Grease Grabber Triple Play Kitchen Exhaust Pollution Control System

Installation

Rigging/Placing Equipment (See Figure #1)

1.  The unit is furnished with lifting lugs at the four 

corners and along the length as necessary.

2.  Lift into place using all the lifting lugs.
3.  Field weight will vary depending upon final 

selections such as fan type, accessories, etc. 
Approximate weights are shown in the table 
below.

4.  The unit can be positioned on a base or curb 

suitable for this purpose.

5.  The unit must be anchored to its base/curb.
6.  Alternatively, the unit may be suspended from 

an adequate overhead structure, using suitable 
undercarriage or hanging rods (by others). If the 
unit is suspended by hanging rods, minimum 
1/2 inch (12.7 mm) diameter threaded rod is to 
be used. All hanger brackets/lifting lugs must be 
used to ensure proper support of the unit. The 
unit must also be hung level to ensure proper 
operation.

7.  A service clearance of 36 inches must be 

provided on the access door side of the unit.

8.  A minimum 18-inch clearance must be 

maintained between this unit and any 
combustible material.

9.  The remote Filter Status Indicator (See Page 

6) should be located in an area convenient for 
monitoring by the cook staff. For details on wiring 
this item, refer to the Electrical Connections 
section on

 

this page.

Duct Connections

Ductwork must conform to the IMC and SMACNA 
guidelines.
As specified in NFPA 96, Ch. 7.5 (latest edition), 
exhaust duct systems must be constructed in the 
following manner; unless otherwise specified by the 
local authority having jurisdiction (AHJ):

Materials 
Ducts shall be constructed of and supported by 
carbon steel not less than 1.37 mm (0.054 in.) (No. 16 
MSG) in thickness or stainless steel not less than  
1.09 mm (0.043 in.) (No. 18 MSG) in thickness.

Installation
All seams, joints, penetrations, and duct to hood collar 
connections shall have a liquid-tight external weld.
An inlet transition is furnished to match the inlet duct 
size. The inlet transition is furnished with a listed duct 
access door for inspection and cleaning.
Units intended for indoor mounting are provided with a 
UL 762 listed exhaust fan with outlet mounting flange. 
Outlet ductwork from the exhaust fan is required to be 
per the above mentioned methods unless otherwise 
specified by the local authority having jurisdiction 
(AHJ).

Electrical Connections

Electrical wiring must conform to the equipment data 
plate information and to the NEC and local code 
requirements.

Motor
This unit is furnished with a remote-mounted motor 
starter and an ON/OFF disconnect switch mounted 
adjacent to the fan and factory-wired to the fan motor.
A 3-phase electrical supply must be field wired to the 
motor starter and from the motor starter to the ON/
OFF disconnect switch.
Refer to the applicable fan installation manual for 
detailed instructions on wiring the fan.

Remote Status Indicator
A single phase electrical supply must be field wired to 
the pressure switch enclosure (located on the access 
side of the Triple Play housing between filter stages 2 
and 3, adjacent to the exhaust fan). For wiring details, 
refer to the diagram on pages 8 and 9.

Unit Size

Approximate 

Weight (lbs)

Approximate 

Weight (kg)

10-10

1100

500

10-20

1600

727

10-30

2150

977

20-20

2600

1182

20-30

3500

1591

20-40

4200

1909

30-30

4700

2136

30-40

5700

2591

40-40

7300

3318

40-50

8000

3636

Содержание Grease Grabber 474753

Страница 1: ...afety precautions Improper installation can result in electric shock possible injury due to coming in contact with moving parts as well as other potential hazards Other considerations may be required if high winds or seismic activity are present If more information is needed contact a licensed professional engineer before moving forward Follow all local electrical and safety codes as well as the N...

Страница 2: ...ry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts allow cold parts to reach room temperature To dry parts and packages use a portable electric heater to get rid of any moisture buildup Leave coverings loose to permit air circulation and to allow for periodic inspection OUTDOOR Units designed for outdoor ap...

Страница 3: ...ion 5 Start Up 5 Filter Status Indicator 5 Filter Replacement 6 Carbon Panel Replacement 6 Maintenance 6 Regular Scheduled Maintenance 6 Replacement Filter Parts Ordering 6 Figures 1 and 2 7 Wiring Diagram 8 9 Maintenance Log 10 11 Warranty 12 NOTE Grease Grabber Triple Play must be connected to a listed exhaust hood assembly and must be installed in accordance with local building codes NFPA 96 an...

Страница 4: ... Materials Ducts shall be constructed of and supported by carbon steel not less than 1 37 mm 0 054 in No 16 MSG in thickness or stainless steel not less than 1 09 mm 0 043 in No 18 MSG in thickness Installation All seams joints penetrations and duct to hood collar connections shall have a liquid tight external weld An inlet transition is furnished to match the inlet duct size The inlet transition ...

Страница 5: ... in the proper sequence and proper direction of airflow for filter stages 1 2 3 stage 4 carbon panels are not subject to airflow direction Open the access doors Remove the filter compression plates at stages 1 2 3 4 Install filters and replace all 4 filter compression plates Compression plates must be in place to ensure proper filter sealing integrity Close and latch access doors Operation NOTE Pr...

Страница 6: ...odor breakthrough is first noticed When replacing carbon panels follow the instructions in the Operation section Filter Replacement Steps 2 10 There is no particular direction of airflow for carbon panels R R R CHANGE PRE FILTER CHANGE BAG FILTER CHANGE RIGID FILTER REMOTE FILTER STATUS INDICATOR R R R CHANGE PRE FILTER CHANGE BAG FILTER CHANGE RIGID FILTER REMOTE FILTER STATUS INDICATOR Maintenan...

Страница 7: ...ED STAGE 1 FILTER COMPRESSION PLATE STAGE 2 FILTER COMPRESSION PLATE STAGE 3 FILTER COMPRESSION PLATE STAGE 4 FILTER COMPRESSION PLATE ON OFF DISCONNECT Elevation View INLET TRANSITION OPTIONAL STAGE 3 FILTER PRESSURE SWITCH ENCLOSURE ACCESS DOOR SIDE STAGE 1 FILTER STAGE 2 FILTER STAGE 4 FILTER ACCESS DOOR ON OFF DISCONNECT Elevation View ...

Страница 8: ... CIRCUIT BREAKER 1101 L1 130CR1 L2 130CR2 T1 1102 T2 1122 112M L3 130CR3 T3 1142 122 T 0 5A 1102 H4 50VA FAN MOTOR 208 230 460V 60HZ 3PH 1725 RPM STEPDOWN TRANSFORMER PRIMARY FUSE 1301 1261 1261 124 126 128 130 132 130 SW OFF 4 3 ON XOO 1301 1TB2 124FU 0 6A 96 130CR4 1301 1TB5 1301 95 G 128 LT X1 X2 1262 1262 2TB1 C 130CR A1 1302 A2 1262 2TB2 INDICATOR LIGHT PRIMARY POWER 110 112 114 126 FAN CONTR...

Страница 9: ...61 3TB 2 1261 3TB 1 1261 4TB 1 1262 4TB 2 1262 4TB 3 1262 SERIES ADPS 05 2 N READ ACROSS BAG FILTER PRESSURE SWITCH SERIES ADPS 05 2 N ADJUSTABLE DIFFERENTIAL READ ACROSS RIGID FILTER PRESSURE SWITCH ADJUSTABLE DIFFERENTIAL NC NO 1 COM 3 2 NC NO 144DPS COM 3 1 2 3TB 6 1441 SERIES ADPS 03 2 N ADJUSTABLE DIFFERENTIAL PRESSURE SWITCH READ ACROSS PREFILTER COM NO NC 140DPS 1 136DPS 3 2 1401 3TB 5 1361...

Страница 10: ...____________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ ______________________...

Страница 11: ...____________________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ ______________...

Страница 12: ...be returned to the nearest authorized motor service station Greenheck will not be responsible for any removal or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo greenheck com Website www greenheck com Warranty AMCA Publication 410 96 Safety Practices fo...

Отзывы: