background image

CDD4 Duct Carbon Dioxide Transmitter                                               

Installation Manual 

 

 

May 27, 2013

                         

4

 

Setup Menu 

The menu has several items shown below. Some items change depending on the hardware configuration and the CO2 sensor. 

To enter the menu, press and release the <MENU> key while in normal operation. This will enter the SETUP menu step 1, 

pressing <MENU> a second time advances to step 2. Each press of <MENU> advances the menu. No values are saved or 

changed  by using <MENU>.  The <ROLL> key is used to make changes to program variables by scrolling  through the 

available options. When a value is changed, use the <SAVE> key to save it to memory and advance to the next menu item. 

 

<MENU> 

Press and release the <MENU> key to enter the SETUP menu. 

 

If the 2000 ppm CO2 sensor is installed (CDD4A model) 

1.

   Out High  

The default range is 0-2000 ppm. The span can be changed from 1000 to 7500 ppm in increments of 

     2000 ppm 

500. Use the <ROLL> key to change the value and <SAVE> to save. The factory default is 2000 ppm. 

 

If the 20,000 ppm CO2 sensor is installed (CDD4B model) 

1.

   Out High  

The default range is 0-20,000 ppm. The span can be changed from 2000 to 20,000 ppm in increments of 

     20000ppm 

500. Use the <ROLL> key to change the value and <SAVE> to save. The factory default is 20,000 ppm. 

 

<MENU> 

 

2.

   Altitude 

The default is 0 feet. Change by using the <ROLL> key from 0 to 5000 feet in 500 ft increments. Change 

            0 Ft 

for CO2 local altitude correction and press <SAVE> to save a change. 

 

<MENU> 

 

This item is omitted if the 20,000 ppm dual-channel sensor is installed 

3.

   Auto Cal 

Automatic Cal Mode default is ON to correct CO2 sensor drift to better than 

 10 ppm per year. Change 

          ON 

with the <ROLL> key and save using <SAVE>. ON is recommended for applications where the CO2 

level will be close to normal (400 ppm) at least once per day. If a building is occupied 24 hours and the 

CO2 level is fairly constant then this should be set to OFF. 

 

Items 4, 5 and 6 are only available if the Relay Option is installed, otherwise the menu skips directly to step 7. 

 

4.

  Relay SP 

The relay trip setpoint default is 1000 ppm. It can be changed from 500 to 5000 in 100 ppm increments 

    1000 ppm 

for the 2000 ppm CO sensor or 500 to 15,000 for the 20,000 ppm sensor. Save changes by using the 

 

 

<SAVE> key. 

<MENU>

 

 

5.

 Relay Hy 

The relay hysteresis default is 50 ppm. This can be changed from 25 to 200 in 25 ppm increments for 

      50 ppm 

the 2000 ppm sensor or 25 to 500 ppm for the 20,000 ppm sensor. Use <SAVE> to save any change. 

 

<MENU> 

 

6.

    Relay 

Use the <ROLL> key to toggle the relay ON or OFF for testing purposes. Press either  <SAVE> or 

    Test OFF 

<MENU> to turn the relay off and advance to the next item. 

  

<MENU> 

 

7.

 Out Type 

For voltage, the factory default output type is 0-5 Vdc. Use the <ROLL> key to change the value to 0-10  

     0-5 Vdc 

Vdc if necessary. Press the <SAVE> key to save. If the switch is set to mA, then 4-20 mA is displayed. 

 

<MENU> 

 

8.

   Output 

Use the <ROLL> key to toggle the output OFF (normal operation), MIN (minimum output) or MAX 

    Test OFF 

(maximum output) for testing purposes. Press either <SAVE> or <MENU> to set it back to OFF and 

advance to the next item.

 

<MENU> 

DISC

ONTINUED

Содержание CDD4

Страница 1: ...ht section of duct at least five feet from corners and other items that may cause disturbances in the air flow Avoid areas where the detector is exposed to vibrations or rapid temperature changes The duct CO2 transmitter principal of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the pr...

Страница 2: ...d the controller The analog output is available on the CO2 terminal This signal is switch selectable for either voltage or 4 20 mA active output In voltage mode the output is selectable for either 0 5 or 0 10 Vdc via the menu the factory default is 0 5 Vdc The current output operates in the active mode and does not require a loop power supply This means that the signal current is generated by the ...

Страница 3: ...cover of the unit to be calibrated to expose the gas sensor chamber The tubing from the gas bottle can be connected to either port on the chamber after the plastic cap is removed Gently remove one cap and connect the tubing note that strong shock or vibration can affect calibration Ensure the device has been operating normally for at least five minutes before applying gas Turn the valve knob on th...

Страница 4: ...tem is omitted if the 20 000 ppm dual channel sensor is installed 3 Auto Cal Automatic Cal Mode default is ON to correct CO2 sensor drift to better than 10 ppm per year Change ON with the ROLL key and save using SAVE ON is recommended for applications where the CO2 level will be close to normal 400 ppm at least once per day If a building is occupied 24 hours and the CO2 level is fairly constant th...

Страница 5: ...24 Vac with all options Output Signals 4 20 mA active sourcing 0 5 Vdc or 0 10 Vdc field selectable Output Drive Capability 550 ohms maximum for current output 5 Kohm min for voltage output Output Resolution 10 bit PWM Input Voltage Effect Negligible over specified operating range Protection Circuitry Reverse voltage protected overvoltage protected Operating Conditions 0 50 C 32 122 F 0 95 RH non ...

Страница 6: ...x 8 characters Backlight Enable or disable via keypad Optional Temperature Signal Sensing Element Various RTDs and thermistors available as 2 wire resistance output Optional Relay Output Contact Ratings Form A contact N O 2 Amps 140 Vac 2 Amps 30 Vdc Relay Trip Point Programmable via keypad Relay Hysteresis Programmable via keypad D I S C O N T I N U E D ...

Отзывы: