background image

From

Gas

Gas Cock

1/8 in. Plugged

6 in. Trap

Ground Joint Union

To Controls

23

1. Single furnaces (furnace input 100 to 400 MBH)

have a single 

3

4

inch connection. Double furnaces

(furnace input 500 to 800 MBH) have two 

3

4

inch

connections, and triple furnaces (furnace input
1050 to 1200 MBH have three 

3

4

inch connections.

2. When connecting the gas supply, the length of the

run must be considered in determining the pipe
size to avoid excessive pressure drop. Refer to a
Gas Engineer’s Handbook for gas pipe capacities.

3. A drip leg should be installed in the pipe run to the

unit.

4. Install an easily accessible ground joint union and

a manual shut off valve (these are required by
some local codes) for emergency shut off and
easy servicing of the controls.

5. A 

1

8

inch NPT plugged tap shall be installed 

immediately ahead of the gas supply connection
to the furnace.

6. After gas piping is completed, carefully check all 

piping connections for gas leaks. Use soap
solution or equivalent for testing. DO NOT use a
flame or other source of ignition to check for gas
leaks.

7. When leak testing pressures above 14 in. wc (

1

2

psi), close the field installed shutoff valve,
disconnect the furnace and its gas train from the
gas supply line, and plug the supply line before
testing.

8. When leak testing at pressures equal to or less

than 14 in. wc (

1

psi) close the field-installed

shutoff valve to isolate the unit from the gas
supply line before testing.

Recommended Piping to Controls

Gas Supply Pressure Requirements

Natural:  6 to 14 in. wc

LP:  11 to 14 in. wc

Start-Up Instructions:

Furnace - Gas Connection

Manual Shut
Off Valve

Содержание IGX

Страница 1: ...Unit is approved for installation downstream from refrigeration units In these conditions condensate could form in the duct furnace and provision must be made to dispose of the condensate WARNING Impr...

Страница 2: ...tal and Downblast Discharge with Optional Mixing Box 5 Downblast Discharge Optional with Combination Extension 6 7 Venting for Indoor units 8 17 Control Center Layout 18 Start Up Electrical 19 Mixing...

Страница 3: ...ed by others Figure 1 Step 3 Install Venting Ductwork The instructions for the indoor venting are listed on the following pages Refer to your unit submittal to determine the correct venting option ins...

Страница 4: ...B The use of a duct adapter is recommended on a downblast arrangement to properly align the ductwork with the supply unit The duct adapter is only a guide and is not intended to be used as support for...

Страница 5: ...equipment support s Installation Instructions for Roof Mounted with Optional Mixing Box Arrangements HZ and DB Step 5 Assemble and Attach Weatherhood The weatherhood can now be assembled and attached...

Страница 6: ...e equipment support s to the roof remove metal cover flash to wooden nailer and reinstall cover Step 2 Install Combination Extension Install combination extension over curb use wood screws to lag in p...

Страница 7: ...bar hooked to the factory lifting lugs as shown in the diagram to lift and center the unit on the curb equipment support s NOTE THE USE OF ALL LIFTING LUGS IS MANDATORY WHEN LIFTING UNIT Use self tapp...

Страница 8: ...l clearance of 4 feet from electric meters gas meters regulators and relief equipment In Canada the minimum clearance is 6 feet 5 Local codes may supercede any of the above provisions 6 Be sure that t...

Страница 9: ...s recommended at the flue outlet before any elbows 7 Avoid venting through unheated spaces if possible To minimize condensation insulate any vent runs greater than 5 feet that must pass through an unh...

Страница 10: ...tion air from the outside The rule of thumb is that an opening of one square inch should be provided for every 1000 BTU per hour of input rating Vent Construction To vent using this method the vent te...

Страница 11: ...tical Venting A1 A 12 inch minimum A1 12 inch minimum but should size according to expected snow depth Standard Indoor Venting EXHAUST Exhaust Vent Terminal Air Inlet Building Roof Venting Instruction...

Страница 12: ...of the box Make sure to add the thickness of the wall or roof and the length of the mounting brackets Attach the proper length of pipe to the CVA using three corrosion resistant sheet metal screws and...

Страница 13: ...Side Air Inlet Concentric Side CVA Flue Outlet Non Concentric Side Air Inlet Non Concentric Side Flue Outlet Concentric Side Air Inlet Concentric Side Flue Outlet Non Concentric Side Air Inlet Non Con...

Страница 14: ...stallation of the combustion air intake guard 3 Caulk between the wall and the air intake pipe 4 Maintain 12 inches from the combustion air inlet guard to the back of the vent terminal 5 Now attach th...

Страница 15: ...6 Caulk the gap between the combustion air cap and the vent pipe with silicone sealant or other appropriate sealants suitable for metal to metal contact and temperatures of 350 degrees F Vertical Ven...

Страница 16: ...e as shown below Horizontal Venting Exterior Wall B A EXHAUST COMBUSTION AIR Pitch vent pipe downward from furnace 25 inches per foot C Field Supplied Support Brackets The venting parts listed above a...

Страница 17: ...ing A A A B C A1 A 12 inch minimum A1 12 inch minimum but should size according to expected snow depth B 24 inch minimum C 12 inch minimum EXHAUST COMBUSTION AIR Tee with drip leg and cleanout cap Com...

Страница 18: ...nal Exhaust Starter and Fusing Shown 6 Terminal Strip 24 Volt power at strip for control wiring Note This is a typical control center an exact wiring diagram is shipped with the unit Control Center La...

Страница 19: ...ad for CUBE exhaust fan through side breather tube The power lead should be of sufficient length as to allow the CUBE fan to hinge open and to allow service of the burner controls NOTE Any wiring runn...

Страница 20: ...the customer to program occupied and unoccupied operation periods Building Pressure Control requires field wiring from the unit to the factory provided remote control panel This option enables outdoor...

Страница 21: ...to measure the air volume is by using the pitot traverse method in the ductwork away from the blower Other methods can be used but should be proven and accurate To adjust the air volume change the fa...

Страница 22: ...8 988 926 871 823 780 741 1 PVF 150 150 120 4444 3704 3175 2778 2469 2222 2020 1852 1709 1587 1481 1389 1307 1235 1170 1111 1 PVF 200 200 160 5926 4938 4233 3704 3292 2963 2694 2469 2279 2116 1975 185...

Страница 23: ...ncy shut off and easy servicing of the controls 5 A 1 8 inch NPT plugged tap shall be installed immediately ahead of the gas supply connection to the furnace 6 After gas piping is completed carefully...

Страница 24: ...gnites burner by sparking 13 Flame Sensor Ensures that each burner has ignited Furnace Control Center Layout Figure 7 Furnace Control Center 1 2 3 4 5 6 7 10 11 12 13 8 9 WARNING Disconnect power supp...

Страница 25: ...fied the combination gas valve is de energized and the combustion blower shuts off following a 30 second post purge period Recovery from Lockout The ignition control will automatically reset after 1 h...

Страница 26: ...the pressure use the low fire adjustment screw on the combination gas valve High Fire Adjustment Low Fire Adjustment Solenoid Staged Temperature Controls The furnace stage controls are located in the...

Страница 27: ...ure for each furnace at the pressure test port see Figure 7 using a high quality manometer that can measure low gas pressures The pressure at high fire should be 3 5 in wc for natural gas and 10 0 in...

Страница 28: ...per operation and water drainage Piping should be of adequate size to provide sufficient supply of water to meet the maximum demand of the unit Installation Instructions for Optional Evaporative Cooli...

Страница 29: ...a without any air flow through the unit A jumper wire is required on the terminal strip to provide power to the evaporative cooler pump See the wiring diagram for the proper location This saturation p...

Страница 30: ...ULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head pressure available from the circulation pump Piping should be in accor...

Страница 31: ...eck for correct drives and rpm with catalog data Dampers or registers closed Open and adjust Dirty or clogged filters Clean or replace Leaks in ductwork Repair Elbows or other obstructions Correct or...

Страница 32: ...airflow fault will be declared If proper airflow is detected at any time a normal ignition sequence will begin Once proper airflow is detected the normal Sequence Of Operation for ignition will follo...

Страница 33: ...uble flush and clean the system more frequently C If this condition persists chemicals may need to be added Water pH should be maintained between 6 and 8 A Irregular water distribution on face of medi...

Страница 34: ...hesive spray can be applied to increase filter efficiency If disposable filters are installed check by holding up to a light source If light cannot pass through the filter it should be replaced Replac...

Страница 35: ...easer or compressed air Wipe the inside of the burner clean Cleaning the burner with a degreaser will slow the future buildup of dirt Before reinstalling the burner assembly look down the heat exchang...

Страница 36: ...hould be shut off and all the lines drained when the temperature drops below 50 F 4 When the evaporative cooler is going to be used for the first time each season it is recommended that the media be f...

Страница 37: ...his build up from plugging the drain and causing the drain pan to overflow Inspect twice a year to avoid the possibility of overflow Also drain pans should be kept clean to prevent the spread of disea...

Страница 38: ...38 Documentation Date Problem Resolution...

Страница 39: ..._______________ Fax ___________________ Work Done By ___________________________________ Name Plate Information Model ________________________________________ Volts ___________ Hertz __________ Phase...

Страница 40: ...o the nearest authorized motor service station Greenheck will not be responsible for any removal or installation costs Due to continuing research Greenheck reserves the right to change specifications...

Отзывы:

Похожие инструкции для IGX