5.2 Setting the parity
The parity can be set either manually by using SW3 or via
software-defined settings.
Manual setting of parity
Default byte format (11 bits):
• 1 start bit
• 8 data bits (least significant bit sent first)
• 1 parity bit (even parity)
• 1 stop bit.
The default setting of the CIM 200 Modbus module is even parity
(1 stop bit). It is possible to change the parity using DIP switch
SW3. The parity can be changed to no parity (2 stop bits). See
fig.
.
Fig. 6
Parity
DIP switch settings
Software-defined parity and stop bits
When SW4 and SW5 are set to "software-defined", the value in
the holding registers at addresses 00009 and 00010 will override
the setting of SW3. See figures
and
.
The software-defined parity and stop bit values will be stored in
the communication interface and will remain after a power-off.
5.3 Modbus address selection
A Modbus slave on a Modbus network must have a unique
address from 1-247. Address 0 is reserved for broadcasting, and
is not a valid slave address.
To set the Modbus address, two hexadecimal rotary switches
(SW6 and SW7) are used. See fig.
Fig. 7
Setting the Modbus address
For a complete overview of Modbus addresses, see section
5.4 Termination resistor
The termination resistor is fitted on the CIM 200 Modbus module
and has a value of 150
Ω
.
The CIM 200 has a DIP switch with two switches (SW1 and SW2)
for cutting the termination resistor in and out. Figure
shows the
DIP switches in cut-out state.
Fig. 8
Cutting the termination resistor in and out
DIP switch settings
Default setting: Termination resistor cut out.
Cable length
We recommend the following maximum lengths:
Note
When software-defined transmission speed is
enabled (ON), software-defined parity and stop bits
are also enabled.
TM
04
17
09
09
08
Parity
SW3
Even parity, 1 stop bit
OFF
No parity, 2 stop bits
ON
Software-defined parity
Value to set in register
00009
No parity (default)
0
Even parity
1
Odd parity
2
Software-defined stop bit
Value to set in register
00010
1 stop bit (default)
1
2 stop bits
2
Note
Before the parity and stop bits can be set via
software-defined settings, SW4 and SW5 must be
set to ON.
SW3
T
M
04
17
06
09
0
8
Note
The Modbus address must be set decimally from 1 to
247.
T
M
04
17
01
09
0
8
Status
SW1
SW2
Cut in
ON
ON
Cut out
OFF
OFF
ON
OFF
OFF
ON
Bits/s
Maximum cable length
Terminated cable
Unterminated cable
[m/ft]
[m/ft]
1200-9600
1200/4000
1200/4000
19200
1200/4000
500/1700
38400
1200/4000
250/800
Note
To ensure a stable and reliable communication, it is
important that only the termination resistor of the first
and last units in the Modbus network are cut in.
Note
All switch settings will be effective immediately after
setting the values, no power-off needed.