The screen shows four "pending errors".
(0= did not occur / 1= occurred):
rdgr
relief valve activated during the last pump phase.
rto
the drive shaft of pump turns too slowly or not at
all during the last pump phase. The pump phase
has been cut short.
end1
the end switch in the greasing system did not
send any or not enough pulses to the control unit
during the last pump phase.
eres
reservoir is empty, the reserve of grease 400cc
(4000 revolutions after the first low level
warning is expired). The pump is discon-nected
and the signal lamp lits.
Press <NEXT>.
Press <F2> (
I/O
).
The screen shows the current operating mode of the
greasing system:
0 auto
the system operates on automa-tic and is
executing the program stored in the control unit.
1 man
the functions of the greasing system are
operated by hand (by means of the GINA).
2 test
the system is performing a test cycle (amount
dependent on parameter setting)
You can change the current operating mode by pressing one
of the numeric keys <0> to <2> and confirm that with
<ENTER>.
If the current greasing cycle (in “auto” mode) is interrupted,
that greasing cycle will not be completed when the system is
put back on “auto”. The “auto” mode will automatically be
restored when the contact is switched on.
Press <NEXT>.
This is the first I/O-screen. It shows the status of various
output signals:
pump
electric pump motor is running.
lamp
signal light lits.
spr
spare.
To test the system, these outputs may toggled manually by
pressing function key <F1> and <F3> to (de)activate the
signal light or the pump motor. You can only do this after
the system’s operating mode has been set to “1”
(manual)
.
Press <NEXT>.
DIAGNOSIS
Pending errors (2)
0
0
0
0
rdgr rto end1 eres
DIAGNOSIS MENU
err I/O var tinfo
INP/OUTP
Mode: 0=auto 1=man
X
2=test
Mode
INP/OUTP hh:mm:ss
I/O (1)
0
0
0
0
pump spr
lamp
spr