5 08fault
08fault means BUS voltage too high. It is caused by interaction of inverter and battery.
Fig.6 08fault
Testing method:
a. Try to restart the inverter
b. Try to upgrade special firmware for 08fault. You can request it from Sacolar.
c. After the upgrading, if 08fault still occurs frequently like once several hours, most probably mainbard
or control board has some trouble.
d. Try to replace control board or mainboard
Solution:
Replace control board or mainboard
M alfunction Reason:
08 error will occur when BUS voltage is higher than 510V and lasts for 20.8ms or BUS voltage reaches
higher than 500V and lasts for 1s.