A CD for integration of the DDI pump with PROFIBUS-DP option 
into the device communication of the dosing pump (slave)/master 
(SPS) is supplied with the PROFIBUS-DP.
The CD contains
• a GSD file (device master data file)
• an illustration of the DDI pump for integration into visualisation 

programs

• documentation.

5. Electrical connections

5.1 PROFIBUS cabling and start-up, possible faults

5.1.1 Signal line

• Short-circuit between line A, line B or screen.
• Line A and line B interchanged or crossed.
• Line A, line B or screen interrupted.

5.1.2 Bus termination

• One end of the bus segment is not terminated.
• Two or more bus terminal resistors are switched on.
• The bus terminal resistor is not powered.
• No bus terminal resistor after a repeater without slaves.

Warning

These installation and operating instructions are 
also available on www.Grundfosalldos.com. 

Prior to installation, read these installation and 
operating instructions. Installation and operation 
must comply with local regulations and accepted 
codes of good practice.

Warning

If these safety instructions are not observed, 
it may result in personal injury!

Caution

If these safety instructions are not observed, 
it may result in malfunction or damage to the 
equipment!

Note

Notes or instructions that make the job easier 
and ensure safe operation.

Warning

First read the installation and operating 
instructions for the DDI pump. Only the 
additional functions are described in this manual.

Control variant

Description

AP

With PROFIBUS

APF

With PROFIBUS and Flow Monitor

Warning

IP 65 can only be ensured if the connectors have 
been screwed on correctly.

Warning

Electrical connections must only be carried out 
by qualified personnel!

First read the installation and operating 
instructions for the DDI pump.

IP 65 can only be ensured if the connectors have 
been screwed on correctly.

Содержание DDI Series

Страница 1: ...DDI with PROFIBUS DP GRUNDFOS ALLDOS INSTRUCTIONS Supplement to installation and operating instructions ...

Страница 2: ...The DDI pump with PROFIBUS DP option is integrated into the PROFIBUS DP V0 network using the device master data file GSD which must be integrated into the engineering system of the PROFIBUS network This file contains the properties of the device specifications on its communication capabilities and additional information such as diagnosis values A CD for integration of the DDI pump with PROFIBUS DP...

Страница 3: ... bus segment 5 2 Connection to the DDI pump Fig 1 Connection to DDI 209 Fig 2 Connection to DDI 222 For the PROFIBUS DP attach a Y M12 connector to socket 6 of the pump Connect the bus to the sockets of the Y M12 connector using 2 pin PROFIBUS cables 5 2 1 Pin assignment socket 6 5 2 2 Bus connection If the pump is the last device on the bus it must be equipped with a bus terminal resistor Screw t...

Страница 4: ...ion level 6 1 4 Bus error A possible problem with the PROFIBUS communication is indicated on the pump ERROR and BUS flash in the display If there is no connection to the PROFIBUS master cable connection master failure ERROR BUS and the Arrow icon flash in the display The pump continues trying to establish bus communication TM03 6586 4506 Note The minimum cable length of 1 metre between the devices...

Страница 5: ...e 6 3 1 Remote control of pump via PROFIBUS DP Data flow from the PROFIBUS master to the pump 4 bytes are available for controlling the pump To control the pump using the PROFIBUS master proceed as follows 1 Select the operating mode byte 1 bits 0 1 manual contact current control 0 20 mA current control 4 20 mA 2 The operating mode is enabled when bit 4 changes from 0 to 1 3 Enter the setpoint byt...

Страница 6: ...xternal pre empty signal empty signal Hall sensor for motor monitoring PROFIBUS communication current control for operating mode manual 4 20 mA An error message is sent if the current input is 2 mA Bit Byte 2 Control functions for DDI 209 Byte 2 Control functions for DDI 222 0 Remote on off 0 off 1 on Remote on off 0 off 1 on 1 Slow mode 0 off 1 on Slow mode 1 0 off 1 on 2 Continuous operation dea...

Страница 7: ...ar with activated pressure control 8 11 Operating mode Bit 11 Bit 10 Bit 9 Bit 8 Manual 0 0 0 0 Contact 0 0 0 1 Current control 0 20 mA 0 0 1 0 Current control 4 20 mA 0 0 1 1 Batch dosing with manual start 0 1 0 0 Batch dosing with contact start 0 1 0 1 Timer with manual start 0 1 1 0 Timer with contact start 0 1 1 1 Calibration 1 0 0 0 12 15 Reserve Bit Bytes 7 8 Status messages for DDI 222 0 Pu...

Страница 8: ...operated in slow mode PROFIBUS settings for transferring the setpoint byte 1 20 set bit 5 accept setpoint byte 2 00h byte 3 03h setpoint 1000 ml h decimal byte 4 E8h corresponds to 03E8 in hexadecimal format The transferred setpoint can be read and monitored via the feedback actual value for bytes 1 and 2 for switching on the pump and slow mode byte 1 00h byte 2 03h set bits 0 and 1 switch on pump...

Страница 9: ...9 ...

Страница 10: ...10 ...

Страница 11: ...1 0022 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilni...

Страница 12: ...www grundfosalldos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 15 720092 V4 0 Repl 15 720092 V3 0 GB 96681437 1007 ...

Отзывы: