20
®
Model MSX Make-Up Air
Water Wizard™ User Interface
Key Function Description
Function Key
Recommended Water Pressure Chart
Housing
Size
Media Width
(inches)
Water Pressure
(in. wc)
MSX-H12
30
20
MSX-H22
43
3
⁄
4
36
60
61
MSX-H32
66
72
96*
42
MSX-H35
120*
61
MSX-H38
180*
37
MSX-H42
216*
51
*Multiple media sections. Values represent total media width.
WARNING
Opening the manual supply valve will allow water
to pass to the media. Be sure the sump is safely
draining before opening the manual supply valve.
NOTE
The manual supply valve ships closed and must be
adjusted for proper performance.
NOTE
The recommended water pressure is based on
media width. Refer to the table provided for proper
water pressure settings.
Start-Up - Water Wizard™ (optional)
Program Display
NOTE
Steps 6 through 8 are provided to adjust the
minimum cooling temperature. The minimum cooling
is preset to the factory recommended 75°F (24°C).
Only adjust if needed.
NOTE
The inlet air sensor function overrides and shuts
down the evaporative cooler if the outside
temperature falls below the minimum cooling
temperature.
7. Adjust the Minimum Cooling
Temperature
While in the
Program Menu,
use the Up and
Down Keys to
navigate the
Menu Options
until “toF” is
displayed. Press the
Enter Key to access the selected Menu Option setting.
Use the Up and Down Keys to adjust the Minimum
Cooling Temperature as needed. Press the Enter Key
to save the Minimum Cooling Temperature setting and
return to the Program Menu.
8. Exit Program Mode
After 15 seconds of idle time the controller will exit
Program Mode.
Minimum Cooling
Temperature Display
NOTE
The enter key must be pressed to save the new
minimum cooling temperature.
5. Check Media
Start the cooling cycle and check the media after one
hour of operation. If the media is continuously dry or if
too much water is draining from the sump tank, refer
to Troubleshooting, Water Wizard™.
6. Enter Program Mode
Press and hold
the Enter Key
for three seconds. The
display will read “Pro”
when Program Mode is
active.
L1
L2
L3
Enter Key
Up Key
Down Key
1. Open the Solenoid
Confirm that the manual water supply valve
is closed. Press and hold the Function Button
for one second. L3 will begin blinking (short on, long
off), indicating that Flow Test Mode is active and the
supply solenoid is open.
2. Set the Water Pressure
With the solenoid open, set the supply water
pressure to the correct setting (see table below).
Use the manual supply valve to adjust the supply
pressure. A pressure gauge is provided between the
manual supply valve and the media.
3. Break-in Media
Leave the supply solenoid open to saturate and
break-in media for 20 minutes with the blower off.
4. Close Solenoid
With the pressure set, press the Function Key
for one second to deactivate Flow Test Mode
and allow the supply solenoid to close.