Pressure Drop Data 

SSSMD-201

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All 

data has been corrected to represent standard air at a density of .075 lb/ft

3

 (1.201 kg/m

3

).

Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an 

analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC 

system.

AMCA Test Figures

Figure 5.3

 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations 

because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper. 

Figure 5.2

 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than 

Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Figure 5.5

 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high 

entrance and exit losses due to the sudden changes of area in the system.

5D

6D

5D

D

4 (W) (H)

3.14

Содержание Stainless Steel 3V Blade SSSMD-201

Страница 1: ...exible 304 stainless steel jamb seals Linkage 304 stainless steel concealed in jamb Axles 1 2 in 13mm dia 304 stainless steel Bearings 304 stainless steel sleeve type Size Limitations Minimum Size 8 i...

Страница 2: ...stem AMCA Test Figures Figure 5 3 Illustrates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by s...

Страница 3: ...sureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 04 500 0 02 500 0 01 500 0 01 1000 0 14 1000 0 07 1000 0 04 1000 0 06 1500 0 31 150...

Страница 4: ...0 0 48 3500 0 33 3500 0 53 4000 1 44 4000 0 63 4000 0 42 4000 0 70 12in x12in 305mm x 305mm 24in x24in 610mm x 610mm 36in x36in 914mm x 914mm 12in x48in 305mm x 1219mm Velocity fpm Pressure Drop in wg...

Страница 5: ...pm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 06 500 0 03 500 0 03 500 0 03 1000 0 22 1000 0 14 1000 0 12 1000 0 13 1500 0 50 1500 0 31 1500 0 26 1500 0 3...

Страница 6: ...ry standard sideplate and sleeve mountings for the SSSMD 201 The standard A dimensions listed in the table provide adequate space for the mounting of actuators and controls If space constraints are a...

Страница 7: ...longitudinal grooves for reinforcement Blades shall be completely symmetrical relative to their axle pivot point presenting identical resistance to airflow and operation in either direction through t...

Отзывы: