4.  SECURING THE DAMPER/SLEEVE ASSEMBLY TO 

WALL OPENINGS.

   Damper/sleeve assemblies must be installed in wall 

openings using flanges and sheet metal screws as 
illustrated and described below.

  •  Flange on front (grille end) of sleeve must be a 

minimum of 16 gauge (1.5mm) steel and have a 

5

8

 in. 

(16mm) minimum flange leg (refer to 

Figure 2

). Using 

#10  (19mm) sheet metal screws, screw from inside 
of sleeve through the rear portion of the studs (as 
shown in 

Figure 1

). Space screws a maximum of 6 in.  

(152mm) on center and a maximum of 2 in.  (51mm) 
from the corners (minimum of 2 screws per side). 
No retaining angles are required on the side of wall 
opposite from the grille.

  •  Retaining angles on continuing duct must be a 

minimum of 1 

1

2

 in. x 1 

1

2

 in. (38mm x 38mm) 16 gauge 

(1.5mm) steel (refer to 

Figure 3

). Screwing sleeve to 

steel studs is not required.

  •  Retaining angles must be attached to the sleeve using 

one or more of the following methods of attachment: 
 

• Tack or spot welds 

 

• #10  (19mm) sheet metal screws 

 

• 

1

4

 in. (6mm) bolts and nuts 

 

• 

3

16

 in. (4.7mm) steel pop rivets

   Attachments must be spaced a minimum of 6 in. 

(152mm) on center and a maximum of 2 in. (51mm) from 
corners. The angles must be attached to all 4 sides of 
the sleeve. A minimum of two attachments are required 
on each side, top and bottom. The angles need not be 
attached to each other at the 

corners.

   c

aution

!

 

Do not tear the thermal blanket during 

installation.

   Dampers are tested for correct operation and are square 

and straight before shipment from the factory. Dampers 
must be installed square and straight and must not be 
twisted or racked. Failure to install the damper square 
and straight may prevent the damper blades from 
operating open and closed.

5. ACTUATOR CONNECTIONS
 

 

Electrical and/or pneumatic connections to 
damper actuators should be made in accordance 
with wiring and piping diagrams developed in 
compliance with applicable codes, ordinances 
and regulations (see 

Electrical Guidelines).

6  

Recommended Preparation of Openings in 

Wood and Metal Stud Walls

  • Frame wall openings as shown (see 

Figure 4

)

  •  Double vertical studs are not required for openings 36 

in. x 36 in. (914mm x 914mm) or smaller.

  •  Gypsum wall board must be fastened 12 in. (305mm) 

on center to all stud and runner flanges surrounding 
opening(see 

Figure 4)

.

  •  All construction and fasteners must meet the 

requirements of the appropriate wall design (See UL 
Fire Resistance Directory) and/or local codes.

5IFSNBM#MBOLFU

 JOTUBMMFEBSPVOEFOUJSF

PVUTJEFTVSGBDFPGTMFFWF

8BMM

'MBOHF

Figure 2:  Sleeved damper with Thermal 

Blanket (duct termination).

3FUBJOJOH"OHMF

5IFSNBM#MBOLFU

 JOTUBMMFEBSPVOE

FOUJSFPVUTJEF

TVSGBDFPGTMFFWF

JO.BY

JO.BY

JO.BY

JO.BY

8BMM

Figure 3:  Sleeved damper with Thermal 

Blanket (duct continuation).

Note: Thermal blanket is riveted to the damper sleeve and 
the seam is taped with acrylic adhesive tape, FSK facing 
tape 152 5CWnt, manufacuted by Venture Tape Company.  