![Grossenbacher Systeme SmartPanel SP-240 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/grossenbacher-systeme/smartpanel-sp-240/smartpanel-sp-240_device-description_2269874023.webp)
S
mart
P
anel
Hardware
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
23
6 Operation
6.1 S
TARTUP
/ S
HUTDOWN BEHAVIOUR
After power on the SmartPanel boots the installed operating system from
the Onboard-Flash.
7 Mounting instructions
7.1 G
ENERAL MOUNTING INSTRUCTIONS
All SmartPanel series devices are mounted from the front, i.e. in a control
panel. They are fastened from the rear with the supplied 4 securing nuts.
All SmartPanel series devices can be operated up to a maximum ambient
temperature of 60°C (
Î
Section 11). The ambient temperature stated
applies to the area 5cm above the device, if it is mounted vertically with
unimpeded air convection and a maximum operating height of 2000m above
sea level.
The device can be mounted in an enclosure if the ambient temperature is
taken into consideration. Provide a wall clearance of at least 50 mm on all
sides of the housing, so that sufficient air circulation is ensured. A minimum
clearance of 75 mm from active elements such as load current supply,
transformers etc. must be ensured.
Avoid the exposure of the flat screen to direct sunlight. The radiation from
the sun (UV component) reduces the lifespan of the LCD display.
The following must be ensured in order to prevent the
device from overheating during operation:
-
The cooling slots must always be free in order to
ensure the proper cooling of the system.
-
Avoid the exposure of the flat screen to direct
sunlight.
-
The mounting angle must not exceed ± 35° from
the vertical
If these conditions cannot be met, the mounting of an
external fan is recommended.
7.2 M
OUNTING IN THE FRONT PANEL
- G
ENERAL
1. The front seal must be inlayed from the back side. The seal is self-
adhesive on one side.
2. Push the SmartPanel from the front into the cutout of the front panel.
3. Secure the device from the rear with the supplied 4 securing nuts
which should be tightened evenly from the rear until the front frame is
flush with the front panel all round.
Ensure that the seal is fitted correctly on the front panel.
Avoid tightening torques of greater than 0.5 Nm as this
could otherwise damage the device.
The thickness of the front panel must not exceed 2.5
mm.
DVS 63067-V3.0
Содержание SmartPanel SP-240
Страница 6: ...SmartPanel Hardware 6 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 8: ...SmartPanel Hardware 8 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 10: ...SmartPanel Hardware 10 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 14: ...SmartPanel Hardware 14 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 26: ...SmartPanel Hardware 26 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG Dimensions 4 3 IR DVS 63067 V3 0...
Страница 27: ...SmartPanel Hardware 2011 by Grossenbacher Systeme AG DVS 63067 V2 0 27 Dimensions 5 7 DVS 63067 V3 0...
Страница 28: ...SmartPanel Hardware 28 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG Dimensions 7 DVS 63067 V3 0...
Страница 30: ...SmartPanel Hardware 30 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 32: ...SmartPanel Hardware 32 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 34: ...SmartPanel Hardware 34 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 38: ...SmartPanel Hardware 38 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 40: ...SmartPanel Hardware 40 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 42: ...SmartPanel Hardware 42 DVS 63067 V2 0 2011 by Grossenbacher Systeme AG DVS 63067 V3 0...
Страница 44: ...DVS 63067 V3 0...