Product description 

 

3.1  Mounting description 

Instructions for mounting: 

 

 When mounting the instrument, ensure that the sealing faces of the in-
strument and the measuring point are clean and undamaged. 

 

Screw in or unscrew the instrument only via the flats using a suitable tool 
(fixed spanner, wrench size 27mm) and the prescribed torque. The ap-
propriate torque depends on the dimension of the pressure connection 
and on the sealing element used (form/material).  
A maximum torque of 50 Nm must not been exceeded. Do not use the 
case as working surface for screwing in or unscrewing the instrument. 

 

When screwing the transmitter in, ensure that the threads are not 
jammed.  

 

 As described in the installation example the sealing (

GDZ-28

) must be 

made at the face surface of the pressure connection. 

 

 

3.2  Identification 

Examples for type plates 

 







Type 



CE-Mark, with code of the notified body monitoring the 
quality assurance system for the production 



Approval number 



Ex identification 



Date for month/year of manufacture 





 

 



Serial number 



Measuring range 

3.3  Operating and Maintenance Advice 

a.) You must only use the sensor with GMH 3111 - ex, GMH 3151 - ex or GMH 3156 - ex devices! 

Usage of other devices may result in destruction of sensor and device. 

b)  Treat sensor and device carefully. Use only in accordance with above specification. (do not throw, hit against etc.).  

Protect plug from soiling. 

c)  To disconnect pressure sensor adapter cable from the device do not pull at the cable but at the plug  (to open 

lock). 
When connecting the sensor make sure that arrows are pointing upwards and that plug is entered into device 
socket centrally. Do not twist plug when entering socket. 
If plug is entered correctly, it will slide in smoothly 

 

If plug is twisted or entered incorrectly the connecting pins of the plug can be spoilt by bending or broken   
=> Plug can no longer be used and connecting cable needs to be replaced. 

d) 

MSD … .RE - ex

  (= relative pressure sensor): 

 

Caution:   The pressure compensation hole has to be kept clean! It is placed at the back part of the housing. 

 

Do not cover with stickers or similar things! 

 

 

 

 
 
 
 

      Torque 

 

      

max. 50 Nm 

 
 
 
 
 
 
 
 
 
Sealing 

GDZ-28

 

Содержание MSD-ex Series

Страница 1: ...M Messtechnik GmbH Hans Sachs Str 26 93128 Regenstauf GERMANY Tel 49 9402 9383 0 info greisinger de www greisinger de Digital pressure sensor for GMH 3111 ex GMH 3151 ex and GMH 3156 ex Operating Manu...

Страница 2: ...y in order to be able to look up in the case of doubt 2 Safety 2 1 Intended Use The pressure sensors are designed for the connection to an hand held instrument of the following types GMH 3111 ex GMH 3...

Страница 3: ...device 5 When using a GMH 3156 ex with 2 stainless steel sensors take care that the sensors are not screwed in or have contact to surfaces with different electrical potentials 6 Potential equalisation...

Страница 4: ...oduction Approval number Ex identification Date for month year of manufacture Serial number Measuring range 3 3 Operating and Maintenance Advice a You must only use the sensor with GMH 3111 ex GMH 315...

Страница 5: ...ex MSD 600 BRE ex MSD 1000 BRE ex MSD RE ex special range Measuring range 0 00 60 00 bar rel 0 0 100 0 bar rel 0 0 160 0 bar rel 0 0 250 0 bar rel 0 0 400 0 bar rel 0 0 600 0 bar rel 0 1000 bar rel re...

Страница 6: ...manufacturer have to be free of any residual of measuring media and or other hazardous substances Measuring residuals at housing or sensor may be a risk for persons or environment Use an adequate tra...

Страница 7: ...H57 0 1X 6C 03 Operating Manual MSD ex page 7 of 8...

Страница 8: ...H57 0 1X 6C 03 Operating Manual MSD ex page 8 of 8 7 Addendum 1 EU Declaration of Conformity...

Отзывы: