Greenheck Sure-Aire 386719 Скачать руководство пользователя страница 7

Sure-Aire™ Flow Monitoring System

7

®

Recalibration Procedure

The electronics are calibrated per order at the factory. Under certain circumstances, there may be a discrepancy 
of calibration once installed on site. The following procedure is used to re-calibrate the pressure trandsucer within 
the electronics. In the event an error occurs trying to re-calibrate, the tranducer parameters can be re-set to factory 
settings using “Load Factory Settings” within the setup menu.

Equipment

Digital multimeter.
Vacuum pressure device with gauge (only needed if calibrating upper range).
200-900 ohm resistor (only needed if calibrating using 4-20 mA).

Procedure

1.  Remove power to the electronics.
2.  Remove any wires connected on the analog outputs.
3.  Remove tubing from Sure-Aire™ electronics box, box uses push-to connect fittings.
4.    Connect multimeter to analog points on terminal strip. If calibrating using 4-20 mA, a series load resistor 

between 200 and 900 ohms is required.

5.  Set multimeter to the correct measurement units, VDC or mA.
6.  Apply power to the Sure-Aire™ electronics.
7.  Press the “Setup“ button on the LCD panel.
8.  Verify the analog signal is setup for your measurement and that the signal is linear to Differential Pressure.
9.    Go to the “Trans Min/Trans Max” screen. Record the values for each. It is correct that the trans min value is 

higher than the trans max value.

10.  Press “Enter / Edit”.
11.    With all tubing removed, adjust the trans min value up / down until the multimeter reads either 2 VDC or 4 mA.
12.  Press “Next” if only calibrating low value. Press “Enter” to complete.
13.    To calibrate upper range, apply the pressure device to the high port and pull vacuum to maximum pressure on 

Sure-Aire™ label.

14.  Adjust the trans mix value up/down until the multimeter reads either 10 VDC or 20 mA.
15. Press “Enter” to store the new value.
16.  Press “Exit” to return to the main screen.
17.  Optional: go to “Save Customer Defaults” and save for future resetting to the changes.

Содержание Sure-Aire 386719

Страница 1: ...P Modbus Temperature compensation for air density Tools Required Four 4 8 32 screws 1 4 inch nylon tubing length dependent on distance between fan and Sure Aire electronics maximum 75 feet 23 m each line Sensor wiring for temperature sensor if temperature sensor is being used Pressure ranges reflect differential pressures between the fan inlet and inlet cone not system static pressure Flow Accurac...

Страница 2: ...ronics is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly maintained between 30 to 110 F 1 to 43 C Wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Removing from Storage As electronics are removed from storage to...

Страница 3: ...ctronics page 7 Switch SW1 2 Wire 4 Wire Select Left Position 2 Wire Right Position 4 Wire 4 3 Temperature Density Compensation Temperature compensation can adjust airflow calculation based on changing airstream temperatures If temperature compensation is not used the air density value will be a function of standard air 70 F 21 C The supplied sensor measures the exterior temperature of the ductwor...

Страница 4: ...er you are in i e Setup will change to Home and Home will change to Edit Home Screen To view the different settings use the Up and Down buttons to scroll through the list To adjust settings press Setup and scroll through the settings Below is information on the adjustable settings Settings Menu Home Screen Top Bottom View Press Edit to change Main Display Value Press Prev or Next to adjust what re...

Страница 5: ... Server Device Settings Setting Value Baud Rate Set to match BMS Parity No Parity 1 Stop Bit APDU Timeout ms 1000 Number of APDU Retries 3 Max Master Address 127 Max Info Frames 1 Modbus RTU Slave When the electronics is configured for Modbus it will expose a total of seven 7 registers on the network The Modbus RTU Slave settings and list of registers can be seen below Modbus RTU Slave Device Sett...

Страница 6: ...c fan model and size ΔP is the measured differential pressure across the inlet cone in wg and is the density of air lb ft3 CFM K P Voltage and Amperage Signal If using the analog signal linear to flow the max flow is automatically calculated based on the pressure range and K factor input into the electronics The max value is displayed in the setup menu If output signal is linear to pressure the co...

Страница 7: ...f calibrating using 4 20 mA a series load resistor between 200 and 900 ohms is required 5 Set multimeter to the correct measurement units VDC or mA 6 Apply power to the Sure Aire electronics 7 Press the Setup button on the LCD panel 8 Verify the analog signal is setup for your measurement and that the signal is linear to Differential Pressure 9 Go to the Trans Min Trans Max screen Record the value...

Страница 8: ...79 not applicable not applicable 355 329 8 not applicable not applicable 179 not applicable 179 not applicable not applicable 400 406 9 not applicable not applicable 179 408 179 248 not applicable 450 536 10 not applicable not applicable 179 not applicable 179 202 not applicable 500 652 12 355 592 244 408 244 296 not applicable 560 847 13 not applicable 701 not applicable not applicable 296 351 no...

Отзывы: