10. Technical data
10.1 Enclosure class
IPX4D
10.2 Sound pressure level
The sound pressure level of the pump is lower than
70 dB(A).
10.3 Ambient temperature
-30 to 55 °C.
Relative humidity
Maximum 95 %.
Liquid temperature
-20 to 60 °C.
Insulation of pump head
Do not insulate the pump head. If you insulate the
pump display and the liquid temperature is lower
than the ambient temperature, do not cover the drain
holes in the stator housing.
System pressure
See the pump nameplate.
Start and stop input, basic and relay modules
External potential-free contact.
Maximum load: 250 V, 1.5 mA.
Minimum load: 100 V, 0.5 mA.
Operating and fault signal output, relay module
Internal potential-free changeover contact.
Maximum load: 250 V, 2 A, AC.
Minimum load: 5 V, 100 mA, DC.
10.4 Minimum inlet pressure
Minimum inlet pressure: 1 bar
10.5 Maximum inlet pressure
The actual inlet pressure plus the pressure when the
pump is operating against a closed valve must
always be lower than the maximum system pressure.