background image

Fire Damper Sleeve

Neoprene or Butyl gasket

between all angles

Flanged system angles

(Attach per

manufacturer's

instructions)

Duct

3/8 in. bolts in
corners are optional

6 in. long metal cleat or 1/16 in.

max. thickness plastic cleat;

12 in. c-c (min. 1 per side)

Figure 13

Duct

Sleeve

6 in.

Std. Clip
Length

CL

Duct

60 in. Duct

4 Req’d.

48 in. Duct

3 Req’d.

36 in. Duct

3 Req’d.

24 in. Duct

2 Req’d.

18 in. Duct  &

Smaller

1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in.

6 in.

9 in.

7 in.

7 in.

5 in.

5 in.

5 in.

5 in.

Figure 15

Duct End
Flange

Corner Piece

3/8 in. bolt 
(optional)

Figure 16

Proprietary Flange System Breakaway Connections

(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF 
addendum to the SMACNA Duct Construction Standards. Standard 6 in. (152 mm) metal clips may be used with 
spacing as shown in diagram (

see Figure 14 & 15

). A 

3

8

 in. (9.5 mm) metal bolts and nuts may be used to fasten 

together corner pieces (

see Figure 16

).

Duct

Sleeve

6 in.

Std. Clip
Length

CL

Duct

60 in. Duct

4 Req’d.

48 in. Duct

3 Req’d.

36 in. Duct

3 Req’d.

24 in. Duct

2 Req’d.

18 in. Duct  &

Smaller

1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in.

6 in.

9 in.

7 in.

7 in.

5 in.

5 in.

5 in.

5 in.

Figure 14

Manufactured Flanged System Breakaway Connections

Flanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ are 
approved as breakaway connections when installed as illustrated (

see Figure 13

).

Figure 17: Metal cleat method

Figure 18: Screw method

TDC/TDF to Manufactured Flange

Flanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ can 
be connected to TDC and TDF system as an alternate breakaway connection. This alternate connection is covered 
under the UL certification of the damper. See Supplement: Duct-Sleeve Connection (IOM #468502) for more 
information.

Spot weld or Tek screw per
manufacturer instructions

Spot weld or Tek screw per
manufacturer instructions

Damper Sleeve

Damper Sleeve

Butyl Gasket

Butyl Gasket

TDC or TDF

Connection

TDC or TDF

Connection

Metal cleat

#10 x 3/4”

TEK Screw

Spot weld or Tek screw per
manufacturer instructions

Spot weld or Tek screw per
manufacturer instructions

Damper Sleeve

Damper Sleeve

Butyl Gasket

Butyl Gasket

TDC or TDF

Connection

TDC or TDF

Connection

Metal cleat

#10 x 3/4”

TEK Screw

Out of Wall Fire and Combination Fire Smoke Dampers

9

®

Содержание ODFD Series

Страница 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Страница 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Страница 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Страница 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Страница 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Страница 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Страница 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Страница 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Страница 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Страница 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Страница 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Страница 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...