Situation
Fault
Code
Fault Event
Possible cause
Situation
11
Solar over current
Surge
1. Restart the inverter.
2. If the error message still remains,
please contact your installer.
12
GFCI fault
Leakage current
excceds the limit.
1. Check the wire and panels which
may cause the leakage.
2. If the error message still remains,
please contact your installer.
13
PV ISO fault
The resistance
between PV and
ground is too low.
14
INV DC current over
Utility fluctuates.
1. Restart the inverter.
2. If the error message still remains,
please contact your installer.
16
GFCI sensor fault
GFCI sensor failed.
Please contact your installer.
22
Battery high voltage
fault
Battery voltage
exceeds the limit.
1. Check the battery voltage.
2. If the error message still remains,
please contact your installer.
23
Over load
The inverter is loaded
with more than 110%
load and time is up.
Reduced the connected load by
switching off some equipment.
26
INV short
Output short circuited.
Check if wiring is connected well
and remove abnormal load.
27
Fan lock
Fan failed.
Please contact your installer.
32
INV DC voltage over
Load fluctuates
1. Restart the inverter.
2. If the error message still remains,
please contact your installer.
33
INV voltage low
Load fluctuates
1. Restart the inverter.
2. If the error message still remains,
please contact your installer.
34
INV voltage high
Internal components
failed.
Please contact your installer.
35
Wire connection fault
Internal wires loosen.
Please contact your installer.
36
OP voltage fault
Grid connects to
output terminal
Don’t connect the grid to the
ouput terminal.
Specifications
20
MODEL
Growatt 5000HYP
RATED POWER
PV INPUT (DC)
10000 W
10000 W
720 VDC
900 VDC
200 VDC ~ 900 VDC
250 VDC / 300 VDC
250 VDC ~ 850 VDC
500 VDC ~ 850 VDC
2*10 A
25 A
0 A
Maximum DC Power
Nominal DC Voltage
Maximum DC Voltage
Working DC Voltage Range
Start-up Voltage /
Initial Feeding Voltage
MPP Voltage Range
Full Load MPP Voltage Range
Maximum Input Current
Isc PV (absolute maximum)
Max. inverter back feed
current to the array
GRID OUTPUT (AC)
Nominal Output Voltage
Output Voltage Range
Output Frequency Range
Nominal Output Current
Inrush Current/Duration
Maximum Output Fault
Current/Duration
Maximum output Overcurrent
Protection
Power Factor Range
230 VAC (P-N) / 400 VAC (P-P)
184 - 265 VAC per phase
47.5 ~ 51.5 Hz or
59.3~ 60.5Hz
21.8 A per phase
25 A per phase / 20ms
65 A per phase / 1ms
65 A
0.9 lead – 0.9 lag
AC INPUT
AC Start-up Voltage
Auto Restart Voltage
Acceptable Input Voltage Range
Nominal Frequency
AC Input Power
Maximum AC Input Current
Inrush Input Current
120-140 VAC
180 VAC
170 - 280 VAC
50 Hz / 60 Hz
5000VA/5000W
40 A
40 A / 1ms
59
60