Js/gp/bbq/bbqbench/milobenchelectricalwiringrequirements.doc Updated 08.09.14 

 

 

 

Myles Single Bench Base Slab Information and Electrical Wiring Requirements 

 

Suggested slab size 2866 mm x 2866 x 100 mm thick 

Base size of Milo barbecue bench 872 mm x 872 mm OD 

130 mm turn in for fixing of bench to the concrete slab 

4 x M10 Dyna bolts 50 mm deep (supplied) 

 

ELECTRICAL WIRING REQUIRMENTS: 

Electrical wiring to waterproof GPO 10 amp to AS3000:2007 standard requires a minimum of 2.5 mm² cabling for each Greenplate Inbench 

barbecue unit, larger for long runs, with each barbecue unit having it’s own 20 amp RCBO C-Curve type A in the mains sub-board. 

“Under No circumstance should more than one barbecue unit be on one power line.  Failure to install correctly will VOID 

the warranty as damage to the electrical equipment will occur.” 

 

 

872 MM 

872 MM

 

Single GPO power point with 

separate 10 amp circuit for each GP 

300 Inbench Unit to be installed on 

timber or steel post 200 mm from 

back wall, of Milo bench 

 

[BASE VIEW] 

200 MM 

130 MM 

DOOR 

2866 MM 

250 MM 

 2866 MM 