148673 REV. G OM-VRC-3E/VRC-6E 5
WARNING
GROUNDING INSTRUCTIONS: THIS APPLIANCE MUST BE CONNECTED TO A GROUNDED
METALLIC, PERMANENT WIRING SYSTEM, OR AN EQUIPMENT GROUNDING
CONDUCTOR MUST BE RUN WITH THE CIRCUIT CONDUCTORS AND CONNECTED TO
THE EQUIPMENT GROUNDING TERMINAL ON THE STATION.
Installation and Start-Up
CAUTION
DO NOT INSTALL THE UNIT WITHIN 2 INCHES OF A HEAT SOURCE (SUCH AS A BRAISING PAN, DEEP FAT
FRYER, CHARBROILER OR KETTLE).
Electrical Supply Connection
- Observe all local, national, or other applicable codes.
Three phase models of the Vortex™ Connectionless
Steamer are supplied with a cord set ready to be
connected to a power supply. See the chart below
for the correct matching receptacle (not supplied with
the unit).
Single phase models are designed to be directly
connected (hard wired) to the electrical supply and
allow sufficient loop in the flexible conduit to facilitate
inspection, servicing, and cleaning.
Branch Circuit Protection
Each Steamer, including individual units of stacked
models, should have its own branch circuit protection
and ground wire. Current and power demands for
each unit are as shown below
.
ELECTRICAL SUPPLY CONNECTIONS
FIELD WIRING TABLE - USE COPPER WIRE ONLY - INSULATION RATING (90ºC)
VOLTAGE
(60 Hz Only)
KW
RATED CURRENT DEMAND
VRC-3E
VRC-6E
VRC-3E
VRC-6E
208 3 PHASE
9KW
10KW
25 Amps
28 Amps
240 3 PHASE
9KW
10KW
22 Amps
25 Amps
480 3 PHASE
9KW
10KW
11 Amps
13 Amps
PLUG AND RECEPTACLE CHART
VOLTS
PHASE
PLUG
RECEPTACLE
9KW
10KW
9KW
10KW
208
3
15-30P
15-50P
15-30R
15-50R
240
3
15-30P
15-50P
15-30R
15-50R
480
3
L16-30P
L16-30P
L16-30R
L16-30R
208
1
----
----
----
----
240
1
----
----
----
----
OM-VRC-3E/VRC-6E