4. Specifications
4.1 CIM module
4.2 CIM 150 PROFIBUS DP
The table below provides an overview of the specifications for
Grundfos CIM 150 and CIU 150. For further details, please refer
to the specific sections of this functional profile.
4.3 CIM 500 PROFINET IO
The table below provides an overview of the specifications for
Grundfos CIM/CIU 500 ethernet for PROFINET IO. For further
details, please refer to the specific sections of this functional
profile.
General data
Description
Comments
Ambient humidity
30-95 %
Relative, non-condensing.
Operating temperature
-20 to +45 °C
Storage temperature
-25 to +70 °C
GENIbus visual diagnostics
LED2
Will be in one of these states:
Off, permanently green, flashing red, permanently
red.
See section
for PROFIBUS DP
and section
for PROFINET IO.
Power supply (CIU)
24-240 V
Located in the CIU.
GENIbus connection type (CIU)
RS-485, 3-wire + screen
Conductors: A, B and Y.
CIU box enclosure class
IP54
CIU box dimensions (H x W x D)
182 x 108 x 82 mm
PROFIBUS DP specifications
Description
Comments
PROFIBUS implementation class
DP-V0
Intelligent pump profile.
PROFIBUS connector
Screw-type terminal
A, B, DGND, VP (+5 V).
PROFIBUS connection type
RS-485, two-wire
Conductors: A, B.
Maximum cable length
100 metres at 12 Mbits/s
Corresponds to 328 feet. See section
transmission rates and cable length
.
Slave address
1-126
Set via rotary switches SW3 and SW4.
See section
5.4 Setting the PROFIBUS address
Line termination
On or off
Set via DIP switches SW1 and SW2.
See section
Auto detected
Recommended cable cross-section
0.20 - 0.25 mm
2
AWG24 or AWG23
Supported transmission speed
9.6 Kbits/s to 12 Mbits/s
Auto detected.
PROFIBUS visual diagnostics
LED1
Off, permanently green, flashing red, permanently
red.
See section
Maximum number of PROFIBUS devices
at a physical network segment
32
Up to 125 devices if repeaters are used (physically
segmented network).
PROFINET IO specifications
Description
Comments
Application layer
DHCP, HTTP, Ping, FTP, SMTP, SNTP,
PROFINET IO
Rotary switch in position 0.
Transport layer
TCP
Internet layer
Internet protocol V4 (IPv4)
Link layer
ARP, Media Access Control (ethernet)
Ethernet cable
CAT5, CAT5e or CAT6
Supports auto cable-crossover detecting (Auto-
MDIX)
Maximum cable length
100 metres at 10/100 Mbits/s
Corresponds to 328 feet.
Transmission speed
10 Mbits/s, 100 Mbits/s
Auto-detected.
Industrial Ethernet protocols
PROFINET IO, Modbus TCP
Selected with rotary switch, section
.