8.7.66 Pressure relief (4.4.8)
Fig. 117
Pressure relief
Description
The purpose of the function is to reduce the pressure in the pipes
by opening a solenoid valve if it exceeds a set limit. If the
pressure is not reduced within a given time, the solenoid valve
will be closed, and a warning can be given.
Fig. 118
Pressure relief
Setting range
• Setting of digital output.
• Setting of pressure to be monitored.
• Setting of valve opening pressure.
• Setting of band for valve opening pressure.
• Setting of warning or alarm.
Setting via the operating panel
• Settings > Monitoring functions > Pressure relief > Go to
setting of digital output.
1. Select digital output.
2. Select: Pressure relief valve.
3. Press [Back] x 2.
4. Select: Pressure to be monitored
• Select: Outlet pressure, System pressure or External
pressure.
5. Press [Back].
6. Select and set:
• Valve opening pressure
• Band, valve opening pressure.
7. Select: Warning > Disabled
or Enabled.
8. Set: Delay. (Only to be set if warning has been enabled).
9. Select: Enabled.
Factory setting
The function is disabled.
8.7.67 Log values (4.4.9)
Fig. 119
Log values
Description
Select the values to be logged and the number of samples per
hour. The resulting timespan is shown. When the timespan has
elapsed, old logged values will be deleted and overwritten by the
new ones.
Log values
• Estimated flow rate (only if no flowmeter is installed)
• Speed of pumps
• Process value
• Setpoint
• Power consumption (MPC-E systems)
• Inlet pressure (if an inlet-pressure sensor is installed).
Setting range
Samples per hour: 1-3600.
Setting via the operating panel
• Settings > Monitoring functions > Log values.
1. Set: Samples per hour.
2. Select the values to be logged.
TM
03
92
0
6
36
07
4
Band
Warning delay
Valve opening
pressure
Valve opening pressure
minus band
P [bar]
Time [s]
1: Solenoid valve opens.
2: Solenoid valve closes.
3: Solenoid valve opens.
4: Warning is activated.
5: Solenoid valve closes, and warning
is reset.
5
3
2
1
Содержание Control MPC 2000 Series
Страница 1: ...Control MPC Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Страница 2: ...2...
Страница 394: ...CN 394 8 3 CU 352 8 4 1 15 6 PV SP H G A MPC E I GENI RS 485 B D E F A B C D E F G H I C 64...
Страница 397: ...CN 397 8 4 8 1 2 6 14 8 7 67 4 4 9 1 2 8 4 9 1 2 7 15 8 4 10 1 6 1 3 1 10 16 1 PI PI 0 100 MPC E EC MPC E EC...
Страница 401: ...CN 401 8 5 5 2 1 4 28 PI PI 8 5 6 1 6 2 1 4 1 2 1 4 6 29 1 6 1 2 3 8 5 7 2 1 4 7 30 100 1 2 1 2...
Страница 403: ...CN 403 8 6 3 3 2 24 33 1 2 214 8 6 4 3 3 34 8 7 4 35 PI S 1 2 CU 352 GENIbus 1 2 3 8 7 1 4 1 36 PI S...
Страница 405: ...CN 405 8 7 3 4 1 2 38 2 7 1 1 CU 352 2 7 8 7 4 2 7 4 1 2 1 4 1 2 7 39 2 7 1 2 8 7 28 4 3 7 3 4 5 6...
Страница 407: ...CN 407 8 7 7 4 1 4 43 2000 2000 0 100 8 7 30 4 3 8 1 AI 2 3 AI 1 CU 352 8 7 8 4 1 5 44 1 2 3 1 2 3 4...
Страница 411: ...CN 411 8 7 16 4 2 3 55 1 0 8 7 17 4 2 4 56 24 CU 352 1 2 3 03 00...
Страница 412: ...CN 412 8 7 18 4 2 5 57 1 2 3 4 8 7 19 4 2 7 58 8 7 20 4 2 8 1 2 3...
Страница 416: ...CN 416 2 Qmin 69 1 8 7 28 4 3 7 2 3 4 70 1 8 7 30 4 3 8 2 3 4 2 71 5 3 15 0 25 0 6 10 25 30 50...
Страница 423: ...CN 423 8 7 39 4 3 14 1 87 MPC S MPC S 100 25 100 8 7 40 4 3 14 2 88 100 100 1 70...
Страница 428: ...CN 428 8 7 49 4 3 25 100 HVAC SP Setpoint alternation Kp Ti 1 2 3 4 5 8 7 50 4 3 25 1 101 1 6 1 AI...
Страница 430: ...CN 430 8 7 53 4 3 27 1 4 104 1 4 1 2 1 4 1 1 2 2 3 4 8 7 54 4 3 28 105 8 1 2 3...
Страница 432: ...CN 432 8 7 57 4 4 1 108 8 7 58 4 4 1 1 8 7 59 4 4 1 2 8 7 60 4 4 1 3 8 7 58 4 4 1 1 109 CU 352 5 8 7 28 4 3 7 1 2 3...
Страница 433: ...CN 433 8 7 59 4 4 1 2 110 8 7 30 4 3 8 1 2 3 4 5 8 7 60 4 4 1 3 111 8 7 30 4 3 8 1 2 3 3 4 5...
Страница 434: ...CN 434 8 7 61 4 4 2 112 CU 352 1 2 3 8 7 62 4 4 3 113 CU 352 8 7 14 4 2 1 1 2...
Страница 435: ...CN 435 8 7 63 4 4 4 114 CU 352 CU 352 CU 352 8 7 28 4 3 7 1 2 3 4 5 8 7 64 1 4 4 5 4 4 6 115 1 CU 352...
Страница 437: ...CN 437 8 7 66 4 4 8 117 118 1 2 3 2 4 5 6 7 8 9 8 7 67 4 4 9 119 MPC E 1 3600 1 2 TM03 9206 3607 4 s 1 2 3 4 5 5 3 2 1...
Страница 438: ...CN 438 8 7 68 4 4 10 120 1 2 8 7 69 4 4 11 121 CU 352 NRV NRV 1 2 G H I J MGE MPC E...
Страница 439: ...CN 439 8 7 70 1 2 4 4 13 4 4 14 122 1 2 CU 352 1 2 3 4 123 1 2 3 4 124 1 2 3 4 5 125...
Страница 440: ...CN 440 126 1 2 1 2 3 2 4 5 6 7 8 4 4 13 1 2 8 7 71 CU 352 4 5 127 CU 352 CU 352 CU 352 15 4 5 1 GENIbus...
Страница 443: ...CN 443 8 7 75 4 5 4 132 CU 352 1 2 3 4 1234 8 7 76 4 5 5 133 CU 352 Internet 8 8 1 CU 352 1 4 4 5 1 134 8 1 1 1 IP...
Страница 447: ...CN 447 9 9 1 9 2 CU 352 CU 352 12 10 5 0 20 mA 4 20 mA CU 352...
Страница 452: ...Arabic AR 452 20 0 20 4 CU 352...
Страница 455: ...Arabic AR 455 CU 352 GENIbus 8 8 8 8 TM05 3235 1012 GENIbus GENIbus Grundfos CIU GENIbus 1 3 9 139...
Страница 518: ...Arabic AR 518 O26 O27 O28 CUE EC Control MPC LC Control MPC F E B A Cont r ol MPC...