background image

Damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild 
detergents or solvents. If lubrication is desired for components such as axle bearings, do not use oil-based lubricants 
or any other lubricants that attract contaminants such as dust.
Dampers must be maintained, cycled, and tested at intervals not less than every six months and in accordance with the 
latest editions of NFPA 90A & 92A, UL864 and local codes.

Copyright © 2006 Greenheck Fan Corporation

462721 DFDR-XXX FS Rev. 4 December 2006

Damper troubleshooting

The following is a possible cause and correction list for common concerns with the dampers.

JO

JOPD
.BYJNVN

'MPPS3VOOFS

JO 

$FJMJOH3VOOFS

1BOIFBE

4DSFXT

JOPD

.BYJNVN

 NFUBMTUVET

JOPD

.BYJNVN

 NFUBMTUVET

JOPD

.BYJNVN

 XPPETUVET

JOPD

.BYJNVN

 XPPETUVET

JO 

Fig. 4

4

DFDR-XXX Blade orientation

Normal

30° Off Horizontal

(Maximum)

30° Off Horizontal

(Maximum)

Axle

Axle

Axle

30°

30°

Round duct connections shall be attached 
with #8 sheet metal screws as follows:

  •  Ducts 22 in. (559mm) dia. and smaller shall have three 

screws.

  •  Ducts larger than 22 in. (559mm) dia. and up to 

including 24 in. dia. shall have five screws.

Note:

 All breakaway connections described may 

have duct sealant, PA2084T Duct Sealant Adhesive 
manufactured by Precision or DP1010 Water Base Duct 
Sealant manufactured by Design Polymetrics, applied 
in accordance with SMACNA recommendations.

6. Round Duct Connections

Symptom

Possible Cause

Corrective Action

Damper does not fully open and/or fully 

close

Frame is out of round causing blades to 

interfere with frame

Adjust frame such that it is round

Screws interfere with blade

Locate screws and remove

Contaminants on damper

Clean with a non-oil based solvent (see 

Damper Maintenance)

Link separated

Heat

Replace link

Содержание DFDR-XXX

Страница 1: ...ntinuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 Classification R13317 DFDR XXX SSDFDR XXX FDR XXX and SSFDR XXX Model Dampers are intended for installation in accordance with fire damper requirements established by National ...

Страница 2: ...red to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design 7 Caulking is not allowed between the damper sleeve and the wall or floor opening annular space However caulking may be applied to the retaining plates and a field applied sealant may b...

Страница 3: ...BLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an option The retai...

Страница 4: ...P D BYJNVN XPPE TUVET JO P D BYJNVN XPPE TUVET JO Fig 4 4 DFDR XXX Blade Orientation Normal 30 Off Horizontal Maximum 30 Off Horizontal Maximum Axle Axle Axle 30 30 Round duct connections shall be attached with 8 sheet metal screws as follows Ducts 22 in 559mm dia and smaller shall have three screws Ducts larger than 22 in 559mm dia and up to including 24 in dia shall have five screws NOTE All bre...

Отзывы: