English (GB)

8

5.4 Setting the PROFIBUS address

The CIM 150 PROFIBUS module has two hexadecimal rotary 
switches for setting the PROFIBUS address. The two switches 
are used for setting the four most significant bits, SW3, and the 
four least significant bits, SW4, respectively. See fig. 

10

.

Fig. 10

Setting the PROFIBUS address

The table below shows examples of PROFIBUS address settings.

A restart of CIM/CIU 150 has to be performed for a PROFIBUS 
address change to take effect.
For a complete overview of the PROFIBUS addresses, see 
section 

10. PROFIBUS address

.

5.5 Termination resistors

The termination resistors are fitted on the CIM 150 PROFIBUS 
module. See fig. 

11

.

Fig. 11

Internal termination resistors

CIM 150 has a DIP switch with two switches, SW1 and SW2, for 
cutting the termination resistors in and out. Fig. 

12

 shows the DIP 

switches in cut-out state.

Fig. 12

Cutting termination resistors in and out

DIP switch settings

5.6 Status LEDs

CIM 150 PROFIBUS has two LEDs. See fig. 

8

.

• Red and green status LED, LED1, for PROFIBUS 

communication.

• Red and green status LED, LED2, for GENIbus 

communication between CIM/CIU 150 and the connected 
Grundfos product.

LED1

LED2

5.7 Communication watchdog

The state of the PROFIBUS communication watchdog can be 
changed with a PROFIBUS commissioning tool, for example 
Siemens Simatic Manager. If the watchdog is enabled, all bits in 
the ControlModule are automatically set to "0" if the PROFIBUS 
communication is broken. See section 

7.2 Control module 

(ControlModule, module 2)

.

As a result, the booster system will be set to local mode and then 
be operating according to the local operating mode, local setpoint 
and local control mode.

5.8 Reaction to PLC "Stop button"

If the PLC is stopped by the operator, all output registers will be 
set to "0". 
As a result, the control bit RemoteAccessReq will be cleared, and 
the booster system will be set to local mode and then be 
operating according to the local operating mode, local setpoint 
and local control mode. 

TM

04 17

02 090

8

You must set the PROFIBUS address decimally from 
1 to 126. The address 126 is normally used for 
special purposes and should not be used.

PROFIBUS address

SW3

SW4

8

0

8

20

1

4

31

1

F

126

7

E

TM

0

4

 1

961

 1

508

TM

04

 17

03

 09

08

Status

SW1

SW2

Cut in

ON

ON

Cut out

OFF

OFF

Undefined state

ON

OFF

OFF

ON

To ensure a stable and reliable communication, it is 
important that only the termination resistors of the 
first and last units in the PROFIBUS network are cut 
in.

SW3

SW4

+5V

390

220

390

SW1

SW2

SW1 SW2

Status

Description

Off.

CIM 150 has been switched off.

Permanently green.

CIM 150 is ready for PROFIBUS data 
transmission (Data Exchange State).

Permanently red.

CIM 150 does not support the connected 
Grundfos product.

Flashing red.

Wrong or missing PROFIBUS 
configuration or no contact to the 
PROFIBUS master.

Status

Description

Off.

CIM 150 is switched off.

Permanently green.

GENIbus communication between CIM 
150 and the Grundfos product is OK.

Permanently red.

CIM 150 does not support the connected 
Grundfos product.

Flashing red.

No GENIbus communication between CIM 
150 and the Grundfos product.

During startup, there may be a delay of up to 5 
seconds before the LED2 status is updated.

Pumpland.ru

Содержание CIM 150 PROFIBUS DP

Страница 1: ...PROFIBUS and PROFINET for Grundfos boosters CIM CIU 150 PROFIBUS DP CIM CIU 500 Ethernet for PROFINET IO Functional profile and user manual GRUNDFOS INSTRUCTIONS Pumpland ru...

Страница 2: ...3 Status module StatusModule module 1 14 7 4 Illustration of closed loop control 16 7 5 Direct bus control of pumps ControlPumps module 50 16 7 6 Change feedback sensor type SelectFeedbackSensor modul...

Страница 3: ...with very high performance CIM Communication Interface Module CIU Communication Interface Unit Control MPC Grundfos pump controller and booster system CRC Cyclic Redundancy Check A data error detecti...

Страница 4: ...th earlier products CU 351 MPC Multi E model G Further you must fit CU 351 MPC with an add on module for the external GENIbus connection to connect to the unit 3 1 PROFIBUS DP CIM 150 Fig 1 Example of...

Страница 5: ...H and later is identical for TPED model H and later and MAGNA3 D In all cases mount the CIM module in the master pump placed to the left For the purpose of redundancy you can mount a second CIM module...

Страница 6: ...US connection type RS 485 two wire Conductors A B Maximum cable length 100 metres at 12 Mbits s Corresponds to 328 feet See section 5 3 1 Data transmission rates and cable length Slave address 1 126 S...

Страница 7: ...699 0908 Pos Designation Description 1 B RxD TxD P PROFIBUS terminal B positive data signal 2 A RxD TxD N PROFIBUS terminal A negative data signal 3 DGND PROFIBUS terminal DGND only for external termi...

Страница 8: ...module 2 As a result the booster system will be set to local mode and then be operating according to the local operating mode local setpoint and local control mode 5 8 Reaction to PLC Stop button If...

Страница 9: ...1013 Pos Description Designation 1 Industrial Ethernet RJ45 connector 1 ETH1 2 Industrial Ethernet RJ45 connector 2 ETH2 3 Rotary switch for protocol selection SW1 4 Data activity LED for connector 1...

Страница 10: ...ss the webserver while the selected Industrial Ethernet protocol is active Status Description Off CIM 500 is switched off Flashing green Wink function LED flashes 10 times when activated from the mast...

Страница 11: ...e change will be reflected in a bit byte value in a corresponding input module 7 2 2 Explanation to control bits RemoteAccessReq Control bit for setting the booster system in remote mode controlled fr...

Страница 12: ...3 ConstPressure 4 ConstDiffPressure 5 The setpoint of the booster system is interpreted as the setpoint for the pressure In these modes the booster system operates in closed loop control and adapts it...

Страница 13: ...is reflected in module 41 UserSetpoint with the same scaling The actual setpoint whether it has been set via Grundfos GO Remote the pump display the pump buttons or the fieldbus can be read from modul...

Страница 14: ...ig 20 Setpoint in open loop control for TPED and MAGNA3 D 7 2 7 Multi E model H and twin head pump TPED model H control For Multi E with a CIM module in the master pump only set CopyToLocal Module 2 b...

Страница 15: ...if the setpoint is influenced for example by analog input If influenced the ActualSetpoint module 29 will differ from the UserSetpoint module 37 Rotation Status bit indicating that the booster system...

Страница 16: ...nge 0 Zone pump 1 is forced to stop from PROFIBUS PROFINET 1 Zone pump 1 is in auto mode controlled from CU 352 1 ControlZonePump2 Value change 0 Zone pump 2 is forced to stop from PROFIBUS PROFINET 1...

Страница 17: ...g 10 Communication fault pump A None 80 Hardware fault IO 351 pump module A None 80 Hardware fault IO 351 I O module A None 83 Verification error EEPROM parameter area A None 88 Sensor fault general m...

Страница 18: ...s the outlet pressure measured by a pressure sensor S S 10 Level 8 m Provides the tank level Requires that a level sensor is installed It has an offset of 100 metres S S S 11 FeedTankLevel 8 m Provide...

Страница 19: ...0 Digital output 1 1 Digital output 2 2 7 Reserved 25 PumpsPresent 5 Bits One bit for each pump configured in the system Logical 1 The pump is present 0 Zone pump 1 present 1 Zone pump 2 present 2 Zo...

Страница 20: ...pm 16 gal h 3 kPa 10 C 17 gal s 4 psi 11 F 18 ft3 h 5 ft 12 19 ft3 min 6 m3 h 13 m3 min 20 ft3 s 45 FeedbackSensorMin 6 Sensor unit Minimum value for the closed loop feedback sensor 46 FeedbackSensorM...

Страница 21: ...ulti E TPED model H PROFIBUS PROFINET module FeedBackSensorUnit Measuring sensor options Primary sensor options VolumeFlow 5 3 0 1 m3 h Flow rate Flow rate Flow rate Series 2000 Head 6 16 0 01 m Diffe...

Страница 22: ...ion general shutdown MPF 51 Blocked motor or pump 54 Motor protection function 3 sec limit 55 Motor current protection activated MCP 56 Underload 57 Dry running 64 Overtemperature 65 Motor temperature...

Страница 23: ...ble for Hydro MPC E and only if the backup pump is an E pump Byte Name Description Bytes 1 to 4 data type 8 Current A Zone pump motor current Bytes 5 to 8 data type 8 Power W Zone pump motor power Byt...

Страница 24: ...7 MGE 3 phase model H and later 7 MP 204 motor protector 1 MP 204 17 Hydro Multi E model G 1 With 3 phase pumps 2 With 1 phase pumps 21 Hydro MPC Control MPC Hydro Multi B 1 Hydro MPC Control MPC CU 3...

Страница 25: ...efore the equipment is installed under real life conditions 8 1 CIM 150 product simulation Product simulation mode is entered when the hexadecimal address switch has one of the values shown in the tab...

Страница 26: ...tting the PROFIBUS address Check that the GSD file used is correct Check that the PROFIBUS cable has been fitted correctly See section 5 3 Connecting the PROFIBUS Check that the PROFIBUS termination i...

Страница 27: ...unning 8 LED1 is permanently red and green at the same time a Error in firmware download Use the webserver to download the firmware again 9 LED2 is permanently red and green at the same time a Memory...

Страница 28: ...0 7 52 3 4 97 6 1 8 0 8 53 3 5 98 6 2 9 0 9 54 3 6 99 6 3 10 0 A 55 3 7 100 6 4 11 0 B 56 3 8 101 6 5 12 0 C 57 3 9 102 6 6 13 0 D 58 3 A 103 6 7 14 0 E 59 3 B 104 6 8 15 0 F 60 3 C 105 6 9 16 1 0 61...

Страница 29: ...module 17 Performance requirement cannot be met 52 Motor slip high 87 18 Commanded alarm standby trip 53 Stalled motor 88 Sensor fault 19 Diaphragm break dosing pump 54 Motor protection function 3 se...

Страница 30: ...winding current too high single phase motors 156 Communication fault internal frequency converter module 191 Limit exceeded sensor 2 for example high level in WW application 122 Auxiliary winding curr...

Страница 31: ...ted or commanded 217 Alarm general purpose sensor high 232 Ethernet Auto disabled due to misuse 247 Power on notice device or system has been switched off 218 Alarm general purpose sensor low 233 Ethe...

Страница 32: ...Pv4 6 Select the Alternate Configuration tab 7 Configure an IP address and subnet mask to be used by your PC See fig 1 Fig 1 Example from Windows A 2 Webserver configuration The built in webserver is...

Страница 33: ...unique Subnet Mask Configure the subnet mask for CIM 500 on the PROFINET IO network Gateway Configure the default gateway for the PROFINET IO network Use DHCP CIM 500 can be configured to automatical...

Страница 34: ...34 Pumpland ru...

Страница 35: ...Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa cent...

Страница 36: ...he name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S ww...

Отзывы: