3

 

Communication Connection

6.3.1 RS 485

6.3.2

 

USB

The MAC series comes standard with two RS485 interfaces, and you can monitor one or 

more inverters via RS485. Another RS485 port is used to connect the smart meter (single 

machine anti-backflow function). When connecting the RS485 communication line to a 

single unit, please follow the instructions below.

1>Loosen the AC protective cover and remove the protective cover;

2>Pass  the  RS  485  communication  cable  through  the  waterproof  rubber  plug  and 

connect to the RS485    interface;

3)>The inverter is connected hand-in-hand through the RS 485 communication line. The 

RS485A1  and  RS485B1  (4/5/6  port  or  7/8/9  port)  at  the  end  of  the  485  cable  are 

connected to the ShineMaster for remote server monitoring

4>Lock the protective casing on the inverter frame to prevent water ingress.

Figure 6.5

Figure 6.6

The USB port is mainly used to connect to the monitoring module or firmware update:

External  optional  data  collector

Shine  GPRS-X 

Shine  WiFi-X

Shine4G-X

),

Can 

be connected to the USB interface for monitoring.

Quickly update software with U disk.

Steps for installing the monitoring module: Make sure 

 is on the front side, then insert 

the display and tighten the screws.

Figure 6.7

19

20

When  multiple  machines  are  connected  in  parallel,  two  customers  use  RS485  wiring 

ports  (4/5/6  and  7/8/9  ports)  at  the  same  time,  and  use  multiple  twisted  pairs  with 

shielding  layers  to  connect  multiple  inverters  by  hand.  Parallel  connection  through  the 

RS485  communication  line,  an  inverter  (defined  as  the  first)  is  connected  to  the 

monitoring  equipment  to  achieve  multi-machine  monitoring,  the  number  of  parallel 

machines  can  reach  32  units.  When  multiple  machines  are  connected  in  parallel  or  the 

transmission  distance  is  long,  it  is  recommended  to  switch  the  DIP  switch  2  of  the  last 

inverter from the left side to the right side to introduce a matching resistor. Refer to the 

following figure for wiring:

No.

Definition

Description

1

RS485B2

RS485A2 / B2

 Anti-backflow 

communication port, connected to smart 

meter

2

GND

3

RS485A2

4 / 7

RS485B1

RS485A1 / B1

 The customer uses the 

communication port to connect to the 

third-party monitoring equipment

5 / 8

GND

6 / 9

RS485A1

Disassembly

Install 

The Inverter Side

The Inverter Side

The Inverter Side

The Inverter Side

GND

TR

+

TR

-

1

4

5

6 7

8

9

2

32

ShineMaster

cable

router

RS 485 twisted pair cable

Multiple

 

inverters

Содержание MAC 15-20KTL3-XL

Страница 1: ...75 A 00 SHENZHENGROWATTNEWENERGYTECHNOLOGYCO LTD No 28GuangmingRoad ShiyanStreet Bao anDistrict Shenzhen P R China T 86 755 27471942 E service ginverter com W www ginverter com Installation Operation...

Страница 2: ...Description 3 1 Appearance 3 2 Size Dimensions 3 3 Nameplate 3 4 Working Principle 3 5 Inverter Storage 3 6 Grid Types 3 Product Introduction 4 Unpacking 5 Installation 5 1 Basic Installation Require...

Страница 3: ...ounding 6 Electrical Connections 7 Debugging 7 1 Debug Inverter 7 2 Operating Mode 7 3 OLED Display and Touch Buttons 8 1 Remote Data Monitoring 8 2 Local Data Monitoring 9 1 Routine Maintenance 9 2 T...

Страница 4: ...on Before installation please read through this manual any damage cause by improper installation Growatt reserve the right to disclaim any warranty Ensure that the MAC is not connected to a power supp...

Страница 5: ...technician Burn Warning Do not touch a running inverter cause it generates high temperature on the case Protective Grounding Connect inverter to grounding bar Delay discharge Residual voltage exists...

Страница 6: ...ce 3 2 Size Description Model Size unit mm Weight unit kg Width High Deep MAC series PV inverter 680 508 281 52 MAC series PV Inverter with packaging 730 650 350 60 Figure 3 1 6 5 Identification Descr...

Страница 7: ...ircuit breaker F Grid 1 Do not unpack the Inverter and store it in a ventilation dry place 2 Keep the storage temperature at 25 60 and humidity at 0 95 3 A maximum of four inverters with package can b...

Страница 8: ...he OLED display and maintenance work F To avoid inverter performance de rate due to the over heat please do not expose the inverter under direct sunlight G The installation humidity should be from 0 9...

Страница 9: ...ury Do not place the inverter with its wiring and signal terminals at the bottom contacting with floor or any other object because the terminals are not designed to support the weight of inverter 1 2...

Страница 10: ...not store inverter in area with flammable and explosive material Each inverter must install one AC breaker AC breaker is forbidden to share with other inverters It is forbidden to add load between inv...

Страница 11: ...vent water ingress Notice Waterproof joints must be blocked with fireproof mud to prevent water ingress Before electrical connection please ensure the inverter DC switch is at OFF also disconnect AC s...

Страница 12: ...5A 3 MAC 50KTL3 X LV 12 5A 4 12 5A 3 12 5A 3 MAC 60KTL3 X LV 12 5A 4 12 5A 4 12 5A 4 MAC 50KTL3 X MV 12 5A 4 12 5A 3 12 5A 3 MAC 50 70KTL3 X MV 12 5A 4 12 5A 4 12 5A 4 MAC 15 36KTL3 XL 12 5A 4 12 5A...

Страница 13: ...Steps for installing the monitoring module Make sure is on the front side then insert the display and tighten the screws Figure 6 7 19 20 When multiple machines are connected in parallel two customers...

Страница 14: ...ght Note2 3 The lightning down conductor and the equipment ground wire eventually sink at a total ground point but the two cannot share the wire That is the equipment grounding wire should be pulled s...

Страница 15: ...2 Local Data Monitoring download the mobile app and log in to the monitoring interface to modify the communication address This operation is performed by a professional 1 Select Parameter Settings 2...

Страница 16: ...enough power voltage 200VDC then the inverter will start automatically The intelligent control system of the inverter constantly monitors and adjusts the state of the system When the inverter detects...

Страница 17: ...ed Set Date 2018 12 14 Set Time 12 30 30 Set Comaddr 1 Set Language English General Advanced Set Parameter Reset factory YES NO WideVolt Set WideVolt Set 1 2 3 Set OK The inverter is factory set to CQ...

Страница 18: ...setting mode switch the language with a single touch and touch the setting twice to confirm the setting Set Language English English Chinese Set OK The default COM address is 1 continuous touch twice...

Страница 19: ...inePhone Main interface 1 The center of the main interface shows the current power station name You can switch between different power stations in the account by clicking the invertedtriangle symbol 2...

Страница 20: ...ve power set PF set inverter time set grid voltage high set grid voltage low The operation password is inverter date For example if the date of the day is April 18 2019 the password is inverter2019041...

Страница 21: ...essary information then go back to login page input the registered username and password click login Figure 8 8 Figure 8 9 On the Plant page click on device list datalog add data logger enter the SN n...

Страница 22: ...Figure 8 13 Figure 8 11 C View detailed data Click Plant device list MAX MID and the inverter list of the power station is displayed Double click on the inverter name in the list to display the detai...

Страница 23: ...5678 If you have already connected you can click Skip to connect directly to the WIFI Figure 8 14 Figure 8 15 When viewing local monitoring you must keep the phone s wifi connected to the collector s...

Страница 24: ...C Parameter configuration The parameter data of the equipment can be modified according to the usage D Intelligent detection Detailed and accurate view of the device s detailed data and status E Intel...

Страница 25: ...me recording detection Inverter voltage and current quality can be observed in real time Figure 8 21 Figure 8 22 Figure 8 20 H One click diagnosis One button detection of power plant environment inclu...

Страница 26: ...to be programming at last time Figure 8 23 Figure 8 25 Figure 8 24 Figure 8 26 2 Fault Recording Create a BCONFIG txt file under the root directory of the USB flash drive write down_fault insert the...

Страница 27: ...ssible reasons or solutions Fan is blocked or the heat sink gathers too much dust it needs to clean the fan fan cover or heat sink Fan is damaged it need to replace the fan Poor ventilation of the ins...

Страница 28: ...normal 2 If error message still exists contact manufacturer Warning 202 DC SPD function abnormal 1 After shutdown Check the DC SPD 2 If error message still exists contact manufacturer Warning 203 PV...

Страница 29: ...ge still exisits contact Manufacturer Error 304 AC F Outrange 1 Restart inverter 2 If error message still exists contact manufacturer 9 2 2 Error Error 402 Output DC current too high 1 Restart inverte...

Страница 30: ...50A 50A 50A 45A 45A 45A 45A 45A 45A 55A 55A 55A 55A 55A 55A 3 3 3 2 3 3 3 4 3 3 4 4 4 33300VA 44400VA 55500VA 66600VA 230V 400V 340 440VAC 50 60 Hz 45 55Hz 55 65 Hz 43 5A cos 1 48 3A cos 0 9 58 0A cos...

Страница 31: ...APP USB YES Rs485 YES WIFI Option GPRS Option 4G Option General Data Dimensions W H D 680 508 281 mm Weight 52kg 0 99 0 8LG 0 8LD Efficiency Protection devices Interfaces Operating temperature range 2...

Страница 32: ...kers Full load MPP voltage MPP voltage range Nominal voltage Start voltage Max DC voltage Max recommended PV PV power for module STC Input data Max output current AC grid frequency range Model Power f...

Страница 33: ...0A 50A 55A 55A 55A 15000W 20000W 22000W 16600kVA 220VAC 22200kVA 220VAC 24400kVA 220VAC 127V 220V 101 6 139 7V 50 60 Hz 45 55Hz 55 65 Hz 39 4A 52 5A 57 7A 46 3A 58 3A 64 0A Nominal AC voltage range Ma...

Страница 34: ...WIFI APP USB YES Rs485 YES WIFI Option GPRS Option 4G Option General Data Dimensions W H D 680 508 281 mm Weight 52kg 0 99 0 8LG 0 8LD Efficiency Protection devices Interfaces Operating temperature ra...

Страница 35: ...tage Max DC voltage Max recommended PV PV power for module STC Input data Nominal output current AC grid frequency range Model MAC 36KTL3 XL MAC 25KTL3 XL MAC 30KTL3 XL Max output current Power factor...

Страница 36: ...o OFF position 3 Wait at least 5 minutes until the internal capacitor discharge is completed 4 Disconnect the AC connector 5 Disconnect DC connector 6 Remove the inverter from the wall 7 Disposing of...

Отзывы: