English (GB)
8
5. Dismantling and assembly
5.1 General information
If it is necessary to dismantle the pump, either because it is
choked or damaged, please follow the instructions in the following
sections.
Position numbers of parts (digits) refer to section
;
position numbers of tools (letters) refer to section
Before dismantling the pump
• Disconnect the electricity supply to the motor.
• Close the isolating valves, if fitted, to avoid draining the
system.
• Remove the electric cable in accordance with local
regulations.
Before assembly
• Clean and check all parts.
• Replace defective parts by new parts.
• Order the necessary service kits.
• Gaskets and O-rings should always be replaced when the
pump is overhauled.
During assembly
• Lubricate and tighten screws and nuts to correct torque.
See section
3. Tightening torques and lubricants
5.2 CM 1, 3, 5, cast iron
5.2.1 Dismantling
1. Remove staybolts (pos. 26).
2. Remove inlet part (pos. 6).
3. Remove gasket (pos. 139b) and chamber (pos. 4e).
4. Hold clamp (pos. 64c), and remove nut (pos. 67).
5. Remove lock washers (pos. 66) and clamp (pos. 64c).
6. Remove impeller (pos. 49).
7. Remove bearing ring (pos. 47a) and short spacing pipe
(pos. 64a).
8. Remove chamber for bearing (pos. 4a), gasket (pos. 139b),
impeller (pos. 49) and spacing pipe (pos. 64).
9. Continue the dismantling until shaft seal (pos. 105).
10.Remove shaft seal (pos. 105). See fig. 3.
Fig. 3
Exploded view of shaft seal
5.2.2 Assembly
1. Fit O-ring (pos. 102) on the stationary shaft seal part.
See fig. 4. For correct lubricant, see section
Fig. 4
Fitting the O-ring on the stationary shaft seal part
2. Press the stationary shaft seal part home. See fig. 5.
Fig. 5
Fitting the stationary shaft seal part (only SiC/SiC)
3. Fit the rotating shaft seal part (pos. 104) so that the seal face
touches the stationary part.
4. Fit O-ring (pos. 107) into the rotating shaft seal part
(pos. 104). For correct lubricant, see section
5. Fit retainer (pos. 111) and stop ring (pos. 111a). See fig. 6.
Fig. 6
Fitting the stop ring
Note
Step 7 applies only to pumps with eight stages.
Note
Step 8 applies only to pumps with eight stages.
T
M
04
43
27
12
09
Note
Dismantling of MG 71 and MG 80,
see section 5.6.1.
Dismantling of MG 90 and MG 100,
see section 5.7.1.
Note
It is advisable always to replace wear rings
(pos. 45) and wear ring retainers (pos. 65).
See section 5.8.
Note
Assembly of MG 71 and MG 80, see section 5.6.2.
Assembly of MG 90 and MG 100, see section 5.7.2.
TM
04 432
2
120
9
Warning
Do not touch the seal face.
TM
04
44
36
12
09
Warning
Do not touch the seal face.
T
M
04
4
3
2
5
12
09
Содержание CM 1
Страница 1: ...GRUNDFOS INSTRUCTIONS CM CME Service instructions ...
Страница 2: ...2 ...
Страница 16: ...English GB 16 7 Drawings 7 1 CM 1 3 5 Fig 30 CM 1 3 5 stainless steel TM04 3588 4608 ...
Страница 17: ...English GB 17 Fig 31 CM 1 3 5 cast iron TM04 3591 4608 ...
Страница 18: ...English GB 18 7 2 CM 10 15 25 Fig 32 CM 10 15 25 stainless steel TM04 3828 5108 ...
Страница 19: ...English GB 19 Fig 33 CM 10 15 25 cast iron TM04 3829 5108 ...