INTRODUCTION

The analog scaling module is used for analog signal conversion 

or re-scaling. It will accept one DC voltage, current or resistive 

input signal and output a non-isolated voltage or current 

signal. The output signal is easily calibrated for various offsets 

and spans can be direct or reverse acting to provide signal 

inversion.

The device also includes a regulated power output that can 

be used to power a transducer or a resistance input. It features 

top-adjust trim-pots for offset, gain, input attenuation and 

reverse-offset calibration. There is also an LED power indicator.

The product comes with standard snap-track for easy mounting or is also available mounted in a hinged 

ABS enclosure

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the device. Failure to follow these 

instructions may result in product damage. Do not use in an explosive or hazardous environment, with 

combustible or flammable gases, as a safety or emergency stop device or in any other application where 

failure of the product could result in personal injury. 

Take electrostatic discharge precautions during 

installation and do not exceed the device ratings.

MOUNTING

The snap-track device may be mounted in any position. Use only fingers to remove the PCB from the 

snap-track, do not pry on the PCB with tools. Do not flex the PCB during removal or installation. Slide the 

PCB out of the snap-track. See Figure 1. Ensure any metallic mounting hardware does not contact the 

underside of the PCB.

Avoid mounting in areas where the device is exposed to vibrations 

or rapid temperature changes. Mount the snap track with the PCB 

removed using two screws as shown in Figure 2.

Once the snap track is mounted, place one side of the PCB into the 

snap track and gently press the other side of the PCB with two fingers 

evenly placed at each corner until the PCB snaps into place, see Figure 

3.

If the enclosure is present it is to be mounted on a vertical surface 

using the four integrated mounting holes that facilitate a #10 screw 

(not supplied) as shown in Figure 4. 

Open the enclosure by pulling on the latch on the right side of the 

enclosure, at the same time pull on the cover as illustrated in Figure 4.

Make wire connections as per the "Wiring" instructions on page 2.

Swing the door closed until latched. For added security, two screws 

are provided that may be installed in the integrated screw tabs. See 

Figure 5.

Figure 1

Figure 3

Figure 4

Figure 5

Figure 2

IN-GE-GTASMXXX-01 03/20

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Analog Scaling Module

GT-ASM Series - Installation Instructions

Содержание GT-ASM Series

Страница 1: ...ed in any position Use only fingers to remove the PCB from the snap track do not pry on the PCB with tools Do not flex the PCB during removal or installation Slide the PCB out of the snap track See Figure 1 Ensure any metallic mounting hardware does not contact the underside of the PCB Avoid mounting in areas where the device is exposed to vibrations or rapid temperature changes Mount the snap tra...

Страница 2: ...nsor CALIBRATION AND SET UP The device is typically calibrated with a voltage type input signal to simplify the procedure If the actual input signal will be a current type then convert the required current signal to voltage first and apply the voltage signal for this procedure Calibration Voltage Input Current Signal Amps x 250 For example if the input signal will be 4 20 mA then use a 1 5 Vdc cal...

Страница 3: ...e required INPUT voltage signal span Vin_span Vin_max Vin_min Examples 0 5 V input 5 volt span 3 12 V 9 volt span If the input is to be 4 20 mA use the equivalent calibration voltage calculated previously 4 20 mA 1 5 V 4 V span Calculate the required OUTPUT voltage signal span Vout span Vout max Vout min Examine 3 15 V output 12 volt span STEP 6 Apply the input voltage span result to the IN termin...

Страница 4: ...ed value then move the OFFSET jumper to the position and adjust the OFF pot to obtain the correct minimum output on the meter If the output reading must be decreased to the desired value then move the OFFSET jumper to the position and adjust the OFF pot to obtain the correct minimum output on the meter Remember that increasing or decreasing the offset value will also increase or decrease the maxim...

Страница 5: ...OUT V mA PWR COM 20V IN OUT ATN GAN REV OFF POWER PCB Jumpers set up for normal acting no offset mA input and voltage output 0001256 REV NORM IN GE GTASMXXX 01 03 20 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...