The BackLite setting is used to control how the LCD backlight functions. Use 

<UP> or <DOWN> to select either Auto, Off or On. Auto means the backlight only 

lights when a menu is accessed or when the setpoint is activated (ie: when a key 

is pressed), Off means the backlight is always off and On means it is always on. 

Factory default is Auto.

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

9. BACKLIGHT

Only if 

Relay

 option Installed

Only if 

Temperature Sensor

 option Installed

Relay

CO2

T Offset

0.0 

°

C

The Relay setting allows the relay alarm to be assigned to either CO

2

 High, 

CO

2

 Low, Temp Hi or Temp Low as applicable. Use <UP> or <DOWN> to select. 

Factory default is CO

2

 High. If the temperature sensor is not installed then the 

options will not be available.

The T Offset value allows calibration of the temperature value displayed on the 

LCD. Units (°C/°F) follow the Temp Units setting. Use <UP> or <DOWN> to add 

or subtract an offset from the temperature value. The range is -5.0 to 5.0 °C or 

-9.0 to 9.0 °F in 0.1° increments. Factory default is 0.0 °C.

11. RELAY

10. TEMPERATURE OFFSET

Relay SP

1000 ppm

Relay SP

1000 ppm

The relay setpoint depends on the relay assignment set previously. Use <UP> 

or <DOWN> to change the setting within the limits as shown in the table. 

Note that only the one previous selection will be available. Note that a high 

alarm activates when the measurement exceeds the setpoint and a low alarm 

activates when the measurement goes below the setpoint. Use <MENU> to 

save and advance.

or

12. RELAY SETPOINT

RELAY ASSIGNMENT

DEFAULT SETPOINT

SETPOINT RANGE

RESOLUTION

Temp High

26.0°C / 79.0°F

5.0 to 40.0°C / 40.0 to 100.0°F 0.5°

Temp Low

15.0°C / 59.0°F

5.0 to 40.0°C / 40.0 to 100.0°F 0.5°

CO

2

 High

1000 ppm

500 to 9000 ppm

100 ppm

CO

2

 Low

1000 ppm

500 to 9000 ppm

100 ppm

<MENU> 

Press to advance to next menu item

<MENU> 

Press to advance to next menu item

Relay Hy

50 ppm

Relay Hy

0.5 

°

C

The Relay Hysteresis will depend on how the relay is assigned. Units will either 

be in ppm for CO

2

 or °C/°F for temperature.

Use <UP> or <DOWN> to change the Relay Hysteresis within the limits as 

shown in the table.

Note that a high alarm resets when the measurement goes below (setpoint 

- hysteresis) and a low alarm resets when the measurement goes above 

(se hysteresis). Note the value is somewhat dependent on the setpoint 

(ie: if the CO

2

 setpoint is 500 ppm then the hysteresis cannot be 500 ppm).

or

13. RELAY HYSTERESIS

RELAY ASSIGNMENT

DEFAULT SETPOINT

SETPOINT RANGE

RESOLUTION

Temp High or Low

0.5°C/F

0.2 to 5.0°C/F

0.1°C/F

CO

2

 High or Low

50 ppm

25 to 500 ppm

25 ppm

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

IN-GE-CD2DTXXX-03

Содержание CD2DT Series

Страница 1: ... intended for life safety applications NOTE This CO2 sensor incorporates a Self Calibration feature to correct CO2 sensor drift This feature is recommended for applications where the CO2 will be exposed to fresh air 400 ppm at least one hour per day If the monitored space is occupied 24 hours or consistently maintains higher or lower levels of CO2 it is recommended that this feature be turned off ...

Страница 2: ...ram See Figure 5 This is a 3 wire sourcing device Connect the plus DC or the AC voltage hot side to the PWR terminal and the common is connected to the COM terminal The device is reverse voltage protected and will not operate if connected backwards It has a half wave power supply so the supply common is the same as the signal common Several devices may be connected to one power supply and the outp...

Страница 3: ...ired SETUP MENU The device has several parameters that can be configured locally via the Setup menu using the keypad and LCD Any changes made are saved in non volatile memory and are restored in case of a power loss The menu can be accessed at any time after the start up mode and if there is 5 minutes of inactivity the menu will close and normal operation will continue To enter the menu press and ...

Страница 4: ...actual output signal will depend on the PCB switch position mA or VOLT and the V Output setting for voltage operation Press MENU to set it back to OFF and advance Factory default is OFF MENU Press to advance to next menu item MENU Press to advance to next menu item 6 OUTPUT TEST Temp Units C Display CO2 ppm CO2 1235 ppm Temp 24 3 C 1235 ppm 24 3 C CO2 1235 ppm Temp 24 3 C The Temp Units setting is...

Страница 5: ...nge the setting within the limits as shown in the table Note that only the one previous selection will be available Note that a high alarm activates when the measurement exceeds the setpoint and a low alarm activates when the measurement goes below the setpoint Use MENU to save and advance or 12 RELAY SETPOINT RELAY ASSIGNMENT DEFAULT SETPOINT SETPOINT RANGE RESOLUTION Temp High 26 0 C 79 0 F 5 0 ...

Страница 6: ...ue Another method is to determine the CO2 ambient level using a calibrated unit as a reference and adjust calibration setting to desired value MENU Press to advance to exit the Setup Menu and return to normal mode 17 CALIBRATE 16 CALIBRATE CALIBRATION Calibration with gas requires a field calibration kit with pressure regulator tubing sensor adapter and bottle of CO2 gas The certified calibration ...

Страница 7: ...ve 24 Vdc Current 550Ω max Voltage 10 000Ω min Ambient Operating Range 0 to 50 C 32 to 122 F 0 to 95 RH non condensing Storage Conditions 40 to 70 C 40 to 158 F 0 to 95 RH non condensing LCD Display Units ppm CO2 C F for optional temperature setpoint Display Range 0 10 000 ppm 0 to 50 C 0 to 122 F Display Size 35mm W x 15mm H 1 4 x 0 6 Digit Height 2 line x 8 character OPTIONAL TEMPERATURE SENSOR ...

Отзывы: