WIRING

• 

Use 18 - 24 AWG shielded wiring for all connections. Do not locate the device wires in the same conduit with wiring used to supply inductive 
loads such as motors. Make all connections in accordance with national and local codes.

• 

Pull at least six inches of wire into the enclosure, then complete the wiring connection according to the wiring diagrams below. All 
connections should be made using either butt-splices or soldering. The use of wire nuts is not recommended.

• 

All thermistors and most RTD's are a 2 wire hook up and are not polarity sensitive. See Figure 6.

• 

For RTD’s that are 3 wire connection see Figure 7.

SPECIFICATIONS

Sensor Type:

 ..........................................

Various thermistors or RTD

Sensor Accuracy: ..................................

Thermistors:

 ±0.2˚C (±0.36˚F) @ 25˚C (77˚F)

 

Platinum RTD’s:

 ±0.3˚C (±0.54˚F) @ 0˚C (32˚F)

 

Nickel RTD’s:

 ±0.4˚C (±0.72˚F) @ 0˚C (32˚F)

Probe Sensing Range: ........................-40 to 50°C (-40 to 122°F)
Ambient Operating Range: .............-40 to 50°C (-40 to 122°F)
Wire Material: .........................................PVC insulated, parallel bonded, 22 AWG 
Enclosure: .................................................ABS, UL94-V0, IP65 (NEMA4X)
Termination: ...........................................

A:

 Pigtail, 2 or 3 wire

 

C & E:

 Terminal block, 2 or 3 wire

Country of Origin: ................................Canada

 

PRINTED IN C

ANAD

A       

TYPICAL WIRE RESISTANCE VALUES 

When using low resistance sensors, long wire runs can add 

significant error to the readings.  Use the following chart to 

determine errors due to wire resistance or consider using a 

1000 ohm sensor or a transmitter for better accuracy. Locate 

the type of wire being used. Multiply the total length of the 

wire (distance from the controller to the sensor and back) 

by the number found in the chart below for total resistance. 

Figure 6                                                          2 Wire Termination for Thermistor or RTD

Figure 7                                                          3 Wire Termination for Thermistor or RTD

Wiring for Enclosures C & E

(terminal block mounted on cover)

GAUGE WIRE TYPE                       18 AWG       22 AWG       24 AWG 
STRANDED (OHMS/FOOT)        5.85 mΩ    14.75 mΩ    23.29 mΩ 
SOLID (OHMS/FOOT)                    6.4 mΩ    15.85 mΩ    25.72 mΩ

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

Green

Red

Black

DIMENSIONS

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

Green

Black

Red

76.2 mm

3.00 “

52.0 mm

2.05 “

0.5” NPT 

92 mm

3.62"

38mm

1.5"

82.5 mm

3.25 “

69.8 mm

2.75 “

132 mm

5.19"

*For illustrative purposes only, terminal block mounted on inside of cover

*

*

IN-GE-TSOBXXX-01