8.7.6 Setting of influence function (4.1.3.2)
Fig. 41
Setting of influence function
Description
You can select the relation between the measuring parameter
which is to influence the setpoint and the desired influence as a
percentage.
The relation is set by entering values in a table with maximum
eight points by means of the operating panel.
Example:
Fig. 42
Relation between setpoint influence and flow rate
The control unit draws straight lines between the points. A
horizontal line is drawn from the minimum value of the relevant
sensor (0 m
3
/h in the example) to the first point. This is also the
case from the last point to the sensor's maximum value (example
50 m
3
/h).
Setting range
Two to eight points can be selected. Each point contains the
relation between the value of the parameter which is to influence
the setpoint and the influence of the value.
Setting via the operating panel
• Settings > Primary controller > External setpoint influence.
1. Set the influence function.
2. Set the number of points.
3. Set: External input value (Point 1).
4. Set as a percentage: Reduce setpoint to (Point 1).
5. Repeat steps 2 to 4 for all desired parameters.
Factory setting
The function is disabled.
8.7.7 Primary sensor (4.1.4)
Fig. 43
Primary sensor
Description
You can select the control parameter of the system and set the
sensor to measure the value.
Setting range
• Outlet pressure
• Diff. pressure, external
• Diff. pressure, pump
• Series 2000, diff. pressure
• External pressure
• Diff. pressure, inlet
• Diff. pressure, outlet
• Flow rate
• Series 2000, flow rate
• Flow-pipe temperature
• Return-pipe temperature
• Differential temperature
• Ambient temperature
• Return-pipe temp., external
• 0-100 % signal
• Not used.
Setting via the operating panel
• Settings > Primary controller > Primary sensor > Go to setting
appears.
1. Select analog input (AI) for the primary sensor and set the
parameters.
2. Press [Back].
3. Select control parameter for the primary sensor.
Factory setting
The primary parameter is the outlet pressure. The sensor is
connected to AI1 (CU 352). Other primary parameters can be
selected in the startup wizard.
TM
03
16
9
1
47
07
20
50
1
2
3
4
40
60
80
100
Flow rate [m
3
/h]
Setpoint influence [%]
Содержание Control MPC 2000 Series
Страница 1: ...Control MPC Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Страница 2: ...2...
Страница 394: ...CN 394 8 3 CU 352 8 4 1 15 6 PV SP H G A MPC E I GENI RS 485 B D E F A B C D E F G H I C 64...
Страница 397: ...CN 397 8 4 8 1 2 6 14 8 7 67 4 4 9 1 2 8 4 9 1 2 7 15 8 4 10 1 6 1 3 1 10 16 1 PI PI 0 100 MPC E EC MPC E EC...
Страница 401: ...CN 401 8 5 5 2 1 4 28 PI PI 8 5 6 1 6 2 1 4 1 2 1 4 6 29 1 6 1 2 3 8 5 7 2 1 4 7 30 100 1 2 1 2...
Страница 403: ...CN 403 8 6 3 3 2 24 33 1 2 214 8 6 4 3 3 34 8 7 4 35 PI S 1 2 CU 352 GENIbus 1 2 3 8 7 1 4 1 36 PI S...
Страница 405: ...CN 405 8 7 3 4 1 2 38 2 7 1 1 CU 352 2 7 8 7 4 2 7 4 1 2 1 4 1 2 7 39 2 7 1 2 8 7 28 4 3 7 3 4 5 6...
Страница 407: ...CN 407 8 7 7 4 1 4 43 2000 2000 0 100 8 7 30 4 3 8 1 AI 2 3 AI 1 CU 352 8 7 8 4 1 5 44 1 2 3 1 2 3 4...
Страница 411: ...CN 411 8 7 16 4 2 3 55 1 0 8 7 17 4 2 4 56 24 CU 352 1 2 3 03 00...
Страница 412: ...CN 412 8 7 18 4 2 5 57 1 2 3 4 8 7 19 4 2 7 58 8 7 20 4 2 8 1 2 3...
Страница 416: ...CN 416 2 Qmin 69 1 8 7 28 4 3 7 2 3 4 70 1 8 7 30 4 3 8 2 3 4 2 71 5 3 15 0 25 0 6 10 25 30 50...
Страница 423: ...CN 423 8 7 39 4 3 14 1 87 MPC S MPC S 100 25 100 8 7 40 4 3 14 2 88 100 100 1 70...
Страница 428: ...CN 428 8 7 49 4 3 25 100 HVAC SP Setpoint alternation Kp Ti 1 2 3 4 5 8 7 50 4 3 25 1 101 1 6 1 AI...
Страница 430: ...CN 430 8 7 53 4 3 27 1 4 104 1 4 1 2 1 4 1 1 2 2 3 4 8 7 54 4 3 28 105 8 1 2 3...
Страница 432: ...CN 432 8 7 57 4 4 1 108 8 7 58 4 4 1 1 8 7 59 4 4 1 2 8 7 60 4 4 1 3 8 7 58 4 4 1 1 109 CU 352 5 8 7 28 4 3 7 1 2 3...
Страница 433: ...CN 433 8 7 59 4 4 1 2 110 8 7 30 4 3 8 1 2 3 4 5 8 7 60 4 4 1 3 111 8 7 30 4 3 8 1 2 3 3 4 5...
Страница 434: ...CN 434 8 7 61 4 4 2 112 CU 352 1 2 3 8 7 62 4 4 3 113 CU 352 8 7 14 4 2 1 1 2...
Страница 435: ...CN 435 8 7 63 4 4 4 114 CU 352 CU 352 CU 352 8 7 28 4 3 7 1 2 3 4 5 8 7 64 1 4 4 5 4 4 6 115 1 CU 352...
Страница 437: ...CN 437 8 7 66 4 4 8 117 118 1 2 3 2 4 5 6 7 8 9 8 7 67 4 4 9 119 MPC E 1 3600 1 2 TM03 9206 3607 4 s 1 2 3 4 5 5 3 2 1...
Страница 438: ...CN 438 8 7 68 4 4 10 120 1 2 8 7 69 4 4 11 121 CU 352 NRV NRV 1 2 G H I J MGE MPC E...
Страница 439: ...CN 439 8 7 70 1 2 4 4 13 4 4 14 122 1 2 CU 352 1 2 3 4 123 1 2 3 4 124 1 2 3 4 5 125...
Страница 440: ...CN 440 126 1 2 1 2 3 2 4 5 6 7 8 4 4 13 1 2 8 7 71 CU 352 4 5 127 CU 352 CU 352 CU 352 15 4 5 1 GENIbus...
Страница 443: ...CN 443 8 7 75 4 5 4 132 CU 352 1 2 3 4 1234 8 7 76 4 5 5 133 CU 352 Internet 8 8 1 CU 352 1 4 4 5 1 134 8 1 1 1 IP...
Страница 447: ...CN 447 9 9 1 9 2 CU 352 CU 352 12 10 5 0 20 mA 4 20 mA CU 352...
Страница 452: ...Arabic AR 452 20 0 20 4 CU 352...
Страница 455: ...Arabic AR 455 CU 352 GENIbus 8 8 8 8 TM05 3235 1012 GENIbus GENIbus Grundfos CIU GENIbus 1 3 9 139...
Страница 518: ...Arabic AR 518 O26 O27 O28 CUE EC Control MPC LC Control MPC F E B A Cont r ol MPC...