Page 27 of 40
Any large deviations from the system designed settings should be investigated for a possible
fault.
Should any faults be found check the symptoms with the Fault Finding Checklist first, and if
necessary contact Grundfos Pumps Ltd for advice or Grundfos Service for Maintenance and
Service.
Details can be found on the front of this manual and also the History log section
12.0 User Maintenance
There are NO user serviceable parts in the FireSAFE unit
13.0 Service and Annual Test (as per BS 9251:2014)
BS 9251:2014 recommends that the full fire protection system is tested and inspected every
twelve months. This includes the FireSAFE unit and ensures that the system remains in first
class working order.
The FireSAFE unit should be tested annually by a suitably qualified and competent person.
Following the below checklist gives some minimum activities that need to be completed at
each service and annual test. Other activities will need completing according to the system
design and any fault rectification required.
The record of the service should be added to the history log at the back of this manual.
Should any maintenance work be required then the water and electricity supply may
require isolating prior to commencing work.
The building will be without the fire protection that the FireSAFE unit gives during this
period and alternative measures should be considered. The owner of the building and
any inhabitants should be informed of this.
Ensure any outgoing signals from the FireSAFE unit are not going to cause
activation of:
Fire alarms/beacons
Fire alarm control panel
Fire service response or fire monitoring service response
Any other warning/monitoring devices installed (eg. SMS to mobile device)
Consideration should be given to contacting any response services beforehand and
informing them of the Service and annual test activity of the FireSAFE unit.
Before removing the terminal box cover from the electric motor or before any
removal/dismantling of the pump/motor unit takes place, ensure that the electricity
supply to the control panel has been suitably isolated and cannot be switched on.
NOTE