11
CMT-90
Accuracy
Refer to “Specifications” for operating conditions and temperature coefficient.
Accuracy is specified as follows:
±
(a percentage of the r a fixed
amount) at 23
°
C
±
5
°
C (73.4
°
F
±
9
°
F), 0% to 80% relative humidity.
Accuracy for AC measurements is specified for input crest factors that do not
exceed the values in the “Maximum Input Crest Factor” table on this page.
Accuracy Table
Characteristic
Range
Accuracy
Frequency
Range
0.6 to 170.0 A
±
(1.9% + 1 A)
AC Current
170.1 to 600.0 A
±
(1.9% + 2 A)
50 to 60 Hz
AC Voltage*
1.3 to 999.9 V
±
(1.5% + 0.3 V)
50 to 500 Hz
DC Voltage*
1.8 to 999.9 V
±
(1.0% + 0.2 V)
N/A
–0.6 to –999.9 V
±
(1.0% + 0.4 V)
Resistance**
0.0 to 99.9
Ω
±
(2% + 1.0
Ω
)†
N/A
100 to 2000
Ω
±
(2% + 2
Ω
)†
* Input impedance: 4 k
Ω
nominal at voltages up to 30 V;
increases with voltage to approximately 277 k
Ω
at 1000 V
** Open circuit voltage: 1.5 V maximum
† Multiply temperature coefficient times 1.5 when operating temperature
is above 40
°
C.
Maximum Input Crest Factor
Continuity
Tone on: Circuit resistance is
≤
25
Ω
(approximately).
Tone off: Circuit resistance is
≥
400
Ω
(approximately).
Maximum
Current
Voltage
Crest Factor
Range
Range
1.414
0.6 to 6.0 A
1.3 to 3.0 V
3
6.1 to 20.0 A
3.1 to 10.0 V
5
20.1 to 500.0 A
10.1 to 250.0 V
Linear decrease from
5 to 1.5 over
500.1 to 600.0 A
250.1 to 999.9 V
range shown
Содержание CMT-90
Страница 10: ...10 Typical Measurements Voltage Measurement Resistance Measurement Continuity Check...
Страница 23: ...23 CMT 90 Mediciones m s comunes Medici n de tensi n Medici n de resistencia Verificaci n de continuidad...
Страница 28: ...28...
Страница 37: ...37 CMT 90 Mesures types Mesure de la tension Mesure de la r sistance V rification de la continuit...
Страница 42: ...42...
Страница 43: ...43 CMT 90...