23

Fire Ready Hood

Cleaning the Hood

To remove built up grease and cooking debris, clean 
the unit thoroughly with mild detergent and water.  Be 
careful when using abrasive cleaning pads as they may 
scratch or mar the stainless steel surfaces. The grease 
entrapment filter, front discharge grille and grease 
tray are dishwasher safe. The carbon filter cannot be 
washed and should be replaced periodically as needed.

Inspect the nozzle caps

The nozzle caps should be inspected and cleaned.  All 
five (5) nozzles should have protective caps installed. 
If necessary, remove the caps and check for build up 
of debris or any signs of clogging of the nozzle orifice. 
If clogging is suspected, remove the nozzle with a 
7/16-inch wrench, and flush with hot water until it flows 
freely through the nozzle.

Replace the nozzle and protective cap.

Replacement caps and nozzle O-rings are available 
from Greenheck or through your representatives.

Inspect Fusible Link System*

Periodic inspection of the fusible link system ensures 
the unit is ready to work in the case of a fire. 

1.  Place safety pin 

in tank valve.

2. Remove tank 

from hood.

3. Remove 

tension from 
cable system 
by loosening the turnbuckle.

4.  If the fusible links need to be replaced, call 1-800-

355-5354 or contact your representative.

5.  Inspect pulleys and cable. Pulleys should rotate 

freely and cable should be flexible. Everything should 
be free of grease build-up.

6.  Tighten the turnbuckle, reapplying tension to the 

stainless steel rope, making sure the cable is running 
through the pulleys properly and there are no kinks or 
knots.

7.  Reposition the tank.

8.  Remove safety pin from tank valve.

*Each fusible link is date-stamped and must be replaced 
if expired or after 12 months of use.

Inspection Procedures

Maintaining the System

WARNING

The protective caps stay on the nozzles at all times. In 
the event of a discharge, the caps will blow off.

WARNING

If grease build-up on the cable system is not kept to 
a minimum, the cable could become stiff and will not 
discharge the suppressant in the event of a fire.

10 Year Maintenance

Hydrostatic testing and new liquid agent, or tank 
replacement is recommended at ten-year intervals. The 
manufactured date is stamped on the top of the tank. 
This should be performed by an authorized technician 
or at the manufacturer’s facilities. Material safety data 
sheets are available from Greenheck.

WARNING

Rubber gloves and safety glasses should be worn 
during service or inspection of the tank. If contact 
with the chemical agent skin or eyes occurs, flush 
immediately with water for 15 minutes. If irritation 
persists, contact a physician. If taken internally, do not 
induce vomiting. Dilute with water or milk and contact 
a physician.

Lighting

Illumination is provided by a 60 watt medium-base 
shatterproof incandescent light bulb. To replace, make 
sure the light switch is in the “OFF” position and then 
gently unscrew the bulb. (Bulb: 60A15/TF)

Removing the Extinguisher Tank

1.  Lower the hood to its service position

2.  Insert the safety pin in the valve head so that 

accidental release of the suppressant does not occur.

3.  Unplug the pressure switch wire and move it out of 

the way for now.

4.  Disconnect the discharge hose from its fitting located 

inside the unit closest to the user. 

5.  Unscrew the two wingnuts holding the bracket for 

the tank.

6.  Lift the tank out of the hood.

7.  To replace the tank, simply reverse these steps. 

Pressure 

Gaug

g

e

Discharge 

Ho

Ho

se

se

Safety

y

 

Pin

Tan

nk 

Valv

lve

Pre

essure 

Sw

witch

Mo

Mo

un

unt

ting

ng 

Br

Br

ac

ac

ke

ket

Actuator arm 

unde

d

r tension

in

in r

r

ea

eady

dy p

p

osit

t

io

io

n

®

Содержание GRRS

Страница 1: ...ssociation NFPA and the American Society of Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities To reduce the risk of fire or electric shock do not use this range hood with an additional speed control device Ducted fans must always be vented to the outdoors...

Страница 2: ... accepting delivery Alert the carrier of any damage detected The customer will make notation of damage or shortage of items on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier If damaged immediately contact your Greenheck Representative Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation U...

Страница 3: ...ional 6 ft shielded control wire for plug and play connection Electrical disconnect box optional 6 ft shielded control wire for plug and play connection 8 ft of metal clad wire for gas disconnect electrical disconnect connection marked with black tape Remote switches ADA optional Manual Pull Kit optional consisting of the following Pull Box 1 Pull Face 1 Elbow Pulley 3 25 ft Cable and Pin The Cloc...

Страница 4: ...e to Fan provided Power Disconnect Cable provided 110 VAC Supply Cable provided Wall Mount Fan Box with Access Cover for Service and Mounting provided Wall Mount Fan Box with Access Cover for Service and Mounting provided Cabinet Wall Cap by others Range Hood provided Airflow 3 x 12 in Ductwork Soffit Power Disconnect Cable provided 110 VAC Supply Cable provided Cabinet Range Hood provided Airflow So...

Страница 5: ... 35 feet Yes Exterior Wall Fan Vertical Duct 550 20 feet Maximum duct length equals horizontal and vertical duct runs plus duct components such as fittings elbows and transitions For installations requiring vertical duct venting to an inline fan and NFPA 101 compliance the hood should be adapted from a 7 inch round duct access hole to a minimum 12 inch duct For installations requiring vertical duct...

Страница 6: ...h the fan box Accessories Location restrictions will apply if the hood system supplied is provided with any of the optional accessories ClockBox Remote ADA Switches Manual Pull Station 2 Attach square duct collar to the bottom of the fan box with included hardware 3 Attach the fan box to the mounting bracket with included 8 32 nuts then complete the installation on the manual pull kit conduit and ...

Страница 7: ...ting points must be secured to studs or drywall hangers C Rear access to junction box connection D Primary access point for connections to junction box E Secondary access point for connections to hood options accessories F Additional mounting points Secure minimum of three 3 screws per row Cabinet Front Cabinet Front Cabinet Bottom Electrical Access Hole 7 inch Round Duct Access Hole C L 5 15 16 i...

Страница 8: ...ove the safety key from the actuator arm by rotating and lifting straight upwards The system will not actuate without completing steps 4 and 5 6 Rotate hood to wall and thread the three thumb nuts to the bolts in the mounting plate Check page 17 for location of thumb nuts Installing Hood onto Mounting Bracket 4 Remove the safety pin identified with the yellow CAUTION flag from the trigger on top of ...

Страница 9: ...inlet and outlet flanges Wall Mounted Fan Fasten the fan box to an external wall via the four 0 27 inch mounting holes Run electrical through the 0 81 inch hole towards the top right corner of the box Attach ductwork using duct sealant caulk or tape to all seams to prevent air leakage and maximize air performance For best results use as few elbows or transitions as possible If necessary long radius...

Страница 10: ...e of the face plate Given this the hole should be about 6 3 8 by 8 3 4 inch The relay box has been designed to fit in a standard 2x4 studded wall 2 If you haven t already done so run wiring from the junction box location on the unit mounting plate to the power disconnect box location and string through one of the knockouts in the box 3 Make all wiring connections and secure face plate to box in wal...

Страница 11: ...nd Pin to hood Thread the cable through the conduit with the pin reaching the unit Remove the grease filter In the upper right corner find the two pulleys as illustrated Hold the rear most pulley in place From the top of the unit replace its pin with the one on the cable Push the pin through the pulley until you hear it click in place Go back to the actuator arm and rehook cable onto the arm Step 4 ...

Страница 12: ...reaker to prevent electrical shock when accessing electrical connections All field installation and wiring of electrical equipment must be done to meet NEC and local codes Electrical Installation Range Supply Line 208 220 VAC 50A max supplied by others Hood Supply 110 120 VAC 15A Metal clad wire from 110 120 VAC supply line 12 2 8 ft length marked with red tape supplied by Greenheck Run metal clad...

Страница 13: ...120 VAC Supply Line Red Tape Green Ground Wire nut inside power disconnect box Green Ground Black Hot 110 120 VAC 14 2 Hood White Neutral Black Hot 110 120 VAC Junction Box White Neutral Contactor 50A Supplied Power Disconnect Box 8 x 6 x 4 Back Support Mounting Bracket GND NEUT HOT GND NEUT HOT H N H H H Metal Clad Wire from 110 120 VAC Supply Line Red Tape 6 Position Orange Connector 6 Position ...

Страница 14: ...r one connection or both depending on your situation When there is a fault a buzzer in the unit will sound and the power disconnect will turn off Local Alarm Connection Connect to output Y0 and common C0 Remote Alarm Connection Connect to output Y1 and common C1 To connect to the alarms it is preferred that you use a spade terminal connector supplied but a stripped wire is acceptable Connecting th...

Страница 15: ...ow Blow MP1 Main Power Connector FP2 Fan Connector SW1 Main Power Switch SW2 Light Switch SW3 Service Switch SW4 Reset Switch SW5 Optional ADA Light SW6 Optional ADA Fan HSW1 Hose Switch HITH1 High Temp Thermostat 190 F LOTH1 2 Low Temp Thermostat 150 F FSP1 Fan Speed Controller 4 0 FLA FAN Inline or Recirc Fan CAP1 For Recirc Fan 10 UF M1 Stove Disconnect 40 FLA 50 A RES LIGHT Hood Light 60 WATT ...

Страница 16: ...l system is not enabled and this reset button needs to be pressed In doing so the Status LED below the reset switch will turn from red to green Environmental Monitoring Pre Suppression Functions The controller operating system is designed to enhance the functionality of the unit and the safety of the cooking environment The system relies on input from a set of thermostats to control the fan and sh...

Страница 17: ... On ducted installations remove the two thumb nuts located at the top inside near the fan intake Slowly lower the unit 4 The unit will now freely pivot downward to a stop position A safety cable is provided to prevent the unit from falling or lowering too far 5 Place safety pin in the tank valve to avoid accidental discharge With the unit in this position basic servicing and cleaning may be perfor...

Страница 18: ...talled Remove the plastic break rod from the pull face with an allen wrench refer to manual pull station appendix for more detailed information on this Pull the handle to actuate the unit Refer to the Manual Pull Kit section on the method to return the pull station to an operational state 2 The unit can be actuated one of two ways A Cut Test Links Replace the actuator arm s safety key Loosen the t...

Страница 19: ...rn the service switch to off for normal operation NOTE LED will flash orange and green Service Switch in the OFF position LED Label Input Function Scenario LED State X0 Hose Switch Hose in place On Hose disconnected Off X1 Reset Switch When switch is depressed On Switch not pressed Off X2 Pressure Switch Pressure okay On Pressure failure Off X3 Service Switch Servicing unit On Normal operation Off ...

Страница 20: ...ns on for 3 minutes after you lower temperature or put red wire back on h Hood remains powered Self Monitoring System These functions are to be checked at start up Low Temperature Switches HOW TO TEST FUNCTION a Use heat gun on either left or right low temp switch b Fan turns on c Fan remains on for three minutes after temperature falls below 150ºF High Temperature and Low Pressure Switches HOW TO...

Страница 21: ...ing before attempting any cleaning Using water to clean any appliance that contains hot grease or cooking oils may result in violent steaming or splattering How to Reset the Suppression System Resetting and testing release mechanisms remote pull and fusible links Reset detection system by completing the following steps 1 Remove extinguisher tank 2 Make sure tension arm cable is in the released sla...

Страница 22: ... will energize into its normal operating open position 2 Examine burners for gaseous odor If gas odor exists turn off power switch which will cause the gas valve to close and shut off gas supply Clear gas fumes by opening windows and doors and then correct gas leak before proceeding 3 Reset gas valve again and if there is no gaseous odor pilot lights may be ignited at this time Gas stoves with a p...

Страница 23: ... or after 12 months of use Inspection Procedures Maintaining the System WARNING The protective caps stay on the nozzles at all times In the event of a discharge the caps will blow off WARNING If grease build up on the cable system is not kept to a minimum the cable could become stiff and will not discharge the suppressant in the event of a fire 10 Year Maintenance Hydrostatic testing and new liqui...

Страница 24: ...Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org As a result of our commitment to continuous improvement Greenheck reserves the right to chang...

Отзывы: