Air Flow Switch 

Installation Instructions 

General 

The plated housing contains a diaphragm, a calibration spring 
and a snap-acting SPST (NC) switch. 
The sample connections located on each side of the diaphragm 
accept a .25” OD tubing via the integral compression and nut or 
barbed fitting. 
An enclosure cover guards against accidental contact with the 
live switch terminal screws and the set point adjusting screw. 
The enclosure cover will accept a .5” conduit connection. The 
AFS-460 has a reset button located on the top surface of the   
enclosure cover.  

Air Sampling Connection 

The AFS is designed to accept firm-wall  sample lines of .25" 
OD tubing by means of ferrule and nut compression connec-
tions.  For sample lines of up to 10 feet, .25" OD tubing is ac-
ceptable. For lines up to 20 feet, use .25" ID tubing. For lines up 
to 60 feet, use .5" ID tubing. A .25" OD adapter,      suitable for 
slip-on flexible tubing is available: order part number 18311.  
Locate the sampling probe a minimum of 1.5 duct diameters 
downstream from the air source. Install the sampling probe as 
close to the center of the airstream as possible. Identify the high 
pressure inlet (H) and the low pressure inlet (L). Select one of 
the five application options listed below and connect the sample 
lines as recommended. 
 
Positive Pressure Only: 
Connect the sample line to inlet H; 
inlet L remains open to the atmosphere. 
Negative Pressure Only: 
Connect the sample line to inlet L; 
inlet H remains open to the atmosphere. 
Two Negative Samples: 
Connect the higher negative sample 
to inlet L. Connect the lower negative 
sample to inlet H. 
Two Positive Samples  
Connect the higher positive sample to inlet 
H. Connect the lower positive sample to inlet L. 
One Positive and One Negative Sample 
Connect the positive sample to inlet H. Connect the negative 
sample to inlet L. 

Application 

The AFS is a general purpose airflow proving switch designed 
for HVAC and energy management  applications. It may be 
used to sense positive, negative or differential air pressure.  

Mounting 

Select a mounting location which is free from    vibration. The 
AFS pressure switch MUST be mounted with the diaphragm in 
any vertical plane in order to obtain the lowest specified         
operating set point. Avoid mounting with the sample line      
connections in the “UP” position. Surface mount via the two 
3/16” diameter holes in the integral mounting bracket. The 
mounting holes are 3 7/8” apart. 

Field Adjustment-AFS-222 (-112) 

The adjustment range of an AFS-222 Air Switch is 0.05 ±.02" 
w.c. to 12.0" w.c. To adjust the set point, t urn the adjusting 
screw counterclockwise until motion has stopped. 
Next, turn the adjusting screw 4 complete turns in a clockwise 
direction to engage the spring. From this point, the next ten 
turns will be used for the actual calibration. 
Each full turn represents approximately 1.2" w.c. 
Please note: To properly calibrate an air switch, a digital      
manometer or other measuring device should be used to       
confirm the actual set point. 

Field Adjustment-AFS-262 (-112) 

The adjustment range of an AFS-262 Air Switch is 0.05 ±.02" 
w.c. to 2.0" w.c. To adjust the set point, t urn the adjusting 
screw counterclockwise until motion has stopped. 
Next, turn the adjusting screw 4 complete turns in a clockwise 
direction to engage the spring. From this point, the next ten 
turns will be used for the actual calibration. 
Each full turn represents approximately 0.2" w.c. 
Please note: To properly calibrate an air switch, a digital      
manometer or other measuring device should be used to       
confirm the actual set point. 

Field Adjustment-AFS-460 

The adjustment range of an AFS-460 Air Switch is 0.4" ± 0.02" 
w.c. to 12.0" w.c. To adjust the set point, turn the adjusting 
screw counterclockwise until motion has stopped.  
Next, turn the adjusting screw four complete turns in a      
clockwise direction to engage the spring. From this point, the 
next ten turns will be used for the actual calibration.  
Each full turn represents approximately 1.16" w.c. 
Please note: To properly calibrate an air switch, a digital      
manometer or othermeasuring device should be used to confirm 
the actual set point.

 