Barbecue Bench Electrical Wiring Requirements
Suggested slab size
3765
mm x 286
5
mm x 100 mm thick.
Base size of M
yles
barbecue bench
1772
mm x
8
72
mm OD
130
mm turn in for fixing of bench to the concrete slab
6
x M10 Dyna bolts 50 mm deep (
S
upplied)
Level bench by adjusting Leveling Feet.
ELECTRICAL WIRING REQUIRMENTS:
Electrical wiring to waterproof GPO 10 amp to AS3000:2007 standard requires a minimum of 2.5 mm² cabling for each Greenplate Inbench
barbecue unit, larger for long runs, with each barbecue unit having it’s own 20 amp RCBO C-Curve type A in the mains sub-board.
“Under No circumstance should more than one barbecue unit be on one power line. Failure to install correctly will VOID
the warranty as damage to the electrical equipment will occur.”
SINGLE GPO POWER POINT WITH
SEPARATE 10 AMP CIRCUIT FOR
EACH INBENCH BBQ UNIT TO BE
INSTALLED
50
mm
CENTRE
FROM
BOTTOM FOLD OF THE
RIGHT
SIDE
PANEL ON A GPO SUPPORT POST.
FRONT
S:\Libraries\Documents\Greenplate BBQ Info\Bench Wiring Requirements\
M
yles
Double
Extended Top
Barbecue Bench Installation Information PID.doc | Updated 14-08-2018
SINGLE GPO POWER POINT WITH
SEPARATE 10 AMP CIRCUIT FOR
EACH INBENCH BBQ UNIT TO BE
INSTALLED
5
57
mm
CENTRE
FROM
BOTTOM FOLD OF THE
RIGHT
SIDE
PANEL ON A GPO SUPPORT POST.