En
gl
is
h (
G
B)
4
English (GB)
Installation and operating instructions
Original installation and operating instructions.
CONTENTS
Page
1. Symbols used in this document
2. Applications
The CIM 3XX BACnet module
(CIM = Communication Interface Module), which is a
BACnet master, enables data transmission between
a BACnet MS/TP (Master-Slave/Token Passing)
network and a Grundfos product.
The CIM 3XX is fitted in the product to be
communicated with, or in a CIU 3XX unit
(CIU = Communication Interface Unit).
Retrofitting of the CIM 3XX is described in the
installation and operating instructions of the
Grundfos product.
Further information
For further information about the configuration and
functionality of the CIM 3XX, see the specific functional
profile on the CD-ROM supplied with the product.
2.1 CIM 3XX BACnet module
Fig. 1
CIM 3XX BACnet module
3.1 Connecting the BACnet module
3.3 Setting the BACnet MAC address
3.4 Setting the Device Object instance number
3.5 Setting the BACnet transmission speed
Warning
Prior to installation, read these installation
and operating instructions. Installation and
operation must comply with local
regulations and accepted codes of good
practice.
Warning
If these safety instructions are not
observed, it may result in personal injury!
Caution
If these safety instructions are not
observed, it may result in malfunction or
damage to the equipment!
Note
Notes or instructions that make the job
easier and ensure safe operation.
TM
04
1
697
09
0
8
Pos.
Designation
Description
1
Plus
BACnet terminal Plus
(positive data signal)
2
Minus
BACnet terminal Minus
(negative data signal)
3
Ground
BACnet terminal Ground
4
SW1/SW2
On/off switches for
termination resistor
5
SW3/SW4/
SW5
SW3 for setting the Device
Object instance number.
SW4 and SW5 for setting
the BACnet transmission
speed.
6
LED1
Red/green status LED for
BACnet communication
7
LED2
Red/green status LED for
internal communication
between the CIM 3XX and
the Grundfos product
8
SW6
Hex switch for setting the
BACnet MAC address
(four most significant bits)
9
SW7
Hex switch for setting the
BACnet MAC address
(four least significant bits)
1 2 3
4
5
6
7
8
9
Содержание CIM 3 Series
Страница 1: ...CIM 300 BACnet module Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Страница 2: ...2...
Страница 80: ...JP 80 8 1 2...
Страница 84: ...84 1 RoHS W W W y K K K K K y K K K K K d K d y d...
Страница 85: ...85...